Circuit breaker time programming: Set the jumper according to the actual closing time+20ms, and check the switching circuit of multiple circuit breakers.
Upper/lower limit voltage: Adjust according to the system rating, usually set the upper limit to 110% rated and the lower limit to 90% rated.
Δ V and Δ F: Based on the allowed impulse current of the generator or system, Δ V is generally 2-3V and Δ F is 0.1-0.2Hz.
6.2 Common Problems and Solutions
Possible causes and solutions for the phenomenon
READY light does not light up. If a certain condition is not met, check the voltage, Δ V, and Δ F indicator lights one by one. Adjust the corresponding knob or check the input
The closing command is not issued, and the operator window is not closed or exceeds the window to check the operator contacts and window settings; Or disable this option
The closing angle is too large, and the programming of the circuit breaker time is inaccurate. Re measure the closing time and adjust the jumper, paying attention to+20ms correction
Frequent missed zero phase angle Δ F is too small or the frequency is unstable. Check if the slip is close to the dead zone (<0.005Hz), or adjust the Δ F limit
Failure to reset the power supply after anti bounce and not disconnecting it for enough time to ensure a power outage of>10 seconds; Or cancel the anti bounce option (customization required)
Poor coordination with M-0194, incorrect signal wiring or improper M-0194 parameters. Check the interconnection circuit and verify the voltage/frequency adjustment settings of M-0194
6.3 Internal Adjustment of Operator Window
To activate the operator window, open the chassis cover and follow the steps in Section 3.0:
Measure the voltage between the test point (small metal hook) and the negative electrode of the capacitor, and calculate according to the required maximum phase angle: V=Φ _max × 0.056 (for a range of 0.05~0.5Hz) or the same formula (for a range of 0.005~0.05Hz).
Adjust R160 to calculate the voltage value.
Adjust R148 to the desired maximum time window (see instructions for rotation direction).
Installation and physical specifications
Dimensions: 19 "wide x 3.5" high x 13 "deep (standard rack 2U).
Weight: Approximately 15 pounds (shipping 20 pounds).
Installation method: Horizontal installation is standard, vertical or GE GES21A retrofit panel is optional.
Environmental tolerance: -40 ℃ to+80 ℃, 95% humidity without condensation, PCB triple proof coating.
Transient protection: Complies with ANSI/IEEE C37.90.1-1989, with input/output isolated from ground and withstand voltage of 1500Vac.
Optional transparent cover to prevent accidental contact with the knob, while providing a physical replacement version of GE GES21A (different in appearance, completely identical in electrical).
Design version evolution
Understanding version changes helps identify the characteristics of older devices:
M-0193 (original version): No operator window.
M-0193A: Added operator window and optimized worst-case phase angle error.
M-0193B (current version): Added input noise filter, modified compatibility interface with M-0194 (providing high/low voltage indication), increased contact capacity of status relay, and improved installation method of panel potentiometer.
All subsequent versions can replace earlier versions, but not necessarily (due to increased functionality).