Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

S7-300 CPU 31xC 和 CPU 31x

来源: | 作者:佚名 | 发布时间 :2023-11-20 | 982 次浏览: | 🔊 Click to read aloud ❚❚ | Share:

Routing and data record routing

Routing is the transmission of data across network boundaries. Information can be sent from sender to receiver across several networks.

The data logging route is an extension of the common route. For example, when the programming device is not directly connected to the target device

PROFIBUS DP subnets, but when connected to the CPU's PROFINET interface, SIMATIC PDM will make

Record routes with data. The data sent through the data recording route includes parameters of the participating field devices (slave stations)

Configuration, and device-specific information (e.g., set values, limit values, etc.). Data records the destination address structure of the route

Depends on the content of the data, i.e. the secondary station receiving the data.

When a programming device is assigned a different subnet from the target slave station, the data record route can also be read using the programming device

Set of parameters that already exist on the field device, edit them, and return them to the field device.

The field devices themselves do not need to support data record routing because they do not forward the received information.

Clock synchronization

1:intro

The CPU interface supports clock synchronization. The CPU can be programmed to act as a time master (with a default synchronization interval)

Interval) or time to run from the station.

Default value: No clock synchronization

Set synchronization mode

In the properties dialog box of HW Config, set the synchronization mode as follows:

In AS (on the central I/O bus) : Tab → Diagnostics/Clock (Tab → Diagnostics/Clock)

(Also applicable to MPI on CPU without DP interface)

● For MPI/DP or DP interface: Tab → Clock

● For PROFINET interface: Tab → Clock synchronization


2: interface

The following interfaces support clock synchronization:

● MPI interface

The CPU can be configured as either a time master or a time slave.

● DP interface

The CPU can be configured as either a time master or a time slave.

● PROFINET interface

The clock is synchronized with the CPU on the client through NTP.

● On the automation system in the central rack

The CPU can be configured as either a time master or a time slave.

Instructions

On many of these interfaces, the CPU cannot be used as a time slave.

CPU as time slave station

When acting as a time slave, a CPU receives synchronization frames only from a time master and uses that time as an internal time for that CPU

Between.

The CPU serves as the time master

When acting as a time master, the CPU broadcasts clock-sync frames at set synchronization intervals to synchronize them in the subnet to which they are connected

It stands.

Requirement: The CPU clock is no longer in the default state. The clock must be set at least once.

Clock synchronization as a time master begins with:

● After this time is initialized by SFC 0 "SET_CLK" or programming device function

● Use another time master, provided that the CPU is also programmed as an MPI/DP or PROFINET interface

Time operates from the station.

Instructions

The real-time clock of the CPU is not set in the following cases:

 before delivery

 after the mode selector switch is reset to factory Settings

 After firmware update

3. Point-to-point connection

Stats:

Point-to-point connections allow data to be exchanged over serial interfaces. Point-to-point connections can be used to interconnect programmable controllers, computations

Computer or third party system with communication function. It can also be adjusted according to the procedures of the communication partner.

3.1 Data Consistency

Stats:

A data area is consistent if it can be read or written to in the operating system as a block. Station to station

The data exchanged centrally between them should belong to a whole and originate from a processing cycle, that is, the data is consistent. If user

Programs that include programmed communication capabilities (for example, using XSEND/XRCV to access shared data) can pass

The "BUSY" parameter itself coordinates access to the corresponding data area.

Use the PUT/GET function

For some S7 communication functions that do not require blocks in CPU (server mode) user programs (e.g.,

In terms of PUT/GET or write/read access via OP communication, the scope of data consistency must be considered during programming.

The PUT/GET function of the S7 communication or the read/write variable operation through the OP communication are executed at the cycle control point of the CPU

Fine. To guarantee the defined hardware interrupt response time, the communication variables need to be in the form of blocks of up to 240 bytes, to/from

The copied user memory in the operating system loop control point is continuously copied. There is no guarantee for larger data areas

Data consistency.

Using PUT/GET functions and "Prioritized OCM communication"

If the operation is configured as "OCM communication by priority", the specified data consistency is lost (see the chapter "OP Communication (page 80)"). Therefore, data consistency must be ensured through user programs.

Keep the following consistent:

● Byte, word, double-word access (e.g. LMDx)

● SFC 14 "DPRD_DAT"

● SFC 15 "DPWR_DAT"

SFC 81 "UBLKMOV" (for copying up to 512 bytes of data)

It should also be understood that if OCM Communication by Priority is configured, the communication will not be changed at the loop control point

Quantities are continuously copied to/from working memory in blocks of up to 240 bytes. Therefore, it should be done while the user program is running

Copy the data.

                                                                                    Quantity name

                                                                                    ① Analog input and analog output

                                                                                    ② Digital input

                                                                                    ③ digital output

3.2 SNMP Communication Service

availability

SNMP V1, MIB-II communication services can be used with integrated PROFINET interfaces and using version 2.2 or later

Firmware for the CPU.

Stats

SNMP (Simple Network Management Protocol) is the standard protocol for TCP/IP networks.

3.3 Open communication over Industrial Ethernet

demand

● Since STEP 7 V5.4 + SP4

Feature

Cpus with integrated PROFINET interfaces support over industrial Ethernet starting with firmware V2.3.0 or V2.4.0

Open communication function (referred to as: Open IE communication)

Open IE communication provides the following services:

● Connection-oriented protocols

- TCP compliant with RFC 793, connection type B#16#01, firmware V2.3.0 and later

- TCP compliant with RFC 793, connection type B#16#11, firmware V2.4.0 and later

- ISO-on-TCP compliant with RFC 1006, firmware V2.4.0 and higher

● No connection protocol

- UDP compliant with RFC 768, firmware V2.4.0 and later

Attributes of the communication protocol

The following protocol types are included in data communication:

● Connection-oriented protocols:

These protocols establish a (logical) connection to a communication partner before the data transfer and then after the transfer is complete

The connection needs to be closed. When the security of data transmission is particularly important, connection-oriented protocols are used. Usually pass

Multiple logical connections can be established over a single physical cable.

FB for open communication over "Industrial Ethernet" supports the following connection-oriented protocols:

- TCP compliant with RFC 793 (connection types B#16#01 and B#16#11)

- ISO-on-TCP according to RFC 1006 (connection type B#16#12)

● No connection protocol:

These protocols can work without establishing a connection. This means there is no need to establish and terminate connections to remote partners

Answer. Connectionless protocols do not require confirmation to transmit data to remote partners; Therefore, data transmission is not secure.

FB for open communication over industrial Ethernet supports the following connectionless protocols:

- UDP compliant with RFC 768 (connection type B#16#13)


How to communicate with Open IE?

To allow the exchange of data with other communication partners, STEP 7 provides the following FB and under Communication Blocks in the Standard Library

UDT:

● Connection-oriented protocols: TCP, ISO-on-TCP

- FB 63 "TSEND" for sending data

- FB 64 "TRCV" for receiving data

- FB 65 "TCON" for connection

- FB 66 "TDISCON" for disconnection

- UDT 65 "TCON_PAR", whose data structure allows the connection to be parameterized

● No connection protocol: UDP

- FB 67 "TUSEND" for sending data

- FB 68 "TURCV" for receiving data

- FB 65 "TCON" for establishing local communication access points

- FB 66 "TDISCON" for parsing local communication access points

- UDT 65 "TCON_PAR", whose data structure can be parameterized to local communication access points

- UDT 66 "TCON_ADR" with remote partner addressing parameter data structure

Operator controls and indicators for CPU 313C-2 DP

                                                                                            Quantity name

                                                                                            ① Status and error indicators

                                                                                            ② Slot of SIMATIC MMC card (including eject device)

                                                                                            ③ Integrated input and output terminals

                                                                                            ④ Power connection

                                                                                            ⑤ 2. Interface X2 (DP)

                                                                                            ⑥ 1. Interface X1 (MPI)

                                                                                            ⑦ Mode selector

A block of data for parameterization

A block of data for parameterizing TCP and ISO-on-TCP connections

To use TCP and ISO-on-TCP configuration connections, you need to create a number that contains UDT 65 "TCON_PAR" medians

According to the structure of DB. This data structure contains all the parameters needed to establish the connection. Each connection requires such a number

According to the structure, you can arrange it in the global data store.

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

A block of data used to parameterize local communication access points using UDP

To assign parameters to the local communication access point, create one that contains the UDT 65 "TCON_PAR" data structure

DB. This data structure contains the parameters needed to establish a connection between the user program and the communication layer of the operating system

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

Instructions

Setting Connection Instructions (UDT 65)

You need to enter the communication interface in the "local_device_id" parameter of UDT65 "TCON_PAR" (for example

B#16#03: Communication via IE interface integrated with CPU 319-3 PN/DP).


Establish communication connection

● Suitable for TCP and ISO-on-TCP

Both communication partners call FB 65 "TCON" to establish a connection. Define which communication partner is used as master during parameterization

Dynamic communication endpoints and which are used as passive communication endpoints. To determine the number of possible connections, see your CPU's technology

The technical specifications.

The CPU automatically monitors and maintains active connections.

If the connection is interrupted, for example due to an open circuit or a telecommunication partner, the active party will attempt to re-establish the connection

Answer. You don't have to call FB 65 "TCON" again.

The active connection is terminated by calling FB 66 "TDISCON" or when the CPU is in STOP mode. Want to re-

To establish a connection, you must call FB 65 "TCON" again.

● Suitable for UDP

Both communication partners call FB 65 "TCON" to set up their local communication access point. This will be in the user program and operation

Connections are established between the communication layers of the system. Connections to remote partners are not established.

The local access point is used to send and receive UDP packets.

Distinguish between PROFINET IO and PROFINET CBA features

                                           PROFINET IO and CBA represent automation equipment for "industrial Ethernet" from two different perspectives.

Component-based automation divides the entire device into different functions. These functions are configured and programmed separately.

The device view provided by PROFINET IO is very similar to the PROFIBUS view. You can continue to configure and configure individual programmable controllers


  • Eaton XV-102-B6-35MQR-10-PLC Touch Panel
  • Omron ZFX-C15 Vision Sensor Controller
  • Kyosan PHS-4C-AN1 Servo Control Power Supply
  • Omron NX-ECC201 EtherCAT Coupler Unit
  • Omron C20-CPU83E CPU Unit 3G2C7-CPU83E
  • Omron FZ-SQ100F Vision Sensor Camera
  • Siemens 6SL3352-6BE00-0AA1 Power Supply Board
  • ABB AO815 3BSE052605R1 Analog Output Module
  • Siemens C98043-A1200-L Control Card
  • Allen-Bradley 1336-BDB-SP72D Gate Drive PCB
  • ST2000 34 Algorab Graphic PLC Terminal
  • OMRON C200HW-PRM21 Profibus DP Module
  • Siemens 2020964-001 DPM Base Board
  • OMRON CJ1W-V600C11 ID Controller Unit
  • Telemecanique TSX7 Series PLC Module
  • Okuma 1911-2861-0236049 Graphic Card Module
  • Parker HPD2S2N Servo Driver
  • OMRON FQ2-D31 Touch Finder Vision Sensor
  • OMRON C500-LK007 Host Link Unit
  • OMRON CJ1W-SCU32 Serial Communication Unit
  • Edwards C41901000 24V Solenoid Valve
  • ABB Procontic CS31 07 KR 91 PLC Controller
  • Siemens 7KG7750-0AA01-0AA0 Power Meter
  • Demag NC4K Compact PLC Controller
  • ABB SAPC 35 PAC/PP8482 Pulse Amplifier Board
  • Yaskawa SGMGH-09DCA6H-OY Servo Motor 850W
  • Saia PCD4.M445 Processor Module PLC
  • Yaskawa SGDH-04AE Servo Drive 400W 200V
  • Omron H8PR-24 Cam Positioner
  • Omron F150-C10E-2 Vision Sensor
  • OMRON 3G3MX2-A4015-E Inverter
  • Pro face GP577R-TC11 HMI
  • Pro face GP477R-EG11 HMI
  • ABB Pluto S20 V2 CFS Safety PLC
  • Siemens A5E00825002 IGD Board
  • Sakae SH40JHK-ZU-3S1R3G-10621B Joystick
  • Siemens 3RK1105-1AE04-0CA0 Safety Relay
  • Allen Bradley 1775-MEF Memory Module
  • OMRON CS1H-CPU63-H PLC CPU Unit
  • OMRON F150-C15E-3 Vision Sensor
  • Omron CJ1W-DA041 Analog Output Module
  • Saia PCD4.M440 PLC Module PCD4.M44
  • Steiel S595 PH Industrial Controller
  • VT650 PC Windows 2000 HMI Panel PC
  • Omron C200H-AD003 Analog Input Module
  • Omron CJ1W-V600C11 ID Sensor Unit
  • Coherent 250W Laser Adjustable Lens Head
  • Omron CQM1-AD042 Analog Input Module
  • SICK XKS09-HTBM-S02 Wire Draw Absolute Encoder
  • Omron 3F88L-P3A-E Cam Positioner PLC
  • OMRON R88M-H1K130 Servo Motor
  • SIEMENS 6ES7 331-7KB01-0AB0 SM331 Analog Input Module
  • LANDIS PCD4.M110 Processor Module
  • OMRON NT631C-ST151-EV2 HMI Touch Screen
  • TE.CO Grey Cable TFX 4G 1.5 ST 564mt UNEL Grey
  • OMRON R88D-H310G Servo Drive
  • ABB SACE SM3 630 630A PLC Switch
  • OMRON DRT2-AD04H Analog Input Terminal
  • OMRON FZ-SQ100F Vision Sensor
  • OMRON CP1E-NA20DT1-D CPU Unit PLC
  • Omron ZFX-C25-CD Vision Controller PNP 2-Camera
  • Omron ZFV-NX1 Smart Vision Sensor CCD Camera
  • GE Multilin F60 Feeder Management Relay UR Series
  • Omron C500-NC222-E Positioning Module 2 Axis
  • Omron C200PC-ISA01-E SYSMAC Board PLC ISA
  • Saia PCD2.W610 Analog Output Module 4 Channels
  • Kollmorgen SERVOSTAR 606 N1 Servo Drive Danaher Motion
  • Biviator RW 3089 CPU Module Industrial Controller
  • Santerno Sinus IFDEV 400T-7.5 AC Drive 8.4kW 380V
  • Omron C60H-C1DR-DE-V1 Programmable Logic Controller
  • SOCOMEC SIRCO 0T510058 1250A Switch
  • REER ARGOLUX ASR 1218 ASE 1218 Safety PLC
  • GE TLINE TCP11G-04-0345 Operator Panel
  • OMRON CJ1G-CPU43H V2.0 PLC CPU
  • OMRON FQ-MS125-ECT Vision System
  • OMRON FND-X06H Position Driver
  • OMRON CPM2C-S110C-DRT Compact PLC
  • YASKAWA SGMAH-02AAA61D-OY 200W Servo Motor
  • OMRON CJ1G-CPU43H V3.0 PLC CPU
  • Schneider PM89M0024 PLC I/O Module 4-20mA
  • Omron H8PR-16P-300 Rotary Positioner
  • Saia PCD2 AP103 PLC Module AP103 V3.5
  • Parker HPD5/K005 Servo Driver
  • Omron ES1-LWT Infrared Temperature Sensor
  • Yaskawa CIMR-V7AZ21P5 VFD 220V 1.5kW
  • Yaskawa CIMR-P5C43P7 Inverter 400V 3.7kW
  • Omron 3F88L-160 Programmable Cam Positioner
  • Yaskawa SGDH-02AE-OY Servo Driver 200V
  • ABB SACE SH800 800A 660V Switch Disconnector
  • Samsung CSDJ-10BX2 AC Servo Drive 1KW 220V
  • OMRON CQM1-DA021 DA022 IPS02 Analog Output PLC
  • OMRON CS1W-EIP21 EtherNet/IP Unit
  • SIEMENS S5 395 6ES5376-0AA11 CPU Module
  • GE Multilin 269-10C-HI Motor Management Relay
  • SIEMENS 3VT9500-3MQ00 Motor Operator
  • OMRON FQ2-S25100F Smart Camera
  • TOSHIBA VFPS1 4220PL WP 22kW Inverter
  • KEB COMBIVERT F4 13.F4.4C1D-4025 5.5kW Inverter
  • VISOLUX SLVA-4Kplus-2528 Photoelectric Sensor
  • PRO-FACE GP370-LG21-24VP HMI Touch Screen
  • YASKAWA SGMPH-04AAA61D-OY 200V 400W Servo Motor
  • YASKAWA SGMPH-08A1A41 750W Servo Motor with Gearbox
  • OMRON C60K-CDR-D K-Type CPU PLC
  • OMRON CS1W-AD081-V1 Analog Input Module
  • OMRON CP1H-X40DT-D Compact PLC
  • OMRON 3G3SV-BB007-E 0.75kW Inverter
  • YASKAWA SGDH-10DE-OY 1kW Servo Pack
  • OMRON C60H-C5DR-DE-V1 SYSMAC CPU PLC
  • OMRON C60H-C5DR-DE-V1 SYSMAC CPU PLC
  • OMRON 3G3MV-P10CDT3-E RS422/485 Inverter PLC Board
  • OMRON C200PC-ISA02-DRM-E SYSMAC Board PLC with Floppy & Operator Panel
  • OMRON 3G3SV-BB007-E 0.75kW Inverter
  • OMRON CP1H-X40DT-D Compact PLC
  • OMRON CS1W-AD081-V1 Analog Input Module
  • OMRON C60K-CDR-C K-Type CPU PLC
  • YASKAWA SGMPH-08A1A41 750W Servo Motor with Gearbox
  • YASKAWA SGMPH-04AAA61D-OY 200V 400W Servo Motor
  • OMRON CJ1W-DA041 Analog Output Module
  • OMRON C60H-C5DR-DE-V1 SYSMAC CPU PLC
  • OMRON 3G3MV-P10CDT3-E RS422/485 Inverter PLC Board
  • OMRON C200PC-ISA02-DRM-E SYSMAC Board PLC
  • Omron CQM1H-MAB42 Analog I/O Board
  • Omron C200PC-ISA02-DRM-E SYSMAC Board
  • Oriental Motor ARD-C CM10-1 Stepping Driver
  • EVA 915.85.003 Embedded CPU Module
  • Omron C60H-C1DR-DE-V1 PLC CPU
  • TE.CO TFX 4G10 Industrial Power Cable
  • Siemens 6SL3120-2TE15-0AA4 Motor Module