6.3 Factory reset
Go to the CoE Online tab and find object 0x1011:01 (Restore default parameters).
Enter 0x64616F6C (ASCII "load") in the Set Value dialog box and confirm.
All BackUp objects will be reset to factory settings. This operation can be automatically executed through the startup list for automatic parameterization when replacing terminals.
Maintenance recommendations and spare parts information
Recommended cycle notes for inspection items
The fastening of motor wiring terminals may become loose due to annual vibration, causing poor contact and overheating.
Ventilation openings should be cleaned every six months using a vacuum cleaner to remove dust, and the use of compressed air is prohibited.
If the fan module (ZB8610) is used continuously for 5 years, it is recommended to replace it preventively.
Parameter backup (startup list): Export the CoE configuration to the startup list after each modification for easy terminal replacement.