Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

S7-300 CPU 31xC 和 CPU 31x

F: | Au:佚名 | DA:2023-11-20 | 1231 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Routing and data record routing

Routing is the transmission of data across network boundaries. Information can be sent from sender to receiver across several networks.

The data logging route is an extension of the common route. For example, when the programming device is not directly connected to the target device

PROFIBUS DP subnets, but when connected to the CPU's PROFINET interface, SIMATIC PDM will make

Record routes with data. The data sent through the data recording route includes parameters of the participating field devices (slave stations)

Configuration, and device-specific information (e.g., set values, limit values, etc.). Data records the destination address structure of the route

Depends on the content of the data, i.e. the secondary station receiving the data.

When a programming device is assigned a different subnet from the target slave station, the data record route can also be read using the programming device

Set of parameters that already exist on the field device, edit them, and return them to the field device.

The field devices themselves do not need to support data record routing because they do not forward the received information.

Clock synchronization

1:intro

The CPU interface supports clock synchronization. The CPU can be programmed to act as a time master (with a default synchronization interval)

Interval) or time to run from the station.

Default value: No clock synchronization

Set synchronization mode

In the properties dialog box of HW Config, set the synchronization mode as follows:

In AS (on the central I/O bus) : Tab → Diagnostics/Clock (Tab → Diagnostics/Clock)

(Also applicable to MPI on CPU without DP interface)

● For MPI/DP or DP interface: Tab → Clock

● For PROFINET interface: Tab → Clock synchronization


2: interface

The following interfaces support clock synchronization:

● MPI interface

The CPU can be configured as either a time master or a time slave.

● DP interface

The CPU can be configured as either a time master or a time slave.

● PROFINET interface

The clock is synchronized with the CPU on the client through NTP.

● On the automation system in the central rack

The CPU can be configured as either a time master or a time slave.

Instructions

On many of these interfaces, the CPU cannot be used as a time slave.

CPU as time slave station

When acting as a time slave, a CPU receives synchronization frames only from a time master and uses that time as an internal time for that CPU

Between.

The CPU serves as the time master

When acting as a time master, the CPU broadcasts clock-sync frames at set synchronization intervals to synchronize them in the subnet to which they are connected

It stands.

Requirement: The CPU clock is no longer in the default state. The clock must be set at least once.

Clock synchronization as a time master begins with:

● After this time is initialized by SFC 0 "SET_CLK" or programming device function

● Use another time master, provided that the CPU is also programmed as an MPI/DP or PROFINET interface

Time operates from the station.

Instructions

The real-time clock of the CPU is not set in the following cases:

 before delivery

 after the mode selector switch is reset to factory Settings

 After firmware update

3. Point-to-point connection

Stats:

Point-to-point connections allow data to be exchanged over serial interfaces. Point-to-point connections can be used to interconnect programmable controllers, computations

Computer or third party system with communication function. It can also be adjusted according to the procedures of the communication partner.

3.1 Data Consistency

Stats:

A data area is consistent if it can be read or written to in the operating system as a block. Station to station

The data exchanged centrally between them should belong to a whole and originate from a processing cycle, that is, the data is consistent. If user

Programs that include programmed communication capabilities (for example, using XSEND/XRCV to access shared data) can pass

The "BUSY" parameter itself coordinates access to the corresponding data area.

Use the PUT/GET function

For some S7 communication functions that do not require blocks in CPU (server mode) user programs (e.g.,

In terms of PUT/GET or write/read access via OP communication, the scope of data consistency must be considered during programming.

The PUT/GET function of the S7 communication or the read/write variable operation through the OP communication are executed at the cycle control point of the CPU

Fine. To guarantee the defined hardware interrupt response time, the communication variables need to be in the form of blocks of up to 240 bytes, to/from

The copied user memory in the operating system loop control point is continuously copied. There is no guarantee for larger data areas

Data consistency.

Using PUT/GET functions and "Prioritized OCM communication"

If the operation is configured as "OCM communication by priority", the specified data consistency is lost (see the chapter "OP Communication (page 80)"). Therefore, data consistency must be ensured through user programs.

Keep the following consistent:

● Byte, word, double-word access (e.g. LMDx)

● SFC 14 "DPRD_DAT"

● SFC 15 "DPWR_DAT"

SFC 81 "UBLKMOV" (for copying up to 512 bytes of data)

It should also be understood that if OCM Communication by Priority is configured, the communication will not be changed at the loop control point

Quantities are continuously copied to/from working memory in blocks of up to 240 bytes. Therefore, it should be done while the user program is running

Copy the data.

                                                                                    Quantity name

                                                                                    ① Analog input and analog output

                                                                                    ② Digital input

                                                                                    ③ digital output

3.2 SNMP Communication Service

availability

SNMP V1, MIB-II communication services can be used with integrated PROFINET interfaces and using version 2.2 or later

Firmware for the CPU.

Stats

SNMP (Simple Network Management Protocol) is the standard protocol for TCP/IP networks.

3.3 Open communication over Industrial Ethernet

demand

● Since STEP 7 V5.4 + SP4

Feature

Cpus with integrated PROFINET interfaces support over industrial Ethernet starting with firmware V2.3.0 or V2.4.0

Open communication function (referred to as: Open IE communication)

Open IE communication provides the following services:

● Connection-oriented protocols

- TCP compliant with RFC 793, connection type B#16#01, firmware V2.3.0 and later

- TCP compliant with RFC 793, connection type B#16#11, firmware V2.4.0 and later

- ISO-on-TCP compliant with RFC 1006, firmware V2.4.0 and higher

● No connection protocol

- UDP compliant with RFC 768, firmware V2.4.0 and later

Attributes of the communication protocol

The following protocol types are included in data communication:

● Connection-oriented protocols:

These protocols establish a (logical) connection to a communication partner before the data transfer and then after the transfer is complete

The connection needs to be closed. When the security of data transmission is particularly important, connection-oriented protocols are used. Usually pass

Multiple logical connections can be established over a single physical cable.

FB for open communication over "Industrial Ethernet" supports the following connection-oriented protocols:

- TCP compliant with RFC 793 (connection types B#16#01 and B#16#11)

- ISO-on-TCP according to RFC 1006 (connection type B#16#12)

● No connection protocol:

These protocols can work without establishing a connection. This means there is no need to establish and terminate connections to remote partners

Answer. Connectionless protocols do not require confirmation to transmit data to remote partners; Therefore, data transmission is not secure.

FB for open communication over industrial Ethernet supports the following connectionless protocols:

- UDP compliant with RFC 768 (connection type B#16#13)


How to communicate with Open IE?

To allow the exchange of data with other communication partners, STEP 7 provides the following FB and under Communication Blocks in the Standard Library

UDT:

● Connection-oriented protocols: TCP, ISO-on-TCP

- FB 63 "TSEND" for sending data

- FB 64 "TRCV" for receiving data

- FB 65 "TCON" for connection

- FB 66 "TDISCON" for disconnection

- UDT 65 "TCON_PAR", whose data structure allows the connection to be parameterized

● No connection protocol: UDP

- FB 67 "TUSEND" for sending data

- FB 68 "TURCV" for receiving data

- FB 65 "TCON" for establishing local communication access points

- FB 66 "TDISCON" for parsing local communication access points

- UDT 65 "TCON_PAR", whose data structure can be parameterized to local communication access points

- UDT 66 "TCON_ADR" with remote partner addressing parameter data structure

Operator controls and indicators for CPU 313C-2 DP

                                                                                            Quantity name

                                                                                            ① Status and error indicators

                                                                                            ② Slot of SIMATIC MMC card (including eject device)

                                                                                            ③ Integrated input and output terminals

                                                                                            ④ Power connection

                                                                                            ⑤ 2. Interface X2 (DP)

                                                                                            ⑥ 1. Interface X1 (MPI)

                                                                                            ⑦ Mode selector

A block of data for parameterization

A block of data for parameterizing TCP and ISO-on-TCP connections

To use TCP and ISO-on-TCP configuration connections, you need to create a number that contains UDT 65 "TCON_PAR" medians

According to the structure of DB. This data structure contains all the parameters needed to establish the connection. Each connection requires such a number

According to the structure, you can arrange it in the global data store.

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

A block of data used to parameterize local communication access points using UDP

To assign parameters to the local communication access point, create one that contains the UDT 65 "TCON_PAR" data structure

DB. This data structure contains the parameters needed to establish a connection between the user program and the communication layer of the operating system

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

Instructions

Setting Connection Instructions (UDT 65)

You need to enter the communication interface in the "local_device_id" parameter of UDT65 "TCON_PAR" (for example

B#16#03: Communication via IE interface integrated with CPU 319-3 PN/DP).


Establish communication connection

● Suitable for TCP and ISO-on-TCP

Both communication partners call FB 65 "TCON" to establish a connection. Define which communication partner is used as master during parameterization

Dynamic communication endpoints and which are used as passive communication endpoints. To determine the number of possible connections, see your CPU's technology

The technical specifications.

The CPU automatically monitors and maintains active connections.

If the connection is interrupted, for example due to an open circuit or a telecommunication partner, the active party will attempt to re-establish the connection

Answer. You don't have to call FB 65 "TCON" again.

The active connection is terminated by calling FB 66 "TDISCON" or when the CPU is in STOP mode. Want to re-

To establish a connection, you must call FB 65 "TCON" again.

● Suitable for UDP

Both communication partners call FB 65 "TCON" to set up their local communication access point. This will be in the user program and operation

Connections are established between the communication layers of the system. Connections to remote partners are not established.

The local access point is used to send and receive UDP packets.

Distinguish between PROFINET IO and PROFINET CBA features

                                           PROFINET IO and CBA represent automation equipment for "industrial Ethernet" from two different perspectives.

Component-based automation divides the entire device into different functions. These functions are configured and programmed separately.

The device view provided by PROFINET IO is very similar to the PROFIBUS view. You can continue to configure and configure individual programmable controllers


  • Alcatel-Lucent 9396 Digital 2U NodeB Outdoor with Indoor Mainframe and Alarm Module
  • Alcatel Lucent MPX-16/64-T-L3 MPX1664TL3 Multiplexer Module
  • Alcatel Lucent 3EH73052AB Power Supply Module
  • Alcatel Lucent ASM2-155FM-2W-4C ASM2155FM2W4C Switch Fabric Module
  • Alcatel Lucent 3AL00124ABAB Interface Card
  • Alcatel-Lucent 1AB429380001 Cable Assembly
  • Alcatel Z24 3BA53065 Analog Extension Card 3BA53065AA
  • Alcatel-Lucent 9500-MPR 11GHz MPT-HC ODU Microwave Packet Radio 3DB20371ACAA01
  • Alcatel-Lucent RRH1900-4x45 Remote Radio Head
  • Alcatel-Lucent 3HE00028AA Ethernet Line Card
  • Alcatel-Lucent 3HE04939CE CWDM SFP Transceiver
  • Nokia Alcatel-Lucent 3FE66546AA Fan Module
  • Alcatel-Lucent SSP-6 Speech Signal Processor Board
  • Alcatel-Lucent 500-1113-212 Channel Bank Assembly
  • Alcatel-Lucent EZ32-2 Board 3BA23265ADKE 01
  • Alcatel-Lucent GSM-FM-2W-4C Filter Module
  • Alcatel-Lucent 3AL00378AF Interface Card
  • Alcatel-Lucent 3AL00124ABAC Interface Module
  • Alcatel-Lucent BJB1 PWPQALGAAG 48V Independent Microprocessor Board
  • Alcatel Lucent MDR-8000 Microwave Digital Radio MDR-8506-4 with 13 Modules
  • Alcatel Lucent 3AL00424AA Interface Card
  • Alcatel Lucent 3BA73012AB Power Supply Module
  • Alcatel Lucent ESX-100C-32W ESX100C32W Power Supply Module
  • Alcatel Lucent GSX-K-FM-2W GSXKFM2W Fan Module
  • Alcatel 8DG59247AA Optical Protection Switch Card
  • Alcatel Lucent 91-E03100-B 91E03100B Interface Module
  • Alcatel Lucent FSX-FM-1W FSXFM1W Fan Module
  • Alcatel Lucent RRH2X40-07L-AT Remote Radio Head
  • Alcatel-Lucent 9500-MPR MSS-8 Shelf 3DB18485CA
  • Alcatel Annecy ACP20 Vacuum Pump CP20
  • Alcatel-Lucent 9500 MPR P32E1DS1 E1 PDH Card
  • Alcatel-Lucent J98726AL-2 D4OI210DAA Module
  • Alcatel 409113651 RRH700L1 700MHz Remote Radio Head
  • Alcatel io2 3ba23050 PCB Card
  • Alcatel-Lucent MDR-8000 MDR-8706-8 Digital Radio
  • Alcatel-Lucent ACT2300M Turbo Pump Controller AF042134A
  • Alcatel-Lucent OmniPCX Office Medium PowerCPU PRA-TI
  • Alcatel-Lucent 9500 MPR 23GHz ODU 3DB23045HDAA01
  • Alcatel-Lucent 9500 MPR ODU Outdoor Unit 300 11GHz TX Low HP 3DB23035AAAA01
  • Alcatel-Lucent ECNT-C 3FE25676 BA AK 06 Termination Card
  • Alcatel Lucent MDR-8000 Microwave Digital Radio MDR-8606-45 with 13 Modules
  • Alcatel-Lucent 849144415 KS-24829L1 Remote Radio Head v1.4
  • Alcatel CFF 450 Turbo Pump Controller 137171
  • Alcatel-Lucent ACS108 109579896 004 Access Controller
  • Alcatel-Lucent OS6850-48 Network Switch with PS-126W-AC Power Supply
  • Alcatel Lucent DFP-CM-14B/2T Filter DCMA Base Station
  • Alcatel Lucent ESX-K100C32W4 ESXK100C32W4 Power Supply Module
  • Alcatel Lucent 91-E03100-A 91E03100A Interface Module
  • Alcatel-Lucent STGR-LIM-A2P-72-HBI ADSL2+ High Bandwidth Module
  • Alcatel-Lucent 9500 Microwave Packet Radio MPT-3DB20547BBAA02
  • Alcatel Lucent Enterprise 4049-4059 MMK Keyboard Console Kit
  • Alcatel-Lucent RRH4X40-1900 Remote Radio Head
  • Alcatel Lucent OS6450-P48 Switch
  • Alcatel Lucent 625617-000-001 Cable Assembly
  • Alcatel Lucent 108320 Module
  • Alcatel Lucent TN801B Board
  • Alcatel-Lucent RRH2X50-800 LTE Remote Radio Head
  • Alcatel Lucent CPU8 Board 3BA23258AB OmniPCX 4400
  • Alcatel-Lucent 3EM22617AAAE 9500 MPT-HL Microwave Radio Transceiver
  • Alcatel-Lucent CPU7-2 3BA23259AAAD 7750 SR Control Processor Module
  • Alcatel-Lucent 9500 Microwave Packet Radio MPT-3DB20371BCAA01
  • Alcatel-Lucent Enterprise 4059 MMK Keyboard + Phone PAC Kit
  • Alcatel-Lucent Nokia 3HE10329AA 7750 SR Series Router Module
  • Alcatel-Lucent 7705 SAR-W IP MPLS Service Aggregation Router 3HE07349AA
  • Alcatel-Lucent-Nokia 3HE08429AARC01 7750 SR SFM5-7 Switching Module
  • Alcatel-Lucent 3HE00272DB 7750 SR-7 DC Chassis with PEM3+EFT
  • Alcatel-Lucent ACT 1300M/1600M HT Turbo Pump Controller
  • Alcatel Lucent IMM48-1GB-TX 3HE03625AAG01 48-Port 7750 SR-12 Interface Module
  • Alcatel-Lucent AP-500 Wireless Access Point
  • Alcatel-Lucent ATP-150 Power Supply
  • Alcatel-Lucent 622-8603-012 Optical Transceiver
  • Alcatel-Lucent 270-0038-010 10.5 VDC Power Supply
  • Nokia 9500-MPR Microwave Radio Module XPIC-RPS/3DB20116BCAA01
  • Alcatel-Lucent 3DB19017AB EAS Access Switch v2
  • Alcatel-Lucent 3AL81072AA Matrix Enhanced Unit - Cross-Connect Module
  • Alcatel-Lucent MDR-8606-135 6GHz Digital Microwave Radio
  • Alcatel-Lucent 3EM09626AD RF Transmitter - MDR-8000 Component
  • Alcatel 3HE03619AAAF01 Network Module
  • Alcatel-Lucent 3EH76027AEJC OmniPCX Enterprise Communication Server
  • Alcatel-Lucent 9500 MPR 11GHz Microwave Link - 3DB22001DA
  • Alcatel-Lucent GSX-FM-4W - Gigabit Ethernet Fiber Module 4-Port
  • Alcatel-Lucent 270-0038-020 - Power Supply Interface Module
  • Alcatel-Lucent LNW64 - Network Processor Module for Switching Systems
  • Alcatel-Lucent 3DB19017AB - High-Density Interface Module Board
  • Valmet U4600063 - Industrial Automation Module
  • Valmet M851040 M1 MEMU Module - Memory and Expansion Unit
  • Metso Valmet A413016 NCU2 Board - Network Control Unit Model 17
  • Valmet A413115 TCU41 Board Ver.06 - Temperature Control Unit
  • Metso Valmet PEFT A413792 - Power Supply Module for Automation Systems
  • Valmet ABTU M2512201 - Analog Binary Termination Unit Module
  • Valmet ABMB MT036 PCB Card - Auxiliary Backplane Motherboard
  • Valmet A413345 FPUS Battery Backup Unit - Standby Power Module
  • Valmet A413060 DMU Rev 04 - Drive Monitor Unit Board
  • Valmet BOR82 A413292 - Binary Output Relay Module
  • Valmet A413383 Ver.04 ESW - Electronic Switching Module Board
  • Valmet Neles A415579 Valve Controller
  • Metso Valmet A413381 ESW Drive Board
  • Valmet ABTU Module 545266-2A 2-545264-2B - Analog Binary Termination Unit
  • Valmet ABMB MT838 PCB - Backplane Bus Mother Board
  • Valmet LEV-EL PG4 N1 H2S Sensor - 600mbar Gas Detector
  • Valmet ABMB MT940 PCB - Analogue Bus Mother Board Backplane
  • Valmet VAT65425921A MT241 PCB Board
  • Valmet A413310 VPU Power Unit - 230VAC 1.5A Automation Supply
  • Valmet Metso IOP303 Input Module 181504 - 32-Channel Digital Input
  • Valmet A413060 DMU Rev 07 - Data Management Unit
  • Valmet M851220 M1 PCB Card - Process Automation Interface Board
  • Valmet A413042 Ver.06 CPU
  • Valmet A413200-01 AIU 8 Analog Input Module
  • Basler DECS-250-CGCM-LN2SA1C Digital Excitation Control System
  • Valmet Automation PLC Module A413171
  • Valmet Automation 542852-3A Rack-Mount Cross Connect Panel
  • Valmet Marine Damatic M851565 Main Keyboard
  • Valmet TIU 6 Printed Circuit Board A413110
  • Metso Valmet U4440253V1.1 RMI CPU 300
  • Metso Valmet A413016 Ver.12 NCU2
  • Valmet M851565 Damatic Keyboard
  • Valmet ATB16-4 16 Channel Relay Card
  • Valmet Metso A413331 SPU Power Supply
  • Valmet PUD 10B Automation Control Rack
  • Valmet MT917 ABMB DMU PCB I/O Module
  • Valmet M851565 Damatic Keyboard Mkb2
  • Valmet EDS-518A-MM-SC Ethernet Gateway
  • Valmet 542836-6A PCB Card
  • Valmet ATB16-4/2 Terminal Board 9144047
  • Valmet ATB16-4 Controller Board 0-50°C 4-20mA Analog Output
  • Valmet 542852-3A Slot Rack Chassis Module
  • Valmet A413026 Ver.M1 FBC Board
  • Valmet IQ Basis Weight SH Sending Assembly A418081