Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

S7-300 CPU 31xC 和 CPU 31x

F: | Au:佚名 | DA:2023-11-20 | 1049 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Routing and data record routing

Routing is the transmission of data across network boundaries. Information can be sent from sender to receiver across several networks.

The data logging route is an extension of the common route. For example, when the programming device is not directly connected to the target device

PROFIBUS DP subnets, but when connected to the CPU's PROFINET interface, SIMATIC PDM will make

Record routes with data. The data sent through the data recording route includes parameters of the participating field devices (slave stations)

Configuration, and device-specific information (e.g., set values, limit values, etc.). Data records the destination address structure of the route

Depends on the content of the data, i.e. the secondary station receiving the data.

When a programming device is assigned a different subnet from the target slave station, the data record route can also be read using the programming device

Set of parameters that already exist on the field device, edit them, and return them to the field device.

The field devices themselves do not need to support data record routing because they do not forward the received information.

Clock synchronization

1:intro

The CPU interface supports clock synchronization. The CPU can be programmed to act as a time master (with a default synchronization interval)

Interval) or time to run from the station.

Default value: No clock synchronization

Set synchronization mode

In the properties dialog box of HW Config, set the synchronization mode as follows:

In AS (on the central I/O bus) : Tab → Diagnostics/Clock (Tab → Diagnostics/Clock)

(Also applicable to MPI on CPU without DP interface)

● For MPI/DP or DP interface: Tab → Clock

● For PROFINET interface: Tab → Clock synchronization


2: interface

The following interfaces support clock synchronization:

● MPI interface

The CPU can be configured as either a time master or a time slave.

● DP interface

The CPU can be configured as either a time master or a time slave.

● PROFINET interface

The clock is synchronized with the CPU on the client through NTP.

● On the automation system in the central rack

The CPU can be configured as either a time master or a time slave.

Instructions

On many of these interfaces, the CPU cannot be used as a time slave.

CPU as time slave station

When acting as a time slave, a CPU receives synchronization frames only from a time master and uses that time as an internal time for that CPU

Between.

The CPU serves as the time master

When acting as a time master, the CPU broadcasts clock-sync frames at set synchronization intervals to synchronize them in the subnet to which they are connected

It stands.

Requirement: The CPU clock is no longer in the default state. The clock must be set at least once.

Clock synchronization as a time master begins with:

● After this time is initialized by SFC 0 "SET_CLK" or programming device function

● Use another time master, provided that the CPU is also programmed as an MPI/DP or PROFINET interface

Time operates from the station.

Instructions

The real-time clock of the CPU is not set in the following cases:

 before delivery

 after the mode selector switch is reset to factory Settings

 After firmware update

3. Point-to-point connection

Stats:

Point-to-point connections allow data to be exchanged over serial interfaces. Point-to-point connections can be used to interconnect programmable controllers, computations

Computer or third party system with communication function. It can also be adjusted according to the procedures of the communication partner.

3.1 Data Consistency

Stats:

A data area is consistent if it can be read or written to in the operating system as a block. Station to station

The data exchanged centrally between them should belong to a whole and originate from a processing cycle, that is, the data is consistent. If user

Programs that include programmed communication capabilities (for example, using XSEND/XRCV to access shared data) can pass

The "BUSY" parameter itself coordinates access to the corresponding data area.

Use the PUT/GET function

For some S7 communication functions that do not require blocks in CPU (server mode) user programs (e.g.,

In terms of PUT/GET or write/read access via OP communication, the scope of data consistency must be considered during programming.

The PUT/GET function of the S7 communication or the read/write variable operation through the OP communication are executed at the cycle control point of the CPU

Fine. To guarantee the defined hardware interrupt response time, the communication variables need to be in the form of blocks of up to 240 bytes, to/from

The copied user memory in the operating system loop control point is continuously copied. There is no guarantee for larger data areas

Data consistency.

Using PUT/GET functions and "Prioritized OCM communication"

If the operation is configured as "OCM communication by priority", the specified data consistency is lost (see the chapter "OP Communication (page 80)"). Therefore, data consistency must be ensured through user programs.

Keep the following consistent:

● Byte, word, double-word access (e.g. LMDx)

● SFC 14 "DPRD_DAT"

● SFC 15 "DPWR_DAT"

SFC 81 "UBLKMOV" (for copying up to 512 bytes of data)

It should also be understood that if OCM Communication by Priority is configured, the communication will not be changed at the loop control point

Quantities are continuously copied to/from working memory in blocks of up to 240 bytes. Therefore, it should be done while the user program is running

Copy the data.

                                                                                    Quantity name

                                                                                    ① Analog input and analog output

                                                                                    ② Digital input

                                                                                    ③ digital output

3.2 SNMP Communication Service

availability

SNMP V1, MIB-II communication services can be used with integrated PROFINET interfaces and using version 2.2 or later

Firmware for the CPU.

Stats

SNMP (Simple Network Management Protocol) is the standard protocol for TCP/IP networks.

3.3 Open communication over Industrial Ethernet

demand

● Since STEP 7 V5.4 + SP4

Feature

Cpus with integrated PROFINET interfaces support over industrial Ethernet starting with firmware V2.3.0 or V2.4.0

Open communication function (referred to as: Open IE communication)

Open IE communication provides the following services:

● Connection-oriented protocols

- TCP compliant with RFC 793, connection type B#16#01, firmware V2.3.0 and later

- TCP compliant with RFC 793, connection type B#16#11, firmware V2.4.0 and later

- ISO-on-TCP compliant with RFC 1006, firmware V2.4.0 and higher

● No connection protocol

- UDP compliant with RFC 768, firmware V2.4.0 and later

Attributes of the communication protocol

The following protocol types are included in data communication:

● Connection-oriented protocols:

These protocols establish a (logical) connection to a communication partner before the data transfer and then after the transfer is complete

The connection needs to be closed. When the security of data transmission is particularly important, connection-oriented protocols are used. Usually pass

Multiple logical connections can be established over a single physical cable.

FB for open communication over "Industrial Ethernet" supports the following connection-oriented protocols:

- TCP compliant with RFC 793 (connection types B#16#01 and B#16#11)

- ISO-on-TCP according to RFC 1006 (connection type B#16#12)

● No connection protocol:

These protocols can work without establishing a connection. This means there is no need to establish and terminate connections to remote partners

Answer. Connectionless protocols do not require confirmation to transmit data to remote partners; Therefore, data transmission is not secure.

FB for open communication over industrial Ethernet supports the following connectionless protocols:

- UDP compliant with RFC 768 (connection type B#16#13)


How to communicate with Open IE?

To allow the exchange of data with other communication partners, STEP 7 provides the following FB and under Communication Blocks in the Standard Library

UDT:

● Connection-oriented protocols: TCP, ISO-on-TCP

- FB 63 "TSEND" for sending data

- FB 64 "TRCV" for receiving data

- FB 65 "TCON" for connection

- FB 66 "TDISCON" for disconnection

- UDT 65 "TCON_PAR", whose data structure allows the connection to be parameterized

● No connection protocol: UDP

- FB 67 "TUSEND" for sending data

- FB 68 "TURCV" for receiving data

- FB 65 "TCON" for establishing local communication access points

- FB 66 "TDISCON" for parsing local communication access points

- UDT 65 "TCON_PAR", whose data structure can be parameterized to local communication access points

- UDT 66 "TCON_ADR" with remote partner addressing parameter data structure

Operator controls and indicators for CPU 313C-2 DP

                                                                                            Quantity name

                                                                                            ① Status and error indicators

                                                                                            ② Slot of SIMATIC MMC card (including eject device)

                                                                                            ③ Integrated input and output terminals

                                                                                            ④ Power connection

                                                                                            ⑤ 2. Interface X2 (DP)

                                                                                            ⑥ 1. Interface X1 (MPI)

                                                                                            ⑦ Mode selector

A block of data for parameterization

A block of data for parameterizing TCP and ISO-on-TCP connections

To use TCP and ISO-on-TCP configuration connections, you need to create a number that contains UDT 65 "TCON_PAR" medians

According to the structure of DB. This data structure contains all the parameters needed to establish the connection. Each connection requires such a number

According to the structure, you can arrange it in the global data store.

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

A block of data used to parameterize local communication access points using UDP

To assign parameters to the local communication access point, create one that contains the UDT 65 "TCON_PAR" data structure

DB. This data structure contains the parameters needed to establish a connection between the user program and the communication layer of the operating system

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

Instructions

Setting Connection Instructions (UDT 65)

You need to enter the communication interface in the "local_device_id" parameter of UDT65 "TCON_PAR" (for example

B#16#03: Communication via IE interface integrated with CPU 319-3 PN/DP).


Establish communication connection

● Suitable for TCP and ISO-on-TCP

Both communication partners call FB 65 "TCON" to establish a connection. Define which communication partner is used as master during parameterization

Dynamic communication endpoints and which are used as passive communication endpoints. To determine the number of possible connections, see your CPU's technology

The technical specifications.

The CPU automatically monitors and maintains active connections.

If the connection is interrupted, for example due to an open circuit or a telecommunication partner, the active party will attempt to re-establish the connection

Answer. You don't have to call FB 65 "TCON" again.

The active connection is terminated by calling FB 66 "TDISCON" or when the CPU is in STOP mode. Want to re-

To establish a connection, you must call FB 65 "TCON" again.

● Suitable for UDP

Both communication partners call FB 65 "TCON" to set up their local communication access point. This will be in the user program and operation

Connections are established between the communication layers of the system. Connections to remote partners are not established.

The local access point is used to send and receive UDP packets.

Distinguish between PROFINET IO and PROFINET CBA features

                                           PROFINET IO and CBA represent automation equipment for "industrial Ethernet" from two different perspectives.

Component-based automation divides the entire device into different functions. These functions are configured and programmed separately.

The device view provided by PROFINET IO is very similar to the PROFIBUS view. You can continue to configure and configure individual programmable controllers


  • ABB 3HAC031851-001 SMB Unit Technical Manual
  • Fuji NB1U56X-01 Programmable Controller Guide
  • Siemens 6AG1153-2BA02-7XB0 SIPLUS IM 153-2 Manual
  • Beckhoff EL6631 PROFINET Terminal Manual
  • Lenze E82EV302-4C Frequency Inverter Manual
  • Siemens 6SE7038-6EK84-1JC2 IGD8 Board Specifications
  • Pilz 774595 Safety Relay Specifications
  • Fanuc A20B-8200-0847 PLC Board Specification
  • Allen Bradley 1785-L60B/E PLC CPU Manual
  • PASABAN MC-2006 03 PLC Card Specifications
  • B&R X20CP1382 PLC Control Module X20 CPU
  • B&R X20DC2395 PLC Module Digital Output
  • AS-2P-70M-B Industrial PLC Communication Cable 70M
  • Siemens 6ES7136-6BA00-0CA0 PLC Module ET 200SP
  • Siemens 1FK7083-5AF71-1EB3 Servo Motor SIMOTICS S
  • WAGO 750 Series I/O Modules 750-842 750-530 750-430 750-602 750-514 750-600
  • Microchip TC9401CPD F/V Converter 100kHz 14DIP
  • Mitsubishi GT2310-VTBA GT2310-VTBD HMI Touch Screen 10.4 Inch
  • Siemens 3RT2036-1AN20 AC Contactor SIRIUS
  • Mitsubishi GT2708 HMI Touch Screen GT2708-VTBA VTBD STBA STBD
  • Siemens 6FC5110-0CB01-0AA0 CNC PLC CPU
  • ABB SINT4130C PCB Board
  • Omron NX1P2-1040DT PLC Controller
  • Fuji FRN3.7C1S-2J VFD
  • PLC-60/75 /E2UK Shielded Braided Cable
  • Omron CJ1W-NC434 Position Control Unit
  • Omron NX-AD2208 Analog Input Module
  • PASABAN MC-2006 03 PLC Card
  • Schneider 9038CR34 Pressure Switch
  • Pilz 240340 Safety Control Module
  • Mitsubishi A2NCPU Programmable Controller MELSEC
  • Mitsubishi Alpha XL Alarm Modem M20 Expansion
  • AutomationDirect D0-06DD2-D PLC DL06 Controller
  • Toshiba COMW01-21 PCB Control Board Turbine
  • Siemens 6FX1122-1AC02 Coupling Module SINUMERIK
  • Omron CVM1-CPU21-V2 CPU Unit Programmable
  • Beckhoff EL7041 Stepper Motor Terminal EtherCAT
  • B&R X20AI4622 Analog Input Module 4 Channels
  • OAT PMC25.2-003 Programmable Controller Module
  • Fanuc A16B-2200-0350 Graphic Board Series 16
  • Eaton Cutler Hammer 6-26-2 Contactor Contact Kit
  • Omron D4SL-NSK10-LK-K Safety Switch
  • Siemens C98043-A7001-L24 CUD1 Control Board
  • Mitsubishi A2NCPUR21-S1 PLC Module
  • National Instruments NI-9242 4-channel analog input module
  • BEMAC UST-202-D PLC Interface Board
  • Omron CJ1W-DA08C Analog Output Module
  • Mitsubishi QX521 CNC Interface Board
  • Schneider BMEP586040 High-Performance PLC Processor
  • Emerson 5X00875G01 Process Control PLC
  • Siemens SIMODRIVE 611 Power Module 6SN1145-1AA01-0AA0
  • Siemens 840C NC-CPU 486DX4 6FC5110-0BB04-0AA1
  • Mitsubishi GT2708 Series Operation Panel Touch HMI
  • Fanuc A04B-0103-C220 Programmable Controller Module
  • IFM CR2530 Programmable Controller for Mobile Automation
  • Omron FH-3050 Vision Controller i7-2715QE High Performance
  • National Instruments NI-9242 4-Ch Analog Input Module
  • B&R X20AI4632 Analog Input Module 4 Channels
  • Pilz 773600 Input Module Safety Automation
  • Panasonic AFPX-C60P Programmable Controller PLC
  • Siemens 6ES7414-2XL07-0AB0 S7-400 CPU Manual
  • Cutler Hammer WM34V Interlock Kit Manual
  • Pilz 777587 Safety Relay Specifications
  • Omron CJ2H-CPU64-EIP CPU Module Manual
  • B&R X20AI1744-3 Analog Input Module Guide
  • Schneider LC1G185BEEA Contactor Specification
  • Sharp LM64P101 LCD Screen Specifications
  • B&R X20AT4222 Temperature Module Guide
  • Mitsubishi A2UCPU-S1 Controller Specifications
  • Stein Sohn E 083.1 Rack Module Technical Guide
  • Omron CK3W-AX1515N Motion Controller
  • Schneider TSXP572634M PLC Processor
  • Epson RAIOC-33 Programmable Controller
  • GRID T&D iRTUe-D1R1-W.125 I/O Module
  • Fanuc A20B-2002-0520 Control Board
  • B&R X20IF1030 Interface Module
  • Schneider ATV320U55N4B VFD
  • Omron NA5-9W001B-V1 HMI Touchscreen
  • Mitsubishi A2NCPU PLC CPU Unit
  • Omron CJ2M-CPU34 PLC CPU Unit
  • Omron NS12-TS01B-V2 Touch Screen HMI
  • Mitsubishi FX3GE-24MT/ESS PLC Controller
  • Grundig NEA02 AES 0 PLC I O Module
  • Beckhoff EP3204-0002 EtherCAT Box Module
  • Mitsubishi MDS-A-CV-220 Power Supply Unit
  • MCX20B2 080G0330 Motion Controller
  • Toyo Keiki P CARD5 Interface Board YH-212
  • National Instruments NI 9242 Analog Input Module
  • B&R 3AM055.6 PLC Module
  • Omron CJ1W-ETN21 Ethernet Module PLC
  • Allen-Bradley 2711P-T15C4A7 PanelView Plus 1500 Guide
  • Pilz 777602 Safety Module XV1P Specifications
  • NI cFP-2220 and cFP Modules Technical Guide
  • Keyence XG-EC80 Camera Input Unit Overview
  • Dynatronix CRS9-10 DC Power Supply Manual
  • Omron G3PW-A220EC-S-FLK Power Controller Manual
  • EVO SP SYSTEM PLC Control Panel Overview
  • B&R X20IF10G3-1 Interface Module Specifications
  • NL8060BC21-11 Industrial LCD Screen Specification
  • SK-G9-FAN1-F6 Cooling Fan Technical Specifications
  • US Drives 3000-4220-4-4 PLC Add-on Module
  • Allen-Bradley 2002-NX70-HSC4 High-Speed Counter
  • Schneider TM258LF42DR PLC Controller
  • Harris 8800-00002-02 PLC Power Control Center
  • NLT NL8060BC21-11C 8.4 LCD Panel
  • ABB PLUTO S20 V2 CFS Safety PLC
  • Omron NS12-TS00B-V2 NS12-TS00B-ECV2 HMI
  • 7-29 10 00 A PLC Expansion Module
  • B&R X20DC2395 PLC Module
  • Omron NE1A-SCPU02 Network Controller
  • GE IC200UEX624-C VersaMax Micro PLC
  • Rexroth GIV50-11 Position Limit Switch Assembly
  • B&R X20SLX410 Safety Logic Module
  • Omron CJ1W-NC433 Position Control Unit
  • Inovance AM600-CPU1608TP PLC Controller
  • ABB Pluto S20 V2 CFS Safety PLC
  • Omron CJ1W-NC113 Position Control Unit
  • Grundig NEA02 AES 0 PLC I O Module
  • Fanuc A16B-2202-0432 Control PCB Board
  • Siemens 6SN1124-1AA00-0DA0 Simodrive LT Module
  • B&R X20AO2632 Analog Output Module Specifications
  • Georges Renault 6159187760 PLC Board Technical Guide
  • IDEC PLC FC6A-D32K3CEE MicroSmart Controller Manual
  • 6ES7226-6BA32-0XB0 Fail-Safe Digital Input Guide
  • Programmable Controller PLC EC20-4040BRA Specification
  • Grundig PLC NEA02 AES 0 I/O Card Specification
  • Seiki POS-M 10-22-01 Card Positioning Board Manual
  • Ormec Systems PMC960 Motion Controller CPU Guide