Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

S7-300 CPU 31xC 和 CPU 31x

来源: | 作者:佚名 | 发布时间 :2023-11-20 | 1013 次浏览: | 🔊 Click to read aloud ❚❚ | Share:

Routing and data record routing

Routing is the transmission of data across network boundaries. Information can be sent from sender to receiver across several networks.

The data logging route is an extension of the common route. For example, when the programming device is not directly connected to the target device

PROFIBUS DP subnets, but when connected to the CPU's PROFINET interface, SIMATIC PDM will make

Record routes with data. The data sent through the data recording route includes parameters of the participating field devices (slave stations)

Configuration, and device-specific information (e.g., set values, limit values, etc.). Data records the destination address structure of the route

Depends on the content of the data, i.e. the secondary station receiving the data.

When a programming device is assigned a different subnet from the target slave station, the data record route can also be read using the programming device

Set of parameters that already exist on the field device, edit them, and return them to the field device.

The field devices themselves do not need to support data record routing because they do not forward the received information.

Clock synchronization

1:intro

The CPU interface supports clock synchronization. The CPU can be programmed to act as a time master (with a default synchronization interval)

Interval) or time to run from the station.

Default value: No clock synchronization

Set synchronization mode

In the properties dialog box of HW Config, set the synchronization mode as follows:

In AS (on the central I/O bus) : Tab → Diagnostics/Clock (Tab → Diagnostics/Clock)

(Also applicable to MPI on CPU without DP interface)

● For MPI/DP or DP interface: Tab → Clock

● For PROFINET interface: Tab → Clock synchronization


2: interface

The following interfaces support clock synchronization:

● MPI interface

The CPU can be configured as either a time master or a time slave.

● DP interface

The CPU can be configured as either a time master or a time slave.

● PROFINET interface

The clock is synchronized with the CPU on the client through NTP.

● On the automation system in the central rack

The CPU can be configured as either a time master or a time slave.

Instructions

On many of these interfaces, the CPU cannot be used as a time slave.

CPU as time slave station

When acting as a time slave, a CPU receives synchronization frames only from a time master and uses that time as an internal time for that CPU

Between.

The CPU serves as the time master

When acting as a time master, the CPU broadcasts clock-sync frames at set synchronization intervals to synchronize them in the subnet to which they are connected

It stands.

Requirement: The CPU clock is no longer in the default state. The clock must be set at least once.

Clock synchronization as a time master begins with:

● After this time is initialized by SFC 0 "SET_CLK" or programming device function

● Use another time master, provided that the CPU is also programmed as an MPI/DP or PROFINET interface

Time operates from the station.

Instructions

The real-time clock of the CPU is not set in the following cases:

 before delivery

 after the mode selector switch is reset to factory Settings

 After firmware update

3. Point-to-point connection

Stats:

Point-to-point connections allow data to be exchanged over serial interfaces. Point-to-point connections can be used to interconnect programmable controllers, computations

Computer or third party system with communication function. It can also be adjusted according to the procedures of the communication partner.

3.1 Data Consistency

Stats:

A data area is consistent if it can be read or written to in the operating system as a block. Station to station

The data exchanged centrally between them should belong to a whole and originate from a processing cycle, that is, the data is consistent. If user

Programs that include programmed communication capabilities (for example, using XSEND/XRCV to access shared data) can pass

The "BUSY" parameter itself coordinates access to the corresponding data area.

Use the PUT/GET function

For some S7 communication functions that do not require blocks in CPU (server mode) user programs (e.g.,

In terms of PUT/GET or write/read access via OP communication, the scope of data consistency must be considered during programming.

The PUT/GET function of the S7 communication or the read/write variable operation through the OP communication are executed at the cycle control point of the CPU

Fine. To guarantee the defined hardware interrupt response time, the communication variables need to be in the form of blocks of up to 240 bytes, to/from

The copied user memory in the operating system loop control point is continuously copied. There is no guarantee for larger data areas

Data consistency.

Using PUT/GET functions and "Prioritized OCM communication"

If the operation is configured as "OCM communication by priority", the specified data consistency is lost (see the chapter "OP Communication (page 80)"). Therefore, data consistency must be ensured through user programs.

Keep the following consistent:

● Byte, word, double-word access (e.g. LMDx)

● SFC 14 "DPRD_DAT"

● SFC 15 "DPWR_DAT"

SFC 81 "UBLKMOV" (for copying up to 512 bytes of data)

It should also be understood that if OCM Communication by Priority is configured, the communication will not be changed at the loop control point

Quantities are continuously copied to/from working memory in blocks of up to 240 bytes. Therefore, it should be done while the user program is running

Copy the data.

                                                                                    Quantity name

                                                                                    ① Analog input and analog output

                                                                                    ② Digital input

                                                                                    ③ digital output

3.2 SNMP Communication Service

availability

SNMP V1, MIB-II communication services can be used with integrated PROFINET interfaces and using version 2.2 or later

Firmware for the CPU.

Stats

SNMP (Simple Network Management Protocol) is the standard protocol for TCP/IP networks.

3.3 Open communication over Industrial Ethernet

demand

● Since STEP 7 V5.4 + SP4

Feature

Cpus with integrated PROFINET interfaces support over industrial Ethernet starting with firmware V2.3.0 or V2.4.0

Open communication function (referred to as: Open IE communication)

Open IE communication provides the following services:

● Connection-oriented protocols

- TCP compliant with RFC 793, connection type B#16#01, firmware V2.3.0 and later

- TCP compliant with RFC 793, connection type B#16#11, firmware V2.4.0 and later

- ISO-on-TCP compliant with RFC 1006, firmware V2.4.0 and higher

● No connection protocol

- UDP compliant with RFC 768, firmware V2.4.0 and later

Attributes of the communication protocol

The following protocol types are included in data communication:

● Connection-oriented protocols:

These protocols establish a (logical) connection to a communication partner before the data transfer and then after the transfer is complete

The connection needs to be closed. When the security of data transmission is particularly important, connection-oriented protocols are used. Usually pass

Multiple logical connections can be established over a single physical cable.

FB for open communication over "Industrial Ethernet" supports the following connection-oriented protocols:

- TCP compliant with RFC 793 (connection types B#16#01 and B#16#11)

- ISO-on-TCP according to RFC 1006 (connection type B#16#12)

● No connection protocol:

These protocols can work without establishing a connection. This means there is no need to establish and terminate connections to remote partners

Answer. Connectionless protocols do not require confirmation to transmit data to remote partners; Therefore, data transmission is not secure.

FB for open communication over industrial Ethernet supports the following connectionless protocols:

- UDP compliant with RFC 768 (connection type B#16#13)


How to communicate with Open IE?

To allow the exchange of data with other communication partners, STEP 7 provides the following FB and under Communication Blocks in the Standard Library

UDT:

● Connection-oriented protocols: TCP, ISO-on-TCP

- FB 63 "TSEND" for sending data

- FB 64 "TRCV" for receiving data

- FB 65 "TCON" for connection

- FB 66 "TDISCON" for disconnection

- UDT 65 "TCON_PAR", whose data structure allows the connection to be parameterized

● No connection protocol: UDP

- FB 67 "TUSEND" for sending data

- FB 68 "TURCV" for receiving data

- FB 65 "TCON" for establishing local communication access points

- FB 66 "TDISCON" for parsing local communication access points

- UDT 65 "TCON_PAR", whose data structure can be parameterized to local communication access points

- UDT 66 "TCON_ADR" with remote partner addressing parameter data structure

Operator controls and indicators for CPU 313C-2 DP

                                                                                            Quantity name

                                                                                            ① Status and error indicators

                                                                                            ② Slot of SIMATIC MMC card (including eject device)

                                                                                            ③ Integrated input and output terminals

                                                                                            ④ Power connection

                                                                                            ⑤ 2. Interface X2 (DP)

                                                                                            ⑥ 1. Interface X1 (MPI)

                                                                                            ⑦ Mode selector

A block of data for parameterization

A block of data for parameterizing TCP and ISO-on-TCP connections

To use TCP and ISO-on-TCP configuration connections, you need to create a number that contains UDT 65 "TCON_PAR" medians

According to the structure of DB. This data structure contains all the parameters needed to establish the connection. Each connection requires such a number

According to the structure, you can arrange it in the global data store.

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

A block of data used to parameterize local communication access points using UDP

To assign parameters to the local communication access point, create one that contains the UDT 65 "TCON_PAR" data structure

DB. This data structure contains the parameters needed to establish a connection between the user program and the communication layer of the operating system

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

Instructions

Setting Connection Instructions (UDT 65)

You need to enter the communication interface in the "local_device_id" parameter of UDT65 "TCON_PAR" (for example

B#16#03: Communication via IE interface integrated with CPU 319-3 PN/DP).


Establish communication connection

● Suitable for TCP and ISO-on-TCP

Both communication partners call FB 65 "TCON" to establish a connection. Define which communication partner is used as master during parameterization

Dynamic communication endpoints and which are used as passive communication endpoints. To determine the number of possible connections, see your CPU's technology

The technical specifications.

The CPU automatically monitors and maintains active connections.

If the connection is interrupted, for example due to an open circuit or a telecommunication partner, the active party will attempt to re-establish the connection

Answer. You don't have to call FB 65 "TCON" again.

The active connection is terminated by calling FB 66 "TDISCON" or when the CPU is in STOP mode. Want to re-

To establish a connection, you must call FB 65 "TCON" again.

● Suitable for UDP

Both communication partners call FB 65 "TCON" to set up their local communication access point. This will be in the user program and operation

Connections are established between the communication layers of the system. Connections to remote partners are not established.

The local access point is used to send and receive UDP packets.

Distinguish between PROFINET IO and PROFINET CBA features

                                           PROFINET IO and CBA represent automation equipment for "industrial Ethernet" from two different perspectives.

Component-based automation divides the entire device into different functions. These functions are configured and programmed separately.

The device view provided by PROFINET IO is very similar to the PROFIBUS view. You can continue to configure and configure individual programmable controllers


  • Pasaban MTC-3052 Fast I/O PLC Module
  • Mitsubishi FX3U-128MR/ES-A PLC
  • OMRON CS1W-CLK21 Controller Link Unit
  • Yokogawa ADV151-E63 Digital Input Module
  • Allen Bradley MPL-B680B-M-X227 Motor
  • OMRON CJ1W-NC413 4-Axis Position Unit
  • Yaskawa SGMGH-30DCA6H-OY Servo Motor
  • Bosch 1070075337-101 Output Card
  • OMRON CQM1-CPU45-EV1 PLC CPU Unit
  • Siemens 6SE7090-0XX84-0AG1 CU3 Control Module
  • OMRON CQM1-TC101 Temperature Control Module
  • MOOG OEM-1030-422 Wind Energy PLC Controller
  • OMRON ZFX-C15 Vision Sensor
  • Square D 8702SCO2V02 Reversing Contactor
  • OMRON C20-LK201-EV1 PLC Link Adapter
  • OMRON NB7W-TW01B HMI PLC
  • Siemens 7ME6920-1AA10-1AA0 Flow Transmitter
  • Allen Bradley 1791-8BR Block I/O Module
  • OMRON CQM1-AD041 Analog Input Module
  • OMRON CJ1M-CPU21 PLC Module
  • Omron Z500-MC10E-001 Laser Profile Controller
  • Omron NA5-7W001B-V1 NA Series Programmable Terminal HMI
  • Allen-Bradley 1606-XLS960EE Power Supply 960W 24VDC
  • GE DS3800NEPB1F1E Power Excitation Board Mark IV
  • Yaskawa SGDH-04AE-OY Sigma-II Servo Drive 400W
  • Allen-Bradley 2711P-RBT7 PanelView Plus 7 Bezel
  • CCS PD3-3024-3-EI Digital Control Unit 3 Channel
  • Yaskawa CPU301 MP3300 Controller JAPMC-CP3301-2-E
  • Omron C40P-EDR-D PLC C Series P Type Controller
  • Omron NX-SID800 Safety Input Unit 8 PNP 24VDC
  • ABB SCC-C 23070-0-10232110 gas cooler
  • Sick LGTN101-521 CPU Module
  • Okuma 1911-2836 PLC Circuit Board
  • Mitsubishi Melsec PM-120M PLC
  • Omron F210-C15 Vision Mate Controller System
  • Siemens 7ML5110-1GD07-4AF3 Ultrasonic Level Gauge
  • ABB Pluto S46 V2 Safety Relay
  • Omron Z3RN-5A Optical Serial Link
  • Omron R7D-APA3H 30W Servo Drive
  • Giddings Lewis 502-03638-41R3 PLC Processor
  • Omron SCY-P1 Sequencer Controller
  • Siemens C98043-A7002-L1-13 PCB Board
  • SACS TECNICA Palletizer PC PLC Control System
  • AutomationDirect T1F-14THM PLC Module T1F14THM
  • OMRON C200H-AD003 Analog Input Unit PLC Module
  • Applied Materials 0010-A0000 Electricity Box PLC 200mm
  • ABB RVT-6 Power Factor Controller RVT6
  • Allen-Bradley 2094-BC01-MP5-M Kinetix 6000 Axis Module
  • OMRON FQM1S-MC233 Motion Controller PLC Module
  • OMRON C200H-SNT31 PLC Special I-O Module
  • Yaskawa SGMPH-04AAA61D-OY Servo Motor 400W 200V
  • Yaskawa SGMGH-09DCA6F-OY AC Servo Motor 850W 400V
  • REFU ELEKTRONIK SR17002 PLC Logic Module Circuit Board
  • Siemens 6DP1231-7AA PLC Board Module Industrial Control
  • ABB SACE ISOMAX S3 N 160 Molded Case Circuit Breaker
  • OMRON C120-SC024-V1 SYSMAC C120 Compact PLC Unit
  • OMRON CJ1W-SCU41-V1 Serial Communication Unit PLC Module
  • OMRON 3G3MX2-A4110-ZV1 MX2 Variable Frequency Drive
  • Yaskawa SGDH-04AE-OY Sigma-II Servo Driver 400W 200V
  • OMRON CQM1-AD041 Analog Input Module PLC I/O Unit
  • Delta Omega XML2-0060-45-4/S-A Servo Drive
  • Omron CJ1W-AD041 Analog Input
  • Omron CJ1W-NC271 Position Control Unit
  • Omron CJ1G-CPU45H PLC CPU
  • Omron CJ1W-EIP21 EtherNet/IP Unit
  • Omron F210-C15 Vision Mate Controller
  • Omron CQM1H-ADB21 Analog I/O Board
  • Omron GRT1-PRT PROFIBUS DP-V1 Adapter
  • Omron CP1H-Y20DT-D PLC CPU
  • TE.CO TFX 4G 1.5 Grey Cable 470m
  • Yaskawa SGDH-04AE-OY Servo Driver 400W 200V
  • OMRON CJ1H-CPU66H V4.0 PLC CPU
  • OMRON R7M-A10030-BS1 Servo Motor 200W 100V
  • OMRON FQM1-MMA21 Motion Controller
  • Yaskawa SJDE-08APA Servo Amplifier
  • OMRON CQM1-AD041 Analog Input Unit
  • Siemens OCI55 Dialogue Module Landis
  • OMRON F350-C10E Image Processing Unit
  • OMRON NT10S-SF121 HMI Terminal
  • SIEMENS 3RB1262-0LB31 Overload Relay
  • OMRON YASKAWA SGDS-02A12A Servo Drive
  • TE.CO TFX 4G 1.5 Grey Cable ST 500m
  • FANUC A16B-3200-0362 PCB Control Board
  • OMRON CQM1-ARM21 Analog Output Unit
  • Allen-Bradley 1788-EN2DN Ethernet DeviceNet Gateway
  • Siemens 3VL9440-7EE40 3VL4740-2AA46-0AA0 Circuit Breaker
  • OMRON CJ1W-AD041-V1 Analog Input Unit
  • OMRON CQM1-AD041 CQM1-IPS02 Analog Input Power Supply
  • Texas Instruments System 505 PLC 525-110 525-1102
  • OMRON CQM1-AD042 Analog Input Unit
  • Yaskawa SGDH-04AE-OY Servo Driver 200V 400W
  • CTI 2512 75W Power Supply for CTI 2500
  • Omron F300-B5 Image Processing Unit
  • Mitsubishi 15050-PR01A PLC Board
  • Omron CQM1-TC101 Temperature Controller
  • SCE M68-2000 2 Axis Motion Controller HW 2.3/B
  • Omron 3Z4SP-C22 Visual Positioning Sensor
  • Omron 3G3SV-BB007-E 0.75kW VFD
  • CML 6622 IRD Entek AW10528 Vibration Monitor
  • Omron CP1L-EL20DR-D PLC CPU
  • TE.CO TFX 4G 1.5 Grey Cable 500m
  • Mitsubishi Electric 3BK23057 Circuit Board Module
  • OMRON FQM1-MMP21 Motion Control Module
  • OMRON CP1E-E40SDR-A Micro PLC CPU Unit
  • KEBA CU201 PLC Control Unit
  • OMRON F150-C10E-2 Vision Sensor Controller
  • YASKAWA SGDH-04AE-OY Sigma-II Servo Driver
  • OMRON CS1H-CPU65-V1 PLC Central Processing Unit
  • OMRON NB7W-TX01B Interactive Display HMI
  • OMRON C500-TU002E Programmable Logic Controller Timer Unit
  • OMRON C200HW-PRT21 PROFIBUS DP Slave Unit
  • ExcelTech MX-5-S-I-6-4 Static Transfer Switch
  • Allen-Bradley 100-B300ND3 Contactor 304A 600V
  • Pasaban MTC-3052 Fast I/O PLC Card
  • OMRON CQM1-TC101 Temperature Control Unit
  • OMRON 3G3SV-BB007-E VFD 0.75kW 220V
  • OMRON CQM1H-MAB42 PLC Module
  • OMRON R88M-K75030T-S2 Servo Motor
  • Yaskawa SGMAH-03DAAA61 Servo Motor 200V 300W
  • OMRON F300-P Power Supply Unit
  • Land System 4 M1 Thermometer 65071800C-L35-A50
  • Yamatake MAH10-ME0100 ME-NET Module
  • Siemens Simatic 505 16 Slot PLC Rack
  • Yaskawa SGDH-02AE-OY Servo Driver 200W
  • SCE M68-2000 2-Axis Motion Controller
  • Zenith Controls K-1201 Transfer Switch Controller
  • Yaskawa SGDH-02AE-OY 200W Servo Driver
  • Yaskawa SGMAH-02AAA61D-0Y 200W Servo Motor