Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

S7-300 CPU 31xC 和 CPU 31x

F: | Au:佚名 | DA:2023-11-20 | 1096 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Routing and data record routing

Routing is the transmission of data across network boundaries. Information can be sent from sender to receiver across several networks.

The data logging route is an extension of the common route. For example, when the programming device is not directly connected to the target device

PROFIBUS DP subnets, but when connected to the CPU's PROFINET interface, SIMATIC PDM will make

Record routes with data. The data sent through the data recording route includes parameters of the participating field devices (slave stations)

Configuration, and device-specific information (e.g., set values, limit values, etc.). Data records the destination address structure of the route

Depends on the content of the data, i.e. the secondary station receiving the data.

When a programming device is assigned a different subnet from the target slave station, the data record route can also be read using the programming device

Set of parameters that already exist on the field device, edit them, and return them to the field device.

The field devices themselves do not need to support data record routing because they do not forward the received information.

Clock synchronization

1:intro

The CPU interface supports clock synchronization. The CPU can be programmed to act as a time master (with a default synchronization interval)

Interval) or time to run from the station.

Default value: No clock synchronization

Set synchronization mode

In the properties dialog box of HW Config, set the synchronization mode as follows:

In AS (on the central I/O bus) : Tab → Diagnostics/Clock (Tab → Diagnostics/Clock)

(Also applicable to MPI on CPU without DP interface)

● For MPI/DP or DP interface: Tab → Clock

● For PROFINET interface: Tab → Clock synchronization


2: interface

The following interfaces support clock synchronization:

● MPI interface

The CPU can be configured as either a time master or a time slave.

● DP interface

The CPU can be configured as either a time master or a time slave.

● PROFINET interface

The clock is synchronized with the CPU on the client through NTP.

● On the automation system in the central rack

The CPU can be configured as either a time master or a time slave.

Instructions

On many of these interfaces, the CPU cannot be used as a time slave.

CPU as time slave station

When acting as a time slave, a CPU receives synchronization frames only from a time master and uses that time as an internal time for that CPU

Between.

The CPU serves as the time master

When acting as a time master, the CPU broadcasts clock-sync frames at set synchronization intervals to synchronize them in the subnet to which they are connected

It stands.

Requirement: The CPU clock is no longer in the default state. The clock must be set at least once.

Clock synchronization as a time master begins with:

● After this time is initialized by SFC 0 "SET_CLK" or programming device function

● Use another time master, provided that the CPU is also programmed as an MPI/DP or PROFINET interface

Time operates from the station.

Instructions

The real-time clock of the CPU is not set in the following cases:

 before delivery

 after the mode selector switch is reset to factory Settings

 After firmware update

3. Point-to-point connection

Stats:

Point-to-point connections allow data to be exchanged over serial interfaces. Point-to-point connections can be used to interconnect programmable controllers, computations

Computer or third party system with communication function. It can also be adjusted according to the procedures of the communication partner.

3.1 Data Consistency

Stats:

A data area is consistent if it can be read or written to in the operating system as a block. Station to station

The data exchanged centrally between them should belong to a whole and originate from a processing cycle, that is, the data is consistent. If user

Programs that include programmed communication capabilities (for example, using XSEND/XRCV to access shared data) can pass

The "BUSY" parameter itself coordinates access to the corresponding data area.

Use the PUT/GET function

For some S7 communication functions that do not require blocks in CPU (server mode) user programs (e.g.,

In terms of PUT/GET or write/read access via OP communication, the scope of data consistency must be considered during programming.

The PUT/GET function of the S7 communication or the read/write variable operation through the OP communication are executed at the cycle control point of the CPU

Fine. To guarantee the defined hardware interrupt response time, the communication variables need to be in the form of blocks of up to 240 bytes, to/from

The copied user memory in the operating system loop control point is continuously copied. There is no guarantee for larger data areas

Data consistency.

Using PUT/GET functions and "Prioritized OCM communication"

If the operation is configured as "OCM communication by priority", the specified data consistency is lost (see the chapter "OP Communication (page 80)"). Therefore, data consistency must be ensured through user programs.

Keep the following consistent:

● Byte, word, double-word access (e.g. LMDx)

● SFC 14 "DPRD_DAT"

● SFC 15 "DPWR_DAT"

SFC 81 "UBLKMOV" (for copying up to 512 bytes of data)

It should also be understood that if OCM Communication by Priority is configured, the communication will not be changed at the loop control point

Quantities are continuously copied to/from working memory in blocks of up to 240 bytes. Therefore, it should be done while the user program is running

Copy the data.

                                                                                    Quantity name

                                                                                    ① Analog input and analog output

                                                                                    ② Digital input

                                                                                    ③ digital output

3.2 SNMP Communication Service

availability

SNMP V1, MIB-II communication services can be used with integrated PROFINET interfaces and using version 2.2 or later

Firmware for the CPU.

Stats

SNMP (Simple Network Management Protocol) is the standard protocol for TCP/IP networks.

3.3 Open communication over Industrial Ethernet

demand

● Since STEP 7 V5.4 + SP4

Feature

Cpus with integrated PROFINET interfaces support over industrial Ethernet starting with firmware V2.3.0 or V2.4.0

Open communication function (referred to as: Open IE communication)

Open IE communication provides the following services:

● Connection-oriented protocols

- TCP compliant with RFC 793, connection type B#16#01, firmware V2.3.0 and later

- TCP compliant with RFC 793, connection type B#16#11, firmware V2.4.0 and later

- ISO-on-TCP compliant with RFC 1006, firmware V2.4.0 and higher

● No connection protocol

- UDP compliant with RFC 768, firmware V2.4.0 and later

Attributes of the communication protocol

The following protocol types are included in data communication:

● Connection-oriented protocols:

These protocols establish a (logical) connection to a communication partner before the data transfer and then after the transfer is complete

The connection needs to be closed. When the security of data transmission is particularly important, connection-oriented protocols are used. Usually pass

Multiple logical connections can be established over a single physical cable.

FB for open communication over "Industrial Ethernet" supports the following connection-oriented protocols:

- TCP compliant with RFC 793 (connection types B#16#01 and B#16#11)

- ISO-on-TCP according to RFC 1006 (connection type B#16#12)

● No connection protocol:

These protocols can work without establishing a connection. This means there is no need to establish and terminate connections to remote partners

Answer. Connectionless protocols do not require confirmation to transmit data to remote partners; Therefore, data transmission is not secure.

FB for open communication over industrial Ethernet supports the following connectionless protocols:

- UDP compliant with RFC 768 (connection type B#16#13)


How to communicate with Open IE?

To allow the exchange of data with other communication partners, STEP 7 provides the following FB and under Communication Blocks in the Standard Library

UDT:

● Connection-oriented protocols: TCP, ISO-on-TCP

- FB 63 "TSEND" for sending data

- FB 64 "TRCV" for receiving data

- FB 65 "TCON" for connection

- FB 66 "TDISCON" for disconnection

- UDT 65 "TCON_PAR", whose data structure allows the connection to be parameterized

● No connection protocol: UDP

- FB 67 "TUSEND" for sending data

- FB 68 "TURCV" for receiving data

- FB 65 "TCON" for establishing local communication access points

- FB 66 "TDISCON" for parsing local communication access points

- UDT 65 "TCON_PAR", whose data structure can be parameterized to local communication access points

- UDT 66 "TCON_ADR" with remote partner addressing parameter data structure

Operator controls and indicators for CPU 313C-2 DP

                                                                                            Quantity name

                                                                                            ① Status and error indicators

                                                                                            ② Slot of SIMATIC MMC card (including eject device)

                                                                                            ③ Integrated input and output terminals

                                                                                            ④ Power connection

                                                                                            ⑤ 2. Interface X2 (DP)

                                                                                            ⑥ 1. Interface X1 (MPI)

                                                                                            ⑦ Mode selector

A block of data for parameterization

A block of data for parameterizing TCP and ISO-on-TCP connections

To use TCP and ISO-on-TCP configuration connections, you need to create a number that contains UDT 65 "TCON_PAR" medians

According to the structure of DB. This data structure contains all the parameters needed to establish the connection. Each connection requires such a number

According to the structure, you can arrange it in the global data store.

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

A block of data used to parameterize local communication access points using UDP

To assign parameters to the local communication access point, create one that contains the UDT 65 "TCON_PAR" data structure

DB. This data structure contains the parameters needed to establish a connection between the user program and the communication layer of the operating system

The CONNECT parameter of FB 65 "TCON" contains a reference to the address of the corresponding connection description (e.g.,

P#DB100.DBX0.0 Byte 64).

Instructions

Setting Connection Instructions (UDT 65)

You need to enter the communication interface in the "local_device_id" parameter of UDT65 "TCON_PAR" (for example

B#16#03: Communication via IE interface integrated with CPU 319-3 PN/DP).


Establish communication connection

● Suitable for TCP and ISO-on-TCP

Both communication partners call FB 65 "TCON" to establish a connection. Define which communication partner is used as master during parameterization

Dynamic communication endpoints and which are used as passive communication endpoints. To determine the number of possible connections, see your CPU's technology

The technical specifications.

The CPU automatically monitors and maintains active connections.

If the connection is interrupted, for example due to an open circuit or a telecommunication partner, the active party will attempt to re-establish the connection

Answer. You don't have to call FB 65 "TCON" again.

The active connection is terminated by calling FB 66 "TDISCON" or when the CPU is in STOP mode. Want to re-

To establish a connection, you must call FB 65 "TCON" again.

● Suitable for UDP

Both communication partners call FB 65 "TCON" to set up their local communication access point. This will be in the user program and operation

Connections are established between the communication layers of the system. Connections to remote partners are not established.

The local access point is used to send and receive UDP packets.

Distinguish between PROFINET IO and PROFINET CBA features

                                           PROFINET IO and CBA represent automation equipment for "industrial Ethernet" from two different perspectives.

Component-based automation divides the entire device into different functions. These functions are configured and programmed separately.

The device view provided by PROFINET IO is very similar to the PROFIBUS view. You can continue to configure and configure individual programmable controllers


  • OMRON CJ1W-MD261 Mixed I/O Module
  • Omron NJ301-1100 PLC CPU eCat EIP Specs
  • Omron F500-C15-ETN Vision System PLC Module
  • Modicon M241-24IO TM/T2UK PLC with Ethernet
  • SIXNET YS-800-001 RTU PLC Module
  • BEMAC UST-202-D Interface Board 1307D V08B2
  • Yaskawa JANCD-MMOIC-02 Drive Circuit Board
  • ABB 3BSE005028R1 SDCS-COM-1 Comm Board
  • Omron 3G3MX2-A4110 A4150 Inverter Drives Specs
  • KEYENCE CA-E100 PLC Module
  • GE IC693ALG223-GB Analog Input Module Specs
  • ABB BAILEY IMMFP01 Multi Function Processor System
  • SIEMENS 6FC5372 0AA00 0AA1 NCU 7202 Controller
  • Modicon TM241CE4 40I O Transistor Programmable Controller
  • SIEMENS 6ES7 315 2EH13 0AB0 CPU 3152 PN DP
  • NORIS A1 91 PCB Card Rack Module System
  • SIEMENS 6ES7 313 5BE01 0AB0 Compact CPU
  • SCHNEIDER ELECTRIC S144B MICROLOGIC 60A Trip Unit
  • CNI PLC269 v3 Control Module Board Rev H
  • ABB BAILEY IIMCP02 Processor Module
  • OMRON NT20S ST121 EV3 Operator Interface Terminal
  • OMRON NS-CA001 Video Input Unit
  • GE Fanuc IC695CHS012 RX3i Backplane
  • Allen Bradley 2711E-K14C6 PanelView 1400e Terminal
  • Siemens Sinamics CCB 10000432.71 Power Cell
  • Siemens 6SL3210-1SE21-8UA0 Power Module PM340
  • Yaskawa CIMR-F7A20P4 AC Drive
  • Beckhoff EP1918-0002 EtherCAT Box I/O Module
  • OMRON CQM1-TC001 Temperature Control Module
  • GE Fanuc SGHA36AT0400 Industrial Contactor
  • OMRON NJ501-1500 PLC Machine Automation Controller
  • Mitsubishi MAZAK QX084 Power Supply MELDAS 500 CNC
  • B&R 0AC808.9 PLC Automation Module
  • OMRON CP1H-XA40DT1-D PLC Module
  • G&W Electric PLC15 5111 011 15kV Capnut Assembly
  • GE DS200SLCCG3AGH PCB Circuit Board
  • Siemens SINUMERIK 6FC3981-4FD PLC Extension
  • OMRON F300-DC I/O Image Processing Unit
  • FANUC A06B-0314-B002 AC Servo Motor
  • GC-S84 Programmable Controller Logic Module
  • PASABAN MONTELEC MTC3001-DC Drive Control PLC
  • Allen Bradley 100E460EJ11 Auxiliary Contactor
  • Bosch Rexroth 1070075337-101 Card Parameters
  • HMS Anybus AB7646-F Gateway Specifications
  • Bosch 062633-303401 CNC Servo PLC Card
  • TI 500-5023 Series PLC Power Supply
  • Siemens C98043-A7002-L1-12 Circuit Board
  • Omron E5CC-RX3A5M-000 Controller
  • CN-8032-L Profinet Network Adapter Module
  • Siemens 3TK2804-0BB4 Safety Relay Details
  • Toledo TTLM-2-1M I/O Load Module
  • NORIS A1-91 PLC Rack Board Specifications
  • Mitsubishi A3ACPUR21 MELSEC PLC CPU Module
  • Beckhoff EP7041‑3002 EtherCAT Box Digital Input Module
  • REER EOS2E 1053 EOS2R 1053 Safety Light Curtain
  • Mitsubishi Q80BD-J71BR11 MELSECNET/H Interface Board
  • Omron 3G3IV-B4220-EV2 VFD 400V 22kW
  • Allen-Bradley 96844671 1785-LT3 PLC-5/12 Processor Module
  • Pasaban MTC3001-DC Drive Control PLC Module
  • Omron CJ1M-CPU11 V4.0 PLC CPU Module
  • ABB CM579-PNIO B3 Communication Module
  • B&R X20 AI 4221 Analog Module
  • Siemens 6SY7000-0AC80 PLC Module
  • GE 531X300CCHAFM5 Control Card
  • AB 810-A15C Inverse Time Relay
  • WITTENSTEIN LP120X-MF2-20 Planetary Gear
  • Mitsubishi Kakoki E-01B-4130 PLC I/O Modules
  • ABB DSQC643 Safety Control Board
  • Siemens G26004-A2105-P100-2 PCB
  • OMRON F350-C10E Image Processing Unit
  • FUJI UG430H-TS1 HMI Touch Panel
  • Westronics CB100188-01 Rev F Board
  • Siemens 7MH4900-3AA01 Weighing Module
  • Gilbert & Nash Tracker 2000 Control Cabinet
  • OMRON CJ1M-CPU22 CPU Unit
  • OMRON F3SJ-E0625P25 Light Curtain
  • Siemens 3VA2340-5HL32-0AA0 Breaker
  • Mitsubishi Melsec A61P A2NCPU PLC System
  • Aeco 158-02 DSP-02 PCB Card
  • FUJI NP1PS-32R CPU Module
  • Siemens 6SL3040-1MA01-0AA0 Control Unit CU320-2 PN
  • Fuji RYE.75D PLC Driver AC Drive
  • Electro Cam PS-6144-24-P16M09-L-MB Programmable Limit Switch
  • Siemens C98043-A7001-L2-4 CUD1 Control Board
  • Pilz 312070 PSSu H PLC1 FS SN SD Safety Module
  • Siemens Plc42q4200atsn Circuit Breaker Fuse Box
  • GE Fanuc IC695ALG708-AB Analog Output Module Rx3i
  • Siemens 6SE7036-5GK84-1JC2 IGD8 Gate Driver Board
  • Charmilles 813078 852029 PLC PCB Robocut 2 CNC EDM
  • Siemens 6SL3130-1TE24-0AA0 Smart Line Module
  • Pasaban MTC3001-DC Drive Control PLC Module
  • Modicon AS-P890-000 Remote I/O Processor Power Supply
  • Siemens PXC100-PE96.A PXC Modular Controller
  • TOYO KEIKI P:CARD5 AVH-R YH-212 Industrial Control Card
  • Omron NS5-SQ00B-V2 HMI Touch Screen 5.7 Inch
  • Sciemetric SigPOD 1202-0H00 Data Acquisition Module
  • GE Fanuc IC693CPU331W CPU Module Series 90-30
  • Square D 8903SVO11V02 Lighting Contactor 200A
  • Beckhoff C9900-P224 Power Supply Unit 24V 10A
  • HSD PE323 PLC I/O Module
  • Pillar AB6406-11A Power Control Board
  • GE Fanuc IC693CPU331W CPU Module
  • FANUC A61L-0001-0072 LCD Monitor
  • AB 20D-D-011-A-0-EYNANANE Drive
  • AB 1785-L20B PLC-5/20 Processor
  • Siemens SIREC P/PA Recorder 7ND3021
  • Siemens D2E160-AH01-17 Fan Blower
  • Eaton 101073735-001 LEG Module
  • AB 1404-M605B-ENT Powermonitor 3000
  • OMRON CJ1W-MAD42 Analog I/O
  • Omron CJ1M-CPU13 V3.0 PLC CPU Module
  • Pe323 HSD PLC Module Industrial Controller
  • Pasaban MTC3001-DC Drive Control PLC Module
  • Mitsubishi R02CPU PLC Module MELSEC iQ-R
  • B&R X20DC2395 Digital Output Module 32 Ch
  • Hoffman A30N24ALP Enclosure with PLC Addons
  • Rieter PLC with RMC 24/5V 10 RMC188-1 RMC RIO-1
  • Allen-Bradley 1790D-TN4V0 CompactBlock LDX Base Block 4 AI
  • National Instruments NI 9242 Analog Input Module 4-Channel
  • ABB AO820 3BSE008546R1 Analog Output Module
  • Moeller XVC-101-C192K-K82 PLC
  • AB 440F-C4000P MatGuard Controller
  • AB 1692-ZRCLSS Protection Module
  • Schneider S48896 PLC Module
  • FANUC A02B-0303-C205 I/O Module
  • AB 1785-LT4 PLC-5/10 Processor
  • AB 1746-NO8V SLC 500 Analog Output
  • OMRON CQM1-TC001 Temperature Unit