Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

S7-300 CPU 31xC 和 CPU 31x

来源: | 作者:佚名 | 发布时间 :2023-11-20 | 884 次浏览: | Share:

Routing and data record routing

Routing is the transmission of data across network boundaries. Information can be sent from sender to receiver across several networks.

The data logging route is an extension of the common route. For example, when the programming device is not directly connected to the target device

PROFIBUS DP subnets, but when connected to the CPU's PROFINET interface, SIMATIC PDM will make

Record routes with data. The data sent through the data recording route includes parameters of the participating field devices (slave stations)

Configuration, and device-specific information (e.g., set values, limit values, etc.). Data records the destination address structure of the route

Depends on the content of the data, i.e. the secondary station receiving the data.

When a programming device is assigned a different subnet from the target slave station, the data record route can also be read using the programming device

Set of parameters that already exist on the field device, edit them, and return them to the field device.

The field devices themselves do not need to support data record routing because they do not forward the received information.

Clock synchronization

1:intro

The CPU interface supports clock synchronization. The CPU can be programmed to act as a time master (with a default synchronization interval)

Interval) or time to run from the station.

Default value: No clock synchronization

Set synchronization mode

In the properties dialog box of HW Config, set the synchronization mode as follows:

In AS (on the central I/O bus) : Tab → Diagnostics/Clock (Tab → Diagnostics/Clock)

(Also applicable to MPI on CPU without DP interface)

● For MPI/DP or DP interface: Tab → Clock

● For PROFINET interface: Tab → Clock synchronization


2: interface

The following interfaces support clock synchronization:

● MPI interface

The CPU can be configured as either a time master or a time slave.

● DP interface

The CPU can be configured as either a time master or a time slave.

● PROFINET interface

The clock is synchronized with the CPU on the client through NTP.

● On the automation system in the central rack

The CPU can be configured as either a time master or a time slave.

Instructions

On many of these interfaces, the CPU cannot be used as a time slave.

CPU as time slave station

When acting as a time slave, a CPU receives synchronization frames only from a time master and uses that time as an internal time for that CPU

Between.

The CPU serves as the time master

When acting as a time master, the CPU broadcasts clock-sync frames at set synchronization intervals to synchronize them in the subnet to which they are connected

It stands.

Requirement: The CPU clock is no longer in the default state. The clock must be set at least once.

Clock synchronization as a time master begins with:

● After this time is initialized by SFC 0 "SET_CLK" or programming device function

● Use another time master, provided that the CPU is also programmed as an MPI/DP or PROFINET interface

Time operates from the station.

Instructions

The real-time clock of the CPU is not set in the following cases:

 before delivery

 after the mode selector switch is reset to factory Settings

 After firmware update

3. Point-to-point connection

Stats:

Point-to-point connections allow data to be exchanged over serial interfaces. Point-to-point connections can be used to interconnect programmable controllers, computations

Computer or third party system with communication function. It can also be adjusted according to the procedures of the communication partner.

3.1 Data Consistency

Stats:

A data area is consistent if it can be read or written to in the operating system as a block. Station to station

The data exchanged centrally between them should belong to a whole and originate from a processing cycle, that is, the data is consistent. If user

Programs that include programmed communication capabilities (for example, using XSEND/XRCV to access shared data) can pass

The "BUSY" parameter itself coordinates access to the corresponding data area.

Use the PUT/GET function

For some S7 communication functions that do not require blocks in CPU (server mode) user programs (e.g.,

In terms of PUT/GET or write/read access via OP communication, the scope of data consistency must be considered during programming.

The PUT/GET function of the S7 communication or the read/write variable operation through the OP communication are executed at the cycle control point of the CPU

Fine. To guarantee the defined hardware interrupt response time, the communication variables need to be in the form of blocks of up to 240 bytes, to/from

The copied user memory in the operating system loop control point is continuously copied. There is no guarantee for larger data areas

Data consistency.

Using PUT/GET functions and "Prioritized OCM communication"

If the operation is configured as "OCM communication by priority", the specified data consistency is lost (see the chapter "OP Communication (page 80)"). Therefore, data consistency must be ensured through user programs.

Keep the following consistent:

● Byte, word, double-word access (e.g. LMDx)

● SFC 14 "DPRD_DAT"

● SFC 15 "DPWR_DAT"

SFC 81 "UBLKMOV" (for copying up to 512 bytes of data)

It should also be understood that if OCM Communication by Priority is configured, the communication will not be changed at the loop control point

Quantities are continuously copied to/from working memory in blocks of up to 240 bytes. Therefore, it should be done while the user program is running

Copy the data.

                                                                                    Quantity name

                                                                                    ① Analog input and analog output

                                                                                    ② Digital input

                                                                                    ③ digital output

3.2 SNMP Communication Service

availability

SNMP V1, MIB-II communication services can be used with integrated PROFINET interfaces and using version 2.2 or later

Firmware for the CPU.

Stats

SNMP (Simple Network Management Protocol) is the standard protocol for TCP/IP networks.

3.3 Open communication over Industrial Ethernet

demand

● Since STEP 7 V5.4 + SP4

Feature

Cpus with integrated PROFINET interfaces support over industrial Ethernet starting with firmware V2.3.0 or V2.4.0

Open communication function (referred to as: Open IE communication)

Open IE communication provides the following services:

● Connection-oriented protocols

- TCP compliant with RFC 793, connection type B#16#01, firmware V2.3.0 and later

- TCP compliant with RFC 793, connection type B#16#11, firmware V2.4.0 and later

- ISO-on-TCP compliant with RFC 1006, firmware V2.4.0 and higher

● No connection protocol

- UDP compliant with RFC 768, firmware V2.4.0 and later

Attributes of the communication protocol

The following protocol types are included in data communication:

● Connection-oriented protocols:

These protocols establish a (logical) connection to a communication partner before the data transfer and then after the transfer is complete

The connection needs to be closed. When the security of data transmission is particularly important, connection-oriented protocols are used. Usually pass

Multiple logical connections can be established over a single physical cable.

FB for open communication over "Industrial Ethernet" supports the following connection-oriented protocols:

- TCP compliant with RFC 793 (connection types B#16#01 and B#16#11)

- ISO-on-TCP according to RFC 1006 (connection type B#16#12)

● No connection protocol:

These protocols can work without establishing a connection. This means there is no need to establish and terminate connections to remote partners

Answer. Connectionless protocols do not require confirmation to transmit data to remote partners; Therefore, data transmission is not secure.

FB for open communication over industrial Ethernet supports the following connectionless protocols:

- UDP compliant with RFC 768 (connection type B#16#13)


How to communicate with Open IE?

To allow the exchange of data with other communication partners, STEP 7 provides the following FB and under Communication Blocks in the Standard Library

UDT:

● Connection-oriented protocols: TCP, ISO-on-TCP

- FB 63 "TSEND" for sending data

- FB 64 "TRCV" for receiving data

- FB 65 "TCON" for connection

- FB 66 "TDISCON" for disconnection

- UDT 65 "TCON_PAR", whose data structure allows the connection to be parameterized

● No connection protocol: UDP

- FB 67 "TUSEND" for sending data

- FB 68 "TURCV" for receiving data

- FB 65 "TCON" for establishing local communication access points

- FB 66 "TDISCON" for parsing local communication access points

- UDT 65 "TCON_PAR", whose data structure can be parameterized to local communication access points

- UDT 66 "TCON_ADR" with remote partner addressing parameter data structure

Operator controls and indicators for CPU 313C-2 DP

                                                                                            Quantity name

                                                                                            ① Status and error indicators

                                                                                            ② Slot of SIMATIC MMC card (including eject device)

                                                                                            ③ Integrated input and output terminals

                                                                                            ④ Power connection

                                                                                            ⑤ 2. Interface X2 (DP)

                                                                                            ⑥ 1. Interface X1 (MPI)

                                                                                            ⑦ Mode selector

A block of data for parameterization

A block of data for parameterizing TCP and ISO-on-TCP connections

To use TCP and ISO-on-TCP configuration connections, you need to create a number that contains UDT 65 "TCON_PAR" medians

According to the structure of DB. This data structure contains all the parameters needed to establish the connection. Each connection requires such a number

According to the structure, you can arrange it in the global data store.

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

A block of data used to parameterize local communication access points using UDP

To assign parameters to the local communication access point, create one that contains the UDT 65 "TCON_PAR" data structure

DB. This data structure contains the parameters needed to establish a connection between the user program and the communication layer of the operating system

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

Instructions

Setting Connection Instructions (UDT 65)

You need to enter the communication interface in the "local_device_id" parameter of UDT65 "TCON_PAR" (for example

B#16#03: Communication via IE interface integrated with CPU 319-3 PN/DP).


Establish communication connection

● Suitable for TCP and ISO-on-TCP

Both communication partners call FB 65 "TCON" to establish a connection. Define which communication partner is used as master during parameterization

Dynamic communication endpoints and which are used as passive communication endpoints. To determine the number of possible connections, see your CPU's technology

The technical specifications.

The CPU automatically monitors and maintains active connections.

If the connection is interrupted, for example due to an open circuit or a telecommunication partner, the active party will attempt to re-establish the connection

Answer. You don't have to call FB 65 "TCON" again.

The active connection is terminated by calling FB 66 "TDISCON" or when the CPU is in STOP mode. Want to re-

To establish a connection, you must call FB 65 "TCON" again.

● Suitable for UDP

Both communication partners call FB 65 "TCON" to set up their local communication access point. This will be in the user program and operation

Connections are established between the communication layers of the system. Connections to remote partners are not established.

The local access point is used to send and receive UDP packets.

Distinguish between PROFINET IO and PROFINET CBA features

                                           PROFINET IO and CBA represent automation equipment for "industrial Ethernet" from two different perspectives.

Component-based automation divides the entire device into different functions. These functions are configured and programmed separately.

The device view provided by PROFINET IO is very similar to the PROFIBUS view. You can continue to configure and configure individual programmable controllers


  • Hitachi LPT020A Industrial Power Module
  • Hitachi LPF240F Industrial Power Module
  • Hitachi LPU100A Industrial Power Unit
  • Hitachi PS6515 Industrial Power Supply Module
  • Hitachi PS6548 Power Supply Module
  • Hitachi LCE250B Communication Module
  • Hitachi LCE250A Communication Module
  • Hitachi LPA302P-1 Analog Input Module
  • Hitachi LPA210A Analog Input Interface
  • Hitachi LPA302A Analog Input Module
  • HITACHI PS6524 Switching Power Supply
  • HITACHI MPD310A Color Touch Screen HMI
  • HITACHI MPD110A Graphic Operator Terminal
  • HITACHI MPD060A Operator Interface Display
  • HITACHI LPP100A Power Supply Module
  • Hitachi LPD200A AC Drive Inverter
  • Hitachi LUD060A AC Drive Inverter
  • Hitachi LPD350A AC Drive Inverter
  • Hitachi LPD220A AC Drive Inverter
  • Hitachi LPA220A AC Drive Inverter
  • Hitachi LPA245A Analog Input Module
  • Hitachi LPU100H Central Processing Unit
  • Hitachi LYT000A Output Module
  • Hitachi LPF240A Power Filter Module
  • Hitachi LUD700A Display and Interface Unit
  • HITACHI LYA100A Analog I/O Module
  • HITACHI LYA220A Analog Input Module
  • HITACHI TD000A Temperature Controller
  • HITACHI LYA210A Analog Output Module
  • HITACHI LYD105A Digital Input Module
  • Hitachi LYA010A AC Drive Inverter
  • HITACHI 2-822037-A Servo Motor Controller
  • Honeywell CC-TAIM01 Analog Input Module
  • Honeywell 2104B2131 Temperature Transmitter
  • Honeywell 05704-A-0146 Industrial Pressure Transmitter
  • Honeywell 05701-A-0351 & 05701-A-0302 Control System Components
  • Honeywell 05701-A-0327 System 57 Interface Module
  • Honeywell S2024-2POS-SW2 Spring Return Actuator
  • Honeywell XFR824A Transformer Module 24VAC 40VA
  • Honeywell 05701-A-0284 & 05701-A-0302 System 57 Control Card
  • Honeywell SC-UCMX02 Universal Controller Module 51307198-276
  • Honeywell ISC-UCMX01 Safety Controller Module 51307195-175
  • Honeywell FC-SCNT02 Field Control Scanner Module
  • Honeywell FC-SCNT01 Field Control Scanner Module
  • Honeywell CC-TUIO41 Universal Input/Output Module
  • Honeywell CC-TUI041 Universal Input Module
  • Honeywell CC-PLAIH51 Analog Input HART Module
  • Honeywell XNX-UTAV-RNIF1 XNX Universal Transmitter
  • Honeywell FTA-T-02 Field Termination Assembly
  • Honeywell LG1093AA24 261A1812P012 Flame Amplifier Module
  • Honeywell CC-TCNT01 51308307-175 ControlNet Interface Module
  • Honeywell CC-TUI041 51306873-176 Universal Input Module
  • Honeywell 1569905-6131140220 Specialized Industrial Component
  • Honeywell QPP-0001 Quad Processor Pack Safety Manager
  • Honeywell PSU-240516 Power Supply Unit 24VDC 5A/16A
  • Honeywell CPB-0001 CPCHAS-0001 Control Processor Chassis
  • Honeywell SDO-0824 CCV1.3 Supervised Digital Output Module
  • Honeywell SDI-1624 CCV1.1 Digital Module
  • Honeywell IO-0001 CCV1.0 Interface Module
  • Honeywell IOCHAS-0001S I/O Chassis
  • Honeywell SAI-1620M CCV1.4 Analog Module
  • Honeywell EG1033AA Flame Detector
  • ABB PPD513 A2A-11165 Panel
  • Honeywell 51401497-100 FW25-92 LCN Interface Board
  • Honeywell 05701-A-0405 Digital Output Module
  • HONEYWELL XS824-25 Industrial Sensor Module
  • Honeywell 51120841-101 51120841-201 Power Filter Module
  • Honeywell CC-PUIO01 Module
  • HONEYWELL 0571-A-0328 Industrial Control Module
  • Honeywell 05701-A-0325 Series 57 Control Module
  • Honeywell 05701-A-0282 I/O Module
  • HONEYWELL TC-CCN014 Control Network Module
  • Honeywell 10310/1/1 09701 Safety Manager Controller Module
  • Honeywell GR-2C-DC24V Relay Module
  • HONEYWELL GR-4C-DC24V Relay Module
  • Honeywell GR-2C-AC230V Industrial General Purpose Relay
  • Honeywell SPS5713 Power Supply
  • HONEYWELL SC-TCMX01 51307198-175 Termination Module
  • Honeywell 05704-A-0121 05704-A-0122 05704-A-0131 Control Modules
  • Honeywell SC-PCMX01 Power Module
  • Honeywell SPS5785 51198651-100 System Power Supply
  • HONEYWELL CC-IP0101 51410056-175 Interface Module
  • Honeywell 51402455-100 Profibus Module
  • HONEYWELL 51402455-100 MP-DNCF02-200 Module
  • Honeywell 51403645-100 SBHM Static Buffer Hi-Memory Board
  • Honeywell 51401583-100 EPNI Module
  • Honeywell 51306673-100 EPNI Module
  • HONEYWELL 51196655-100 ACX633 Control Module
  • Honeywell 51403519-160 K4LCN-16 Processor Board
  • Honeywell 51305072-200 CLCN-A Module
  • Honeywell 51305896-200 NIM Modem | TDC 3000 Network Module
  • HONEYWELL 51305072-300 CLCN-B Network Module
  • Honeywell FC-PSU-UNI2450U Power Supply
  • Honeywell CC-MCAR02 Series C Carrier | Experion PKS Chassis
  • HONEYWELL SC-UCMX01 51307198-175 Control Module
  • Honeywell 51404170-175 I/O Module
  • Honeywell 51196653-100-RP Controller Processor Board
  • HONEYWELL 05701-A-0330 Gas Detection Control Module
  • Honeywell SPS5710 Power Supply Module
  • Honeywell FTA-T-21 Field Termination Assembly
  • HONEYWELL FTA-T-14 Field Termination Assembly
  • Honeywell 05701-A-0325 I/O Module
  • Honeywell GR-4C-AC230V Industrial Power Relay
  • HONEYWELL PGR-4C-E Ground Fault Protection Relay
  • HONEYWELL CC-TCNT01 Controller Module
  • HONEYWELL CC-TAIX01 Analog Input Module
  • Honeywell CC-TAIN01 Analog Input IOTA Module
  • Honeywell 51304487-100 Output Module
  • Honeywell J-MSC10 Motor Starter Communication Module
  • HONEYWELL 51304518-150 I/O Module
  • HONEYWELL J-DIM00 Digital Input Module
  • HONEYWELL FF-SB12E04K-S2 Safety Light Curtain
  • Honeywell 51404223-001 TDC 3000 Controller Board
  • Honeywell 51195066-100 I/O Module
  • KEBA CU313 Industrial Controller
  • KEBA AR281 Automation Panel
  • KEBA K2-200 CP253/W Central Processor | KeControl CPU Module
  • KEBA CU313A Control Unit
  • KEBA FB201 Fieldbus Interface Module
  • KEBA CU313 Control Unit | KeControl Processing Module
  • KEBA CU312/E Compact Industrial Controller
  • KEBA OP341/Y-1400 Industrial Operator Panel
  • KEBA IP706 Interface Processor Module
  • KEBA CP450 Operator Panel
  • KEBA CP033/Y Industrial HMI Panel
  • KEBA PS244 Power Supply Module
  • KEBA SI232 Safety Input Module
  • KEBA DO321 Digital Output Module | KeControl System