Implemented by installing a leakage module at the bottom, suitable for 400A and 630A specifications
Module models: GS400-630, GL400-630
Provide 50% I Δ n pre alarm signal output
M5 1600: Main incoming circuit breaker
M5 1600 is the largest capacity model in the MEGATIKER series, suitable for incoming line protection of main distribution cabinets.
Rated current: 500A, 630A, 800A, 1000A, 1250A, 1600A
Breaking capacity: N (50kA), H (70kA), L (100kA)
Electronic protection: Li, Lsi, Lsig, supports high-precision adjustment
Measurement function: Full power measurement, including total harmonic distortion (THD)
Pull out version: supports live plugging and easy maintenance

Installation method and accessories
The MEGATIKER series offers a variety of installation and accessory options to meet different application needs.
1. Installation method
Fixed: directly installed on the panel or DIN rail
Plug in: Installed through a dedicated base for quick replacement
Pull out type: equipped with an operating handle, with three positions for connection, testing, and disconnection, supporting locking function
2. Electrical accessories
Auxiliary contact: indicates the opening and closing status of the circuit breaker
Alarm contact: indicating the trip status
Split release: remote control disconnection
Undervoltage release: automatically disconnects when the voltage is too low
Electric operating mechanism: supports remote closing and opening of switches
3. Mechanical accessories
Rotating handle: direct and extended, supports emergency release
Mechanical interlocking: used for interlocking between two circuit breakers
Locking device: padlock, key lock, to prevent accidental operation
4. Connect attachments
Wiring terminals: front wiring, rear wiring, long terminals
Cable clamp: suitable for copper and aluminum cables, supporting single or double cables
Protective cover: IP2X protection level, ensuring safe wiring
Release curve and selective protection
The MEGATIKER series offers multiple release curves to ensure coordinated protection with upper and lower level equipment.
1. Thermal magnetic release curve
Overload protection: bimetallic strip with cold and hot characteristics
Short circuit protection: electromagnetic trip, instantaneous action
Typical curves: M1 160, M2 250, M3 series M4 630、M5 1600
2. Electronic release curve
Long delay (L): Ir and tr are adjustable to achieve precise overload protection
Short delay (S): Isd and tsd are adjustable to achieve selective protection
Instantaneous (I): Ii fixed or adjustable
Ground fault (G): Ig and TG are adjustable
3. Logic and dynamic selectivity
Logical selectivity: achieved through communication between electronic release devices, ensuring complete upstream and downstream selection
Dynamic selectivity: By adjusting the trip delay, achieve high-level selectivity
Environmental adaptability
The MEGATIKER series products have undergone rigorous environmental testing and are suitable for various working conditions:
Working temperature: -25 ° C to+70 ° C
Storage temperature: -25 ° C to+85 ° C
Humidity: 95% RH, no condensation
Capacity reduction at altitude: Capacity reduction is required for altitudes above 2000m, with a maximum of 5000m
Electromagnetic compatibility: Compliant with IEC EN 60947-2 standard, insensitive to electromagnetic interference
Isolation switch and motor protection circuit breaker
1. Isolation switch (MS and MW series)
MS series: M1 160, M2 250, M3 125/160/250, M4 630, M5 1600
MW series: MW63, MW160, MW250, MW630, MW1600
Features: Visual breakpoint, high short-term withstand current, suitable for isolation use
2. Motor protection circuit breaker (MP series)
MP1 160:16-63A, Electromagnetic protection only
MP2 250:100-250A, Electromagnetic protection only
MP3 250:6.3-220A, Electromagnetic protection only
MP4 630:400-630A, Electromagnetic protection only
MP5 1600:800-1000A, Electromagnetic protection only
Application: Suitable for direct starting of electric motors, used in conjunction with contactors
Application scenarios and selection suggestions
The MEGATIKER series is widely used in the following scenarios:
Industrial power distribution: main incoming cabinet, distribution cabinet, motor control center
Building electrical: high-rise buildings, commercial complexes, data centers
Infrastructure: Rail transit, airports, hospitals
OEM equipment: compressors, pump stations, air conditioning units
When selecting, it is recommended to consider the following factors:
Rated current: selected according to the load current
Breaking capacity: selected based on system short-circuit current
Protection function: Do you need electronic release, grounding protection, and measurement function
Installation method: fixed, plug-in or pull-out
Attachment requirements: auxiliary contacts, electric operation, interlocking, etc