Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

S7-300 CPU 31xC 和 CPU 31x

F: | Au:佚名 | DA:2023-11-20 | 1121 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Routing and data record routing

Routing is the transmission of data across network boundaries. Information can be sent from sender to receiver across several networks.

The data logging route is an extension of the common route. For example, when the programming device is not directly connected to the target device

PROFIBUS DP subnets, but when connected to the CPU's PROFINET interface, SIMATIC PDM will make

Record routes with data. The data sent through the data recording route includes parameters of the participating field devices (slave stations)

Configuration, and device-specific information (e.g., set values, limit values, etc.). Data records the destination address structure of the route

Depends on the content of the data, i.e. the secondary station receiving the data.

When a programming device is assigned a different subnet from the target slave station, the data record route can also be read using the programming device

Set of parameters that already exist on the field device, edit them, and return them to the field device.

The field devices themselves do not need to support data record routing because they do not forward the received information.

Clock synchronization

1:intro

The CPU interface supports clock synchronization. The CPU can be programmed to act as a time master (with a default synchronization interval)

Interval) or time to run from the station.

Default value: No clock synchronization

Set synchronization mode

In the properties dialog box of HW Config, set the synchronization mode as follows:

In AS (on the central I/O bus) : Tab → Diagnostics/Clock (Tab → Diagnostics/Clock)

(Also applicable to MPI on CPU without DP interface)

● For MPI/DP or DP interface: Tab → Clock

● For PROFINET interface: Tab → Clock synchronization


2: interface

The following interfaces support clock synchronization:

● MPI interface

The CPU can be configured as either a time master or a time slave.

● DP interface

The CPU can be configured as either a time master or a time slave.

● PROFINET interface

The clock is synchronized with the CPU on the client through NTP.

● On the automation system in the central rack

The CPU can be configured as either a time master or a time slave.

Instructions

On many of these interfaces, the CPU cannot be used as a time slave.

CPU as time slave station

When acting as a time slave, a CPU receives synchronization frames only from a time master and uses that time as an internal time for that CPU

Between.

The CPU serves as the time master

When acting as a time master, the CPU broadcasts clock-sync frames at set synchronization intervals to synchronize them in the subnet to which they are connected

It stands.

Requirement: The CPU clock is no longer in the default state. The clock must be set at least once.

Clock synchronization as a time master begins with:

● After this time is initialized by SFC 0 "SET_CLK" or programming device function

● Use another time master, provided that the CPU is also programmed as an MPI/DP or PROFINET interface

Time operates from the station.

Instructions

The real-time clock of the CPU is not set in the following cases:

 before delivery

 after the mode selector switch is reset to factory Settings

 After firmware update

3. Point-to-point connection

Stats:

Point-to-point connections allow data to be exchanged over serial interfaces. Point-to-point connections can be used to interconnect programmable controllers, computations

Computer or third party system with communication function. It can also be adjusted according to the procedures of the communication partner.

3.1 Data Consistency

Stats:

A data area is consistent if it can be read or written to in the operating system as a block. Station to station

The data exchanged centrally between them should belong to a whole and originate from a processing cycle, that is, the data is consistent. If user

Programs that include programmed communication capabilities (for example, using XSEND/XRCV to access shared data) can pass

The "BUSY" parameter itself coordinates access to the corresponding data area.

Use the PUT/GET function

For some S7 communication functions that do not require blocks in CPU (server mode) user programs (e.g.,

In terms of PUT/GET or write/read access via OP communication, the scope of data consistency must be considered during programming.

The PUT/GET function of the S7 communication or the read/write variable operation through the OP communication are executed at the cycle control point of the CPU

Fine. To guarantee the defined hardware interrupt response time, the communication variables need to be in the form of blocks of up to 240 bytes, to/from

The copied user memory in the operating system loop control point is continuously copied. There is no guarantee for larger data areas

Data consistency.

Using PUT/GET functions and "Prioritized OCM communication"

If the operation is configured as "OCM communication by priority", the specified data consistency is lost (see the chapter "OP Communication (page 80)"). Therefore, data consistency must be ensured through user programs.

Keep the following consistent:

● Byte, word, double-word access (e.g. LMDx)

● SFC 14 "DPRD_DAT"

● SFC 15 "DPWR_DAT"

SFC 81 "UBLKMOV" (for copying up to 512 bytes of data)

It should also be understood that if OCM Communication by Priority is configured, the communication will not be changed at the loop control point

Quantities are continuously copied to/from working memory in blocks of up to 240 bytes. Therefore, it should be done while the user program is running

Copy the data.

                                                                                    Quantity name

                                                                                    ① Analog input and analog output

                                                                                    ② Digital input

                                                                                    ③ digital output

3.2 SNMP Communication Service

availability

SNMP V1, MIB-II communication services can be used with integrated PROFINET interfaces and using version 2.2 or later

Firmware for the CPU.

Stats

SNMP (Simple Network Management Protocol) is the standard protocol for TCP/IP networks.

3.3 Open communication over Industrial Ethernet

demand

● Since STEP 7 V5.4 + SP4

Feature

Cpus with integrated PROFINET interfaces support over industrial Ethernet starting with firmware V2.3.0 or V2.4.0

Open communication function (referred to as: Open IE communication)

Open IE communication provides the following services:

● Connection-oriented protocols

- TCP compliant with RFC 793, connection type B#16#01, firmware V2.3.0 and later

- TCP compliant with RFC 793, connection type B#16#11, firmware V2.4.0 and later

- ISO-on-TCP compliant with RFC 1006, firmware V2.4.0 and higher

● No connection protocol

- UDP compliant with RFC 768, firmware V2.4.0 and later

Attributes of the communication protocol

The following protocol types are included in data communication:

● Connection-oriented protocols:

These protocols establish a (logical) connection to a communication partner before the data transfer and then after the transfer is complete

The connection needs to be closed. When the security of data transmission is particularly important, connection-oriented protocols are used. Usually pass

Multiple logical connections can be established over a single physical cable.

FB for open communication over "Industrial Ethernet" supports the following connection-oriented protocols:

- TCP compliant with RFC 793 (connection types B#16#01 and B#16#11)

- ISO-on-TCP according to RFC 1006 (connection type B#16#12)

● No connection protocol:

These protocols can work without establishing a connection. This means there is no need to establish and terminate connections to remote partners

Answer. Connectionless protocols do not require confirmation to transmit data to remote partners; Therefore, data transmission is not secure.

FB for open communication over industrial Ethernet supports the following connectionless protocols:

- UDP compliant with RFC 768 (connection type B#16#13)


How to communicate with Open IE?

To allow the exchange of data with other communication partners, STEP 7 provides the following FB and under Communication Blocks in the Standard Library

UDT:

● Connection-oriented protocols: TCP, ISO-on-TCP

- FB 63 "TSEND" for sending data

- FB 64 "TRCV" for receiving data

- FB 65 "TCON" for connection

- FB 66 "TDISCON" for disconnection

- UDT 65 "TCON_PAR", whose data structure allows the connection to be parameterized

● No connection protocol: UDP

- FB 67 "TUSEND" for sending data

- FB 68 "TURCV" for receiving data

- FB 65 "TCON" for establishing local communication access points

- FB 66 "TDISCON" for parsing local communication access points

- UDT 65 "TCON_PAR", whose data structure can be parameterized to local communication access points

- UDT 66 "TCON_ADR" with remote partner addressing parameter data structure

Operator controls and indicators for CPU 313C-2 DP

                                                                                            Quantity name

                                                                                            ① Status and error indicators

                                                                                            ② Slot of SIMATIC MMC card (including eject device)

                                                                                            ③ Integrated input and output terminals

                                                                                            ④ Power connection

                                                                                            ⑤ 2. Interface X2 (DP)

                                                                                            ⑥ 1. Interface X1 (MPI)

                                                                                            ⑦ Mode selector

A block of data for parameterization

A block of data for parameterizing TCP and ISO-on-TCP connections

To use TCP and ISO-on-TCP configuration connections, you need to create a number that contains UDT 65 "TCON_PAR" medians

According to the structure of DB. This data structure contains all the parameters needed to establish the connection. Each connection requires such a number

According to the structure, you can arrange it in the global data store.

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

A block of data used to parameterize local communication access points using UDP

To assign parameters to the local communication access point, create one that contains the UDT 65 "TCON_PAR" data structure

DB. This data structure contains the parameters needed to establish a connection between the user program and the communication layer of the operating system

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

Instructions

Setting Connection Instructions (UDT 65)

You need to enter the communication interface in the "local_device_id" parameter of UDT65 "TCON_PAR" (for example

B#16#03: Communication via IE interface integrated with CPU 319-3 PN/DP).


Establish communication connection

● Suitable for TCP and ISO-on-TCP

Both communication partners call FB 65 "TCON" to establish a connection. Define which communication partner is used as master during parameterization

Dynamic communication endpoints and which are used as passive communication endpoints. To determine the number of possible connections, see your CPU's technology

The technical specifications.

The CPU automatically monitors and maintains active connections.

If the connection is interrupted, for example due to an open circuit or a telecommunication partner, the active party will attempt to re-establish the connection

Answer. You don't have to call FB 65 "TCON" again.

The active connection is terminated by calling FB 66 "TDISCON" or when the CPU is in STOP mode. Want to re-

To establish a connection, you must call FB 65 "TCON" again.

● Suitable for UDP

Both communication partners call FB 65 "TCON" to set up their local communication access point. This will be in the user program and operation

Connections are established between the communication layers of the system. Connections to remote partners are not established.

The local access point is used to send and receive UDP packets.

Distinguish between PROFINET IO and PROFINET CBA features

                                           PROFINET IO and CBA represent automation equipment for "industrial Ethernet" from two different perspectives.

Component-based automation divides the entire device into different functions. These functions are configured and programmed separately.

The device view provided by PROFINET IO is very similar to the PROFIBUS view. You can continue to configure and configure individual programmable controllers


  • Basler Electric Phase Directional Overcurrent Relay BE1-Z2JA0N2F
  • Basler SSR125-12 Static Voltage Regulator
  • Basler Electric KR7F VOLTAGE REGULATOR 9116200100
  • BASLER ELECTRIC BE1-59N-A8E-E1L-N0S1F Ground Overvoltage Relay
  • Basler SR8A2B06B3A Static Voltage Regulator
  • BASLER ELECTRIC BE1-81O/UT3EE1KA7N1F Under/Over Frequency Relay
  • Basler MOC2107 Output Module
  • Basler 9125600102 Control Module
  • BASLER ELECTRIC BE1-81T1EE1EA2N0F
  • Basler BE3-25A Time Overcurrent Relay
  • Basler Electric CBS 212 Current Boost System 9 2650 00 100 120/240 VAC 50/60Hz
  • Basler Electric BE1-27 Under Voltage Relay A3EC1JA0N5F
  • Basler BE1-32R Power Relay B2EE1PA0N1F
  • Basler DECS100-B15 Automatic Voltage Regulator
  • Basler SR8A-2B15B3A Static Voltage Regulator
  • Basler AVC63-4 Analog Voltage Regulator
  • Basler UFOV 260 A Overvoltage Module
  • Basler SR4A-2B16B3A Static Voltage Regulator
  • Basler SR4A-2B16B3E Static Voltage Regulator
  • Basler SCA1300-32GM CCD Camera
  • Basler BE34062001 G18 Transformer
  • Basler BE1-87T Transformer Differential Relay
  • Basler 9 2849 00 101 DECS Power Module
  • Basler RAL6144-16GM Line Scan Camera
  • Basler 9269101107 Voltage Regulator Board
  • Basler BE1-851 Overcurrent Relay
  • Basler SR32A-2B13B3E Static Voltage Regulator
  • Basler 9 2007 00 100 Current Boost System CBS 305
  • Basler DECS-100-B11 Automatic Voltage Regulator
  • Basler BE127 Under Voltage Relay
  • Basler 3300C03B1028-G01 Spike Suppressor
  • Basler SSR 125-12 Static Voltage Regulator
  • Basler SCA1300-32GM CCD Camera Lens Enclosure
  • Basler BE32965001 Transformer Timer Kit
  • Basler D90 96801 100 PCB Card
  • Basler BE1-81-T1E-E1C-A0N1F / 9106400 Underfrequency Relay
  • Pro-Face Basler AGP3600-T1-D24 HMI Touch
  • Basler SR4A2B10B1A Static Voltage Regulator
  • Basler SR8A2B05B3A Static Voltage Regulator
  • Basler BE1-25 Time Overcurrent Relay M1FA6PA4S0F
  • Basler SR4A2B05B3E Static Voltage Regulator
  • Basler DECS-200-2L Digital Excitation Control
  • Basler BE303280001 Control Transformer
  • Basler 9262103004 Voltage Regulator Board For Basler DECS-400
  • Basler ICRM-7 Inrush Current Reduction Module
  • Basler BE1-32R Power Relay
  • BASLER ELECTRIC KR4F VOLTAGE REGULATOR 9042600100 600V 50/60Hz
  • Basler 9222600101 Power Module
  • Basler SR8A-2B15B3A Static Voltage Regulator
  • BASLER BE1-87G G1E A1L A0N1P Generator Differential Relay w/ Reactor 9170818100
  • Basler 9284900101 DECS Power Module
  • Basler PRS250 Veri-Sync Relay
  • Basler BE 12296 001 Transformer
  • Basler 905970-104 Rev.M Voltage Regulator
  • Basler BE1-87T Transformer Differential Relay
  • Basler SR8A-2B15B3A Static Voltage Regulator
  • Basler SR32A2B05B3E Static Voltage Regulator
  • Basler SR4A-2B16B3A Static Voltage Regulator
  • Basler SR32A-2B13B3E Static Voltage Regulator
  • Basler KR4F Voltage Regulator 9042600100
  • Basler SSR 32-12 Static Voltage Regulator 400Hz
  • Basler CBS 212A Current Boost System
  • Basler MVC236 Manual Control Module
  • Basler UFOV Protective Module 9040000100
  • Basler SSR 125-12 Static Voltage Regulator
  • Basler SR4A2B10A3E Static Voltage Regulator
  • Basler BE1-25 Solid State Time Overcurrent Relay
  • Basler MVC 232 Manual Voltage Control Module
  • Basler PRS 250 Veri-Sync Relay
  • Basler UFOV 260A Under Frequency Over Voltage Relay
  • Basler RUL2098-10GC Load Relay
  • Basler 9 1049 04 100 PC Board
  • Basler 125-12 Static Voltage Regulator
  • Basler PRS 250 Veri-Sync Relay
  • Basler 9185900102 SSR 125-12 Regulator
  • Basler BE12819001 Reactor
  • Teradyne 535-100-00 Power Supply
  • Basler BE1-67 Directional OC Relay
  • Basler PRP110 Reverse Power Relay
  • Basler BE30631001 Isolation Transformer
  • Basler DECS-200-2L Digital Excitation Control
  • Basler BE1-47N Voltage Phase Sequence Relay
  • Basler AEC63-7 Analog Excitation Controller 220-277V
  • Basler BE1-50/51B-107 Overcurrent Relay
  • Basler Electric BE1‑32R BE1‑E1P‑BON0F Protective Relay
  • Basler BE1-25 Solid State Time Overcurrent Relay M1EA6PA5S1F
  • Basler MVC 232 Manual Voltage Control Module 90 37000 103 60VAC 55VDC
  • Basler RAL6144-16GM Racer GigE Line Scan Camera
  • Basler SSR 63-12 Static Voltage Regulator
  • Basler BE1-51A Overcurrent Relay
  • Basler BE1-87T Solid State Protective Relay
  • Basler SR4A2B01B3A Static Voltage Regulator
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler TRR00696 Transformer 1KVA 115V
  • Basler DECS-100-B15 AVR Replacement
  • Basler BE1-27 Under-Voltage Relay
  • Basler ACA2000-50GM Interface Module
  • Basler AEC63-7 Analog Excitation Controller
  • Basler PRS 250 Veri-Sync Relay
  • Basler SR4A-2B15B3A Static Voltage Regulator
  • Basler BE1-32R Power Relay
  • Basler SR8A-2B06B3E Static Voltage Regulator
  • Basler BE1-81 O/U Frequency Relay
  • Basler BE1-51A-K2E-W6M-B1N0F Overcurrent Relay
  • Basler BE1-851 Overcurrent Relay G3A1S1 – 48-125V AC/DC
  • Basler BEI-51 Overcurrent Relay – NSN 5945-01-293-2363
  • Basler Electric L301KC Protective Relay – L301KC
  • Basler DECS-100-B15 Automatic Voltage Regulator – Generator AVR
  • Basler SR4A-2B15B3A Static Voltage Regulator – SR4A2B15B3A
  • Basler UF 312 Under Frequency Protective Module – 9094700100
  • Basler Electric MVC 232 Manual Control Module – 60VAC 55VDC 20A
  • Basler PRS 250 Veri-Sync Relay – Generator Synchronizing Relay
  • Basler DECS-100-A05 Digital Regulator Review
  • Basler AEM-2020 Analog Expansion Module Specs
  • Basler DECS-100-B15 Digital Excitation Specs
  • Basler Electric 9125600106 Regulator Component
  • Basler BE1-51A-K1E-W6M-B1N0F Overcurrent Relay
  • Basler MVC-301 MVC 300 Excitation Controller
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler 9-2849-00-101 Control Module
  • Basler BE1-51A Overcurrent Relay
  • Basler BE1-51/27R Overcurrent Relay
  • Basler BE1-51 Overcurrent Relay
  • Basler SR8A-2B15B3A Static Voltage Regulator
  • Basler BE32965001 Transformer and Timer Board
  • Basler 9174700100 EL200-7 Excitation Limiter
  • Basler BE2000E AVR Voltage Regulator
  • Basler BE1-87G Differential Relay