Load current CT inspection: Short circuit the LDC-CT secondary side in a live state, connect a 200mA range ammeter in series to measure the load current, and confirm that it corresponds correctly to the 0.2A full range.
LDC polarity verification: Remove the short-circuit device, apply sufficient+R compensation, the voltage regulator should delay the action and boost the voltage, and confirm that the CT polarity is correct.
On site operation verification: Place the switch in the MANUAL position and use the RAISE/OFF/OWER switch to verify that the motor direction is correct.
Automatic mode verification: Place the switch in the AUTO position and observe the regulator automatically operating based on voltage deviation.

Common faults and their solutions
Possible causes and solutions for the fault phenomenon
After installation, there is no display on the controller. The control voltage fuse is blown and the wiring is incorrect. Check the F2 fuse and confirm that the voltage of TB1-10 and TB1-8 is normal
Manual operation is normal, but automatic does not operate. AUTO/OFF/MANUAL is not in the AUTO position, and automatic jumper removal is prohibited. Check the switch position and confirm that jumper # 15 is in place
Neutral light not on, S1 switch position error, voltage regulator not in neutral position, circuit fault check S1 position, confirm that the voltage regulator is in neutral gear, check TB1-11 circuit
LDC compensation direction is reversed, CT polarity is reversed, and phase angle correction is incorrect. Check CT wiring S1/S2 and adjust CT-VT phase angle correction settings
Operation counter does not count contacts with "wet" voltage, wiring error confirms TB1-13 has no external voltage, check grounding circuit
The SCADA command is ignored. SCADA CUTOFF is in the LOCAL position and the firmware version is incompatible. Set the switch to REMOTE and confirm that the firmware version meets the requirements
The voltage drop is not effective. The external contact did not provide+12V, and the wiring error was confirmed. TB2-28 provided+12V. Check the wiring of TB1-2/TB1-7
Environmental and Physical Specifications
Temperature range: -40 ℃ to+85 ℃
Humidity: 95% without condensation
Transient protection: meets ANSI/IEEE C37.90.1-1989, with input/output isolation withstand voltage of 1500Vac
Dimensions (including M-2001): 15.00 "high x 9.25" wide x 4.185 "deep
Weight: The compatible panel weighs approximately 2.44 pounds, including M-2001 weighing approximately 6.13 pounds