3. Rated short-circuit making capacity (Icm)
Breaking ability level Icm @ 415V
F (36kA) 76.5 kA
N (50kA) 105 kA
H (70kA) 154 kA
L (100kA) 220 kA
Power loss
1. Power loss per pole of the circuit breaker (In=630A)
Connection method: Phase pole (W) Neutral pole (W)
Cage terminal 37.3 21.2
Wiring terminal 37.3 21.2
External wiring terminal 42.1 23.1
Expansion terminal 44.7 24.1
Rear wiring terminal 45.0 24.3
Plug in version 85.3 40.5
With leakage protection 57.2 28.2
2. Power loss per pole of isolation switch (In=630A)
Connection method: Phase pole (W) Neutral pole (W)
Cage terminal 37.3 37.3
Expansion terminal 44.7 44.7
Rear wiring terminal 45.0 45.0
Plug in version 85.3 85.3
With leakage protection 57.2 57.2
Reduced capacity usage
1. Temperature reduction
The ambient temperature has a significant impact on the current carrying capacity of circuit breakers. The following table shows the maximum continuous operating current at different temperatures:
In (A) 10°C 20°C 30°C 40°C 50°C 60°C 70°C
250 336 307 279 250 220 193 166
320 416 384 352 320 288 256 224
400 475 460 425 400 360 320 280
500 600 550 525 500 455 410 365
630 700 683 650 630 580 530 480
2. Altitude Capacity Reduction
When the installation altitude exceeds 2000 meters, it is necessary to reduce the capacity according to the following coefficient:
Altitude (m) ≤ 2000 3000 4000 5000
Working voltage Ue (V) 690 590 520 460
Rated current In 1 × In 0.98 × In 0.93 × In 0.9 × In
3. Environmental adaptability
Climate conditions: Complies with IEC/EN 60947-1 Appendix Q, Cat. F, suitable for temperature, humidity, vibration, shock, and salt spray environments
Electromagnetic compatibility: Complies with Appendix F of IEC/EN 60947-2
Pollution level: Level 3
Accessories and Options
The M4 series offers a wide range of electrical and mechanical accessories to meet different application needs.
1. Leakage protection module
Parameter standard type LED type
Type A - S A - S
Rated current 630A 630A
Rated voltage 500V AC 500V AC
Leakage action current I Δ n 0.03/0.3/1/3 A 0.03/0.3/1/3 A
Delay time Δ t 0/0.3/1/3 s 0/0.3/1/3 s
50% I Δ n pre alarm: None
Model (400A) T7082/400 T7081/400
Model (630A) T7092/630 T7091/630
2. Release device
Split release (ST)
Voltage specifications: 24V, 48V, 110-130V, 220-250V, 380-440V (AC/DC)
Voltage range: 70% to 110% Un
Action time: ≤ 50 ms
Power consumption: 300 VA/W
Undervoltage Release (UVR)
Voltage specifications: 24V AC/DC, 48V DC, 110-125V AC, 220-240V AC, 380-415V AC
Operating voltage: 35% to 70% Un
Reset voltage: 85% to 110% Un
Action time: ≤ 50 ms
Delay module: can be equipped with 800ms delay module (M7000E/024, M7000MR/230, M7000MR/400)
3. Auxiliary contacts
Model: M7X01
Contact form: 1NO/NC conversion contact
Rated current: 3A @ 250V AC
Configuration: M4 supports a maximum of 2 auxiliary contacts, 1 fault signal contact, and 1 release
4. Rotate the handle
Type and Model Description
Direct standard M7447 black handle
Direct emergency M7R14 red/yellow handle
Variable depth standard T7449 IP55, black
Variable depth emergency T7449E IP55, red/yellow
Lock attachment M7R17 for variable depth handle, requires universal lock cylinder
5. Electric operating mechanism
Energy storage electric operating mechanism
Model: M7475P/024, M7475P/048, M7475P/110, M7475P/230
Voltage: 24V, 48V, 110V, 230V AC/DC
Closing time: ≤ 100 ms
Energy storage time: ≤ 2 seconds
Mechanical lifespan: 10000 cycles
Direct acting electric operating mechanism
Model: M740230
Voltage: 230V AC
Closing time: ≤ 550 ms
Opening time: ≤ 450 ms
Mechanical lifespan: 10000 cycles
6. Connect attachments
Cage terminal
Standard type: M7400, supports 1 × 240mm ² (flexible) or 1 × 300mm ² (rigid)
High capacity type: M7400/2, supports 2 × 185mm ² (flexible) or 2 × 240mm ² (rigid)
Expansion terminal
3P model: M7430/3
4P model: M7430/4
Rear wiring terminal
3P model: M7450/P
4P model: M7451/P
7. Insertion and extraction attachments
Insertion attachment
Special terminals: M7B11 (3P), M7B12 (4P)
Front wiring base: M7B13 (3P), M7B14 (4P)
Rear wiring base: M7B15 (3P), M7B16 (4P)
With leakage base: M7B17 (4P front wiring), M7B18 (4P rear wiring)
Pull out the handle: M7B19
24 pin connector: M7B20
Pull out attachment (Debro lift mechanism)
Base: M7B22 (3P), M7B23 (4P), M7B24 (4P with leakage)
Position signal contact: M7T910N
Pull out the handle: M7T412
Auxiliary contact: M7B21 (up to 2)
8. Mechanical accessories
Padlock: M7045, used to lock in the "off" position
Interphase insulation partition: M7295
Terminal protective cover: M7475 (3P), M7476 (4P)
IP20 terminal cover: M7C11 (3P), M7C12 (4P)
9. Universal key lock
Support locking of rotating handle, electric operating mechanism, insertion mechanism, and extraction mechanism:
Lock cylinder type and model
Randomly encoded flat key M7K01
Fixed code EL43525 M7K02
Fixed code EL43363 M7K03
Randomly encoded star key M7K04

Release curve and current limiting curve
1. Thermal magnetic release curve
The M4 circuit breaker provides a typical thermal magnetic trip curve, including:
Cold state characteristic (curve 1): the action time of the circuit breaker when it is in a cold state
Curve 2: The operating time of a circuit breaker when it is in a hot state
The overload protection section has inverse time characteristics, while the short circuit protection section has instantaneous action with adjustable action values (5-10 × In).