Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

S7-300 CPU 31xC 和 CPU 31x

来源: | 作者:佚名 | 发布时间 :2023-11-20 | 912 次浏览: | Share:

Routing and data record routing

Routing is the transmission of data across network boundaries. Information can be sent from sender to receiver across several networks.

The data logging route is an extension of the common route. For example, when the programming device is not directly connected to the target device

PROFIBUS DP subnets, but when connected to the CPU's PROFINET interface, SIMATIC PDM will make

Record routes with data. The data sent through the data recording route includes parameters of the participating field devices (slave stations)

Configuration, and device-specific information (e.g., set values, limit values, etc.). Data records the destination address structure of the route

Depends on the content of the data, i.e. the secondary station receiving the data.

When a programming device is assigned a different subnet from the target slave station, the data record route can also be read using the programming device

Set of parameters that already exist on the field device, edit them, and return them to the field device.

The field devices themselves do not need to support data record routing because they do not forward the received information.

Clock synchronization

1:intro

The CPU interface supports clock synchronization. The CPU can be programmed to act as a time master (with a default synchronization interval)

Interval) or time to run from the station.

Default value: No clock synchronization

Set synchronization mode

In the properties dialog box of HW Config, set the synchronization mode as follows:

In AS (on the central I/O bus) : Tab → Diagnostics/Clock (Tab → Diagnostics/Clock)

(Also applicable to MPI on CPU without DP interface)

● For MPI/DP or DP interface: Tab → Clock

● For PROFINET interface: Tab → Clock synchronization


2: interface

The following interfaces support clock synchronization:

● MPI interface

The CPU can be configured as either a time master or a time slave.

● DP interface

The CPU can be configured as either a time master or a time slave.

● PROFINET interface

The clock is synchronized with the CPU on the client through NTP.

● On the automation system in the central rack

The CPU can be configured as either a time master or a time slave.

Instructions

On many of these interfaces, the CPU cannot be used as a time slave.

CPU as time slave station

When acting as a time slave, a CPU receives synchronization frames only from a time master and uses that time as an internal time for that CPU

Between.

The CPU serves as the time master

When acting as a time master, the CPU broadcasts clock-sync frames at set synchronization intervals to synchronize them in the subnet to which they are connected

It stands.

Requirement: The CPU clock is no longer in the default state. The clock must be set at least once.

Clock synchronization as a time master begins with:

● After this time is initialized by SFC 0 "SET_CLK" or programming device function

● Use another time master, provided that the CPU is also programmed as an MPI/DP or PROFINET interface

Time operates from the station.

Instructions

The real-time clock of the CPU is not set in the following cases:

 before delivery

 after the mode selector switch is reset to factory Settings

 After firmware update

3. Point-to-point connection

Stats:

Point-to-point connections allow data to be exchanged over serial interfaces. Point-to-point connections can be used to interconnect programmable controllers, computations

Computer or third party system with communication function. It can also be adjusted according to the procedures of the communication partner.

3.1 Data Consistency

Stats:

A data area is consistent if it can be read or written to in the operating system as a block. Station to station

The data exchanged centrally between them should belong to a whole and originate from a processing cycle, that is, the data is consistent. If user

Programs that include programmed communication capabilities (for example, using XSEND/XRCV to access shared data) can pass

The "BUSY" parameter itself coordinates access to the corresponding data area.

Use the PUT/GET function

For some S7 communication functions that do not require blocks in CPU (server mode) user programs (e.g.,

In terms of PUT/GET or write/read access via OP communication, the scope of data consistency must be considered during programming.

The PUT/GET function of the S7 communication or the read/write variable operation through the OP communication are executed at the cycle control point of the CPU

Fine. To guarantee the defined hardware interrupt response time, the communication variables need to be in the form of blocks of up to 240 bytes, to/from

The copied user memory in the operating system loop control point is continuously copied. There is no guarantee for larger data areas

Data consistency.

Using PUT/GET functions and "Prioritized OCM communication"

If the operation is configured as "OCM communication by priority", the specified data consistency is lost (see the chapter "OP Communication (page 80)"). Therefore, data consistency must be ensured through user programs.

Keep the following consistent:

● Byte, word, double-word access (e.g. LMDx)

● SFC 14 "DPRD_DAT"

● SFC 15 "DPWR_DAT"

SFC 81 "UBLKMOV" (for copying up to 512 bytes of data)

It should also be understood that if OCM Communication by Priority is configured, the communication will not be changed at the loop control point

Quantities are continuously copied to/from working memory in blocks of up to 240 bytes. Therefore, it should be done while the user program is running

Copy the data.

                                                                                    Quantity name

                                                                                    ① Analog input and analog output

                                                                                    ② Digital input

                                                                                    ③ digital output

3.2 SNMP Communication Service

availability

SNMP V1, MIB-II communication services can be used with integrated PROFINET interfaces and using version 2.2 or later

Firmware for the CPU.

Stats

SNMP (Simple Network Management Protocol) is the standard protocol for TCP/IP networks.

3.3 Open communication over Industrial Ethernet

demand

● Since STEP 7 V5.4 + SP4

Feature

Cpus with integrated PROFINET interfaces support over industrial Ethernet starting with firmware V2.3.0 or V2.4.0

Open communication function (referred to as: Open IE communication)

Open IE communication provides the following services:

● Connection-oriented protocols

- TCP compliant with RFC 793, connection type B#16#01, firmware V2.3.0 and later

- TCP compliant with RFC 793, connection type B#16#11, firmware V2.4.0 and later

- ISO-on-TCP compliant with RFC 1006, firmware V2.4.0 and higher

● No connection protocol

- UDP compliant with RFC 768, firmware V2.4.0 and later

Attributes of the communication protocol

The following protocol types are included in data communication:

● Connection-oriented protocols:

These protocols establish a (logical) connection to a communication partner before the data transfer and then after the transfer is complete

The connection needs to be closed. When the security of data transmission is particularly important, connection-oriented protocols are used. Usually pass

Multiple logical connections can be established over a single physical cable.

FB for open communication over "Industrial Ethernet" supports the following connection-oriented protocols:

- TCP compliant with RFC 793 (connection types B#16#01 and B#16#11)

- ISO-on-TCP according to RFC 1006 (connection type B#16#12)

● No connection protocol:

These protocols can work without establishing a connection. This means there is no need to establish and terminate connections to remote partners

Answer. Connectionless protocols do not require confirmation to transmit data to remote partners; Therefore, data transmission is not secure.

FB for open communication over industrial Ethernet supports the following connectionless protocols:

- UDP compliant with RFC 768 (connection type B#16#13)


How to communicate with Open IE?

To allow the exchange of data with other communication partners, STEP 7 provides the following FB and under Communication Blocks in the Standard Library

UDT:

● Connection-oriented protocols: TCP, ISO-on-TCP

- FB 63 "TSEND" for sending data

- FB 64 "TRCV" for receiving data

- FB 65 "TCON" for connection

- FB 66 "TDISCON" for disconnection

- UDT 65 "TCON_PAR", whose data structure allows the connection to be parameterized

● No connection protocol: UDP

- FB 67 "TUSEND" for sending data

- FB 68 "TURCV" for receiving data

- FB 65 "TCON" for establishing local communication access points

- FB 66 "TDISCON" for parsing local communication access points

- UDT 65 "TCON_PAR", whose data structure can be parameterized to local communication access points

- UDT 66 "TCON_ADR" with remote partner addressing parameter data structure

Operator controls and indicators for CPU 313C-2 DP

                                                                                            Quantity name

                                                                                            ① Status and error indicators

                                                                                            ② Slot of SIMATIC MMC card (including eject device)

                                                                                            ③ Integrated input and output terminals

                                                                                            ④ Power connection

                                                                                            ⑤ 2. Interface X2 (DP)

                                                                                            ⑥ 1. Interface X1 (MPI)

                                                                                            ⑦ Mode selector

A block of data for parameterization

A block of data for parameterizing TCP and ISO-on-TCP connections

To use TCP and ISO-on-TCP configuration connections, you need to create a number that contains UDT 65 "TCON_PAR" medians

According to the structure of DB. This data structure contains all the parameters needed to establish the connection. Each connection requires such a number

According to the structure, you can arrange it in the global data store.

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

A block of data used to parameterize local communication access points using UDP

To assign parameters to the local communication access point, create one that contains the UDT 65 "TCON_PAR" data structure

DB. This data structure contains the parameters needed to establish a connection between the user program and the communication layer of the operating system

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

Instructions

Setting Connection Instructions (UDT 65)

You need to enter the communication interface in the "local_device_id" parameter of UDT65 "TCON_PAR" (for example

B#16#03: Communication via IE interface integrated with CPU 319-3 PN/DP).


Establish communication connection

● Suitable for TCP and ISO-on-TCP

Both communication partners call FB 65 "TCON" to establish a connection. Define which communication partner is used as master during parameterization

Dynamic communication endpoints and which are used as passive communication endpoints. To determine the number of possible connections, see your CPU's technology

The technical specifications.

The CPU automatically monitors and maintains active connections.

If the connection is interrupted, for example due to an open circuit or a telecommunication partner, the active party will attempt to re-establish the connection

Answer. You don't have to call FB 65 "TCON" again.

The active connection is terminated by calling FB 66 "TDISCON" or when the CPU is in STOP mode. Want to re-

To establish a connection, you must call FB 65 "TCON" again.

● Suitable for UDP

Both communication partners call FB 65 "TCON" to set up their local communication access point. This will be in the user program and operation

Connections are established between the communication layers of the system. Connections to remote partners are not established.

The local access point is used to send and receive UDP packets.

Distinguish between PROFINET IO and PROFINET CBA features

                                           PROFINET IO and CBA represent automation equipment for "industrial Ethernet" from two different perspectives.

Component-based automation divides the entire device into different functions. These functions are configured and programmed separately.

The device view provided by PROFINET IO is very similar to the PROFIBUS view. You can continue to configure and configure individual programmable controllers


  • Eaton PW9130I3000T-XL UPS 3000VA
  • Eaton EDB3225L Molded Case Circuit Breaker
  • Eaton SLX010A1-4A1B0 Contactor
  • Eaton 2D78559G01 Control Module
  • Eaton SPD160208Y2A Surge Protective Device
  • EATON MVX001A0-4 Variable Frequency Drive
  • EATON EASY204-DP Programmable Logic Control Relay
  • EATON 99-6120-01 Industrial Control Interface Module
  • EATON MP-4000 66D2206G01 Motor Protection Relay
  • EATON 101073072-001 Industrial Control Switch Module
  • EATON EEA-PAM-523-A-32 Proportional Amplifier
  • EATON FUE-563004 Industrial Control Unit
  • EATON HJD3225 Molded Case Circuit Breaker
  • EATON FP-4000 FP4201-00 Protective Relay
  • EATON 99-6120-01 Industrial Control Component
  • Eaton MP4010 Motor Protection Relay
  • Eaton XV-102-E6-70TWRC-10 HMI Panel
  • Eaton 245U-E Industrial Wireless Ethernet Bridge
  • Eaton XV-430-10TVB-1-10 HMI Touch Panel
  • Eaton MTL 4850 RS485 Surge Protector
  • EATON 1455A-6503 Industrial Control Relay Module
  • EATON XV-230-57CNN-1-13-1 Industrial HMI Touch Panel
  • EATON XV-440-12TSB-1-10 HMI Touch Panel Operator Interface
  • EATON D100DCR40 Digital Control Relay Smart Relay Controller
  • EATON E4548 Industrial Operator Interface Panel
  • EATON HMI06CE Operator Interface
  • EATON FI3200L Molded Case Circuit Breaker
  • EATON XC-CPU201 PLC Controller
  • EATON XV-102-D8-57TVRC-10 HMI PLC
  • EATON 5P650iR Rackmount UPS
  • Eaton HMI10CE / HMI10CE02 Operator Interface
  • Eaton EEA-PAM-523-A-32 Proportional Amplifier
  • Eaton HTP-SC16M / MTL Surge Protection Device
  • Eaton XC-CPU202-EC4M-8DI-6DO-XV PLC CPU
  • Eaton XV-230-57CNN-1-13-1 HMI Panel
  • EATON XV-303-70-C00-A00-1C Industrial HMI
  • EATON XV-440-12TSB-1-50 Industrial HMI Panel
  • EATON XV-152-D6-10TVR-10 Industrial HMI Touch Panel
  • EATON CAN-16DI/P CAN16DIP Digital Input Module
  • EATON S801+N66N3S Soft Starter Motor Controller
  • EATON XV-303-70-B00-A00S07 High-Performance Touch HMI
  • EATON 92-02123-00 7600C Industrial Control Component
  • EATON HMCP150T4CBP10 Motor Circuit Protector
  • EATON EEA-PAM-553-A-32 Proportional Amplifier
  • EATON XV-102-D6-57TVR-10 Touch Panel HMI
  • Eaton 66D2032GX1 MP-3000 Motor Management Relay
  • Eaton CAN-16DO/0.5A-PK Digital Output Module
  • Eaton XV-102-B5-35TQR-10-PLC HMI with PLC
  • Eaton MP-3000 66D2032GX1 Motor Protection Relay
  • Eaton WL-35717F Circuit Breaker Accessory
  • EATON HFD3150 Molded Case Circuit Breaker
  • EATON HFD3030 Molded Case Circuit Breaker
  • EATON XV-230-57CNN-1-13-1 HMI Touch Panel
  • EATON CEAG CU CG-S 40071360300 Control Unit
  • EATON SDN90186 Industrial Power Supply Module
  • EATON HMCP150U4 Motor Circuit Protector
  • EATON 7801C57 Industrial Control Module
  • EATON HMCP400R5 Motor Circuit Protector
  • EATON MP-3000 Motor Protection Relay
  • EATON PGGLOBL1701DPRO 1785T Touch Panel
  • EATON MFD-CP8-NT CPU Module
  • EATON WL-35717F Vacuum Interrupter
  • EATON EEA-PAM-535-A-32 Amplifier
  • EATON FP5000-00 FP5200-00 66D2041G11
  • EATON Q-504A Current Monitoring Relay
  • UniOP eTOP507 Touch Screen Panel
  • UniOP EK-04 Control Panel IT2 6ZA983-7
  • UniOP ETOP33C-0050 Operator Interface Display Panel
  • UniOP Bkdr-16-0045 Operator Interface Display
  • UniOP ETOP504U101 eTOP504 Touchscreen HMI
  • UNIOP CP01F-02-0045 Industrial Control Panel
  • UNIOP MD02R-04-0045 Alphanumeric Display Terminal
  • UNIOP EXOR ERT-16-0045 Communication Module
  • UNIOP EK-04 CONTROL PANEL Alphanumeric Operator Terminal
  • UNIOP ETOP306-109 Industrial HMI Touch Panel
  • UNIOP ETOP 05-0045 5.7" HMI
  • UNIOP ECT-16-0045 Ethernet HMI Controller
  • UNIOP MD02R-04 Air Compressor HMI
  • UNIOP CP11G-04-0045 11" Graphic HMI
  • UNIOP eTOP308 8" High-Performance HMI
  • UniOP ETOP11-0050 Operator Interface Touch Panel HMI
  • UniOP ETOP307-U301 Operator Interface Touch Panel HMI
  • UniOP EPAD03-0046 Operator Interface Panel Industrial HMI
  • UniOP MD00R-04 SC 4000 Operator Panel Industrial HMI
  • UniOP MD01R-02-0045 Operator Panel Industrial HMI Interface
  • UNIOP MD00R-04-0045 Compact Alphanumeric Display Module
  • UNIOP BKDR-16T-0045 Alphanumeric Terminal
  • UNIOP ETOP515 - U2P1 15-Inch High-Performance HMI
  • UNIOP eTOP05-0045 Compact Touch HMI Specifications
  • UNIOP ER-04-0045 Industrial Operator Interface Module
  • UNIOP MDR00R-04-0045 SC4000 HMI
  • UNIOP EK-12 Operator Panel 6ZA952-7
  • UNIOP ETOP06-0050 5.6" Touch HMI
  • UNIOP MD03R-02-0045 Micro HMI
  • UNIOP eTOP507M 15" High-Performance HMI
  • UNIOP ETOP307-U301 High-Performance Touch HMI
  • UNIOP CP01F-02-0042 Industrial Control Panel
  • UNIOP CP01F-02-0021 Compact Operator Panel
  • UNIOP MKDL 16 0021 LCD Operator Terminal
  • UNIOP MD02R-04-00A6 Alphanumeric Display Module
  • UNIOP eTOP11-0050 10.1" Widescreen HMI
  • UNIOP ETOP 05-0045 5.7" HMI
  • UNIOP eTOP40C-0050 4.3" Compact HMI
  • UNIOP epad05 5" Industrial Tablet HMI
  • UNIOP CP10G-04-0045 10.4" Graphic HMI
  • UniOP EK04 Operator Panel HMI Display Keypad 6ZA983-7
  • UniOP TP-01 Touch Screen Panel Industrial HMI Interface
  • UniOP PQ5187 Operator Interface Module Industrial HMI
  • UniOP MD02R-04-0045 Operator Interface Module
  • UniOP MD03R-02-0042 Operator Interface Module Industrial HMI
  • UNIOP MD00R-04-0045 Text-Based Operator Module
  • UNIOP MKDR-16-0045 Alphanumeric Operator Terminal
  • UNIOP eTOP05-0045 Compact HMI Touch Screen
  • UNIOP EK-04 CONTROL Operator Terminal
  • UNIOP eTOP30-0050 Industrial HMI Touch Panel
  • UNIOP ETOP03-0046 3.5" Touch HMI
  • UNIOP CP01F-02-0045 Function Key HMI
  • UNIOP CP01R-04-0045 Text Display HMI
  • UNIOP eTOP06-0050 5.6" Touch HMI
  • UNIOP eTOP10B-0050 10.1" Touch HMI
  • UNIOP eTOP03-0046 Touch Screen HMI
  • UNIOP MKDR-16-TA-0045 Keypad Display Terminal
  • UNIOP MD02R-04-0042 Micro Display Module
  • UNIOP ECT-16-0045 Ethernet HMI Controller
  • UNIOP CP05R-04-0045 HMI Operator Panel
  • UniOP ETOP05-0045 Operator Panel Industrial HMI Interface
  • UniOP MD02R-04-0045 Operator Interface Module Industrial HMI
  • UniOP MD00R-02-0045 Operator Interface Module Industrial HMI