Communication interruption (L/A light off) EtherCAT P cable breakage or length exceeding the limit. Check if the cable is suitable for towing; Ensure that the module motor distance is ≤ 30m
Over temperature alarm, poor heat dissipation or incorrect installation direction. Check module spacing and whether the fan is blocked; Confirm that the installation position is with the interface facing downwards
At the moment of motor start-up, the overcurrent capacitor is not shaped (stored for a long time). Run it under no-load for 60 minutes according to section 5.1
The brake cannot be manually released. The service cable is not connected to 24V or the M8 pin is incorrectly confirmed. Pin 2 is connected to 24V+and pin 4 is connected to GND; Check if the cable is intact
TwinCAT failed to scan the motor electronic nameplate and attempted to switch to PreOp state for scanning; Check if the B23 connector is fully locked
Compliance and Certification
UL certification: applicable to the United States/Canada, requires the use of Class J fuses (maximum 25A), SCCR value 5kA, pollution level 2.
CE: Compliant with the Low Voltage Directive, EMC Directive RoHS。
Dual Use: The maximum rotation frequency of AMP8000 is limited to 599Hz and is not subject to export control (3A225 threshold 600Hz).