The DEIF AGC-100 series is an economical controller designed specifically for generator control, integrating functions such as generator protection, automatic start/stop, synchronization, grid connection, and power management. This series of controllers is widely used in backup power sources, mobile generator sets, and industrial self owned power stations due to its compact size, flexible configuration, and reliable performance. This article is based on the AGC-100 installation manual, systematically explaining the installation requirements, terminal functions, wiring specifications, and communication configuration of the equipment, providing comprehensive technical guidance for installation engineers and switchgear manufacturers.
Product Overview
1. Series model
The AGC-100 series includes multiple models to adapt to different application scenarios:
Model Function Description
AGC 112 Island mode operation, controlling the generator circuit breaker
AGC 113 automatic mains fault switching mode, controlling the generator circuit breaker and main circuit breaker
AGC 145 power management mode, controlling the generator circuit breaker and main circuit breaker
AGC 146 power management mode, controlling the generator circuit breaker, main circuit breaker, and bus tie circuit breaker
2. Main characteristics
Integrated measurement: Three phase true RMS measurement, parameters such as voltage, current, frequency, power, etc
Protection functions: reverse power, overcurrent, overvoltage, undervoltage, overclocking, underflocking, etc
Engine interface: speed sensor input, charging generator monitoring, start/stop control
Communication interface: Modbus RTU, CAN bus (J1939 engine communication)
Scalability: Supports external I/O modules and additional operation panels
3. Certification and Standards
Compliant with EN 61010-1 electrical safety standard
Compliant with EN 61000-6-1/2/3/4 electromagnetic compatibility standards
UL/cUL certification (applicable to UL508 listed generator components)
Protection level: IP52 (standard), optional IP65 (with sealing gasket and additional buckle)
Installation requirements and mechanical dimensions
1. Installation method
AGC-100 is designed for embedded installation on the front of the panel. The standard configuration comes with 8 fixed buckles to achieve IP52 protection level. If IP65 protection is required, an optional L (including 12 buckles and gaskets) must be ordered.
2. Panel opening size
The size of the panel opening is:
Height: 151.00 mm (+1.00 mm)
Width: 211.00 mm (+1.00 mm)
The imperial unit is 5.94 inches x 8.31 inches (+0.04 inches)
3. Tightening torque
Partial torque
Panel door installation 0.15-0.20 Nm (1.4-1.8 lb in)
Plug terminal 0.5 Nm (4.4 lb in)
AOP-1/AOP-2 panel installation 0.7 Nm (6.2 lb in)
Sub-D connector screw 0.2 Nm (1.8 lb in)
DC-DC converter terminal 0.5 Nm (4.4 lb in)

Terminal definition and functional description
The AGC-100 is equipped with multiple terminal blocks at the rear, including power supply, digital input, analog input, speed input, relay output, voltage and current measurement, communication interface, etc.
1. Power and status output (terminals 1-4)
Terminal functional technical parameters
1. Positive pole of power supply 6-36 V DC (UL/cUL: 7.5-32.7 V DC)
2. Negative GND of power supply
3-4 state output/configurable 1 A @ 24 V DC/V AC, resistive load
Terminal 3-4 is the output of the microprocessor watchdog, and the relay is engaged during normal operation; Relay release in case of power failure or microprocessor malfunction.
2. Multi functional input (terminals 5-8)
Terminal Function Description
5 common terminals for terminals 6-8
6 multifunctional inputs 1 can be configured as 4-20mA input, digital input Pt1000
7 Multi functional inputs 2 Same as above
8 Multi functional inputs 3 Same as above
These inputs can be configured as remote alarm suppression, operation mode switching, analog monitoring, or temperature sensor inputs.
3. Digital input (terminals 9-15)
Terminal Function Description
9 common end for terminals 10-15
10-15 digital input 1-6 12/24V DC bidirectional optocoupler, configurable
Digital input can be used for emergency stop, start enable, operation feedback, mode selection, alarm confirmation and other functions.
4. Speed input (terminals 16-18)
Terminal Function Description
16 RPM input (MPU) magneto electric speed sensor (2-wire)
17 RPM-GND speed sensor common terminal
18 RPM input (W/L) magneto electric, PNP, NPN or charging generator W terminal input
The speed input supports various signal sources such as magneto electric sensors, Hall effect sensors, and charging generator W terminals.
5. Relay output (terminals 19-27)
Terminal Function Contact Capacity
19 Public end (emergency stop) -
20 Emergency stop input and common terminal -
21-23 relay output 1-3 2 A @ 30 V DC/V AC
24-25 relay output 4 8 A @ 30 V DC/V AC
26-27 relay output 5 8 A @ 30 V DC/V AC
The relay output can be configured as: running coil, stopping coil, starting preparation, starting motor, closing, opening, alarm horn, status OK, etc. Supports dual system engines (independent operation coil and stop coil).
6. Three phase voltage and current input (terminals 28-48)
Main voltage input:
Terminal 28: L1
Terminal 29: N
Terminal 30: L2
Terminal 32: L3
Generator voltage input:
Terminal 33: L1
Terminal 34: N
Terminal 36: L2
Terminal 38: L3
Generator current input:
Terminal 39-40: L1 current (s1/s2)
Terminal 41-42: L2 current (s1/s2)
Terminal 43-44: L3 current (s1/s2)
Circuit breaker relay:
Terminal 45-46: Generator circuit breaker (normally open, 2A @ 30V DC/250V AC)
Terminal 47-48: Main circuit breaker (normally closed, optional M19 for normally open)
7. Communication interface (terminals 49-59)
Modbus RS-485:
Terminal 49: B (-)
Terminal 50: GND
Terminal 51: A (+)
CAN bus (port A):
Terminal 53: CAN-H
Terminal 54: COM
Terminal 55: CAN-L
Optional CAN bus (port B):
Terminals 57-59: Used for AOP-2 additional operation panel or external I/O module (optional H8)
Wiring specifications
1. DC power supply wiring
The auxiliary power input needs to be protected by a 2A slow melting fuse
Power supply voltage range: 6-36 V DC
Suggest using DEIF DCP-2 power supply or equivalent products
2. Digital input wiring
The digital input is a bidirectional optocoupler type, and the typical input circuit is as follows:
Input conduction voltage: 8-36 V DC
Input shutdown voltage:<2 V DC
Typical input impedance: 4.7 k Ω
3. Circuit breaker control
AGC-100 supports three types of circuit breakers:
Circuit breaker type closing output opening output
Pulse type requires
Continuous type required or not
Compact models require
Select the circuit breaker type through PC configuration software and allocate the corresponding relay output in the I/O configuration.
4. Monitoring of charging generator (D+and W terminals)
AGC-100 supports two monitoring methods for charging generators:
Method 1: Connect the D+terminal to terminal 12
Connect the positive terminal of the battery through a REX resistor (12V system: 47 Ω/4W; 24V system: 100 Ω/6W)
When starting, the current flows through REX to assist in exciting the generator
After the generator generates electricity, the voltage at terminal 12 increases, cutting off the excitation current and providing operational feedback
Method 2: Connect the W terminal to the speed input (terminal 18)
Directly monitor the AC frequency of the charging generator
Provide speed signal and operational status feedback
5. AC measurement wiring
Three phase system (AGC 112):
The generator voltage is directly connected to terminals 33-38
The generator current is connected to terminals 39-44 through CT
Suitable for islanded operation mode
Three phase AMF system (AGC 113):
Simultaneously connect the main voltage (terminals 28-32) to the generator voltage
Suitable for automatic mains power fault switching applications
Single phase system:
Connect the voltage to L1 and N
Current connection to L1 CT
Phase separation system:
Voltage connection to L1, L2, and N
Connect current to L1 and L2 CT
6. Power management wiring (AGC 145/146)
AGC 145 (Main Circuit Breaker):
Connect the main voltage, generator voltage, and current
Relay output controls generator circuit breaker and main circuit breaker
AGC 146 (main circuit breaker+bus tie circuit breaker):
In addition to the main circuit breaker, additionally control the bus tie circuit breaker
Suitable for power management between two busbars

Communication interface configuration
1. Modbus RTU
Interface: RS-485, 2-wire system
Supporting protocols: Modbus RTU or ASCII
Maximum bus length: 300 meters
Cable recommendation: Belden 3106A or equivalent (22 AWG shielded twisted pair, shielding coverage ≥ 95%)
Terminal resistor: When the bus length exceeds 30 meters, 120 Ω terminal resistors need to be installed at both ends
2. CAN bus engine communication
Interface: CAN J1939
Maximum bus length: 300 meters
Cable recommendation: Belden 3106A or equivalent (22 AWG shielded twisted pair, shielding coverage ≥ 95%)
Terminal resistor: 120 Ω terminal resistors need to be installed at both ends of the bus
3. External I/O modules
Connected via CAN bus, supports optional H8 external I/O module
Bus length ≤ 300 meters
Use Belden 3106A or equivalent cable
When sharing the bus with AOP-2, the total terminal resistance should be 120 Ω
4. Additional operation panel AOP-2
Connect through CAN port B
Comes with DC-DC converter and 2 x 1 meter RJ12 connection cable
Maximum bus length: 300 meters
Use Belden 3106A or equivalent cable
Summary of Technical Specifications
1. Electrical parameters
Project Parameters
Auxiliary power supply 6-36 V DC (UL/cUL: 7.5-32.7 V DC)
Maximum power consumption of 8W
Measurement voltage range 100-25000 V (primary side)
Measure current range 5-9000 A (primary side, through CT)
Measurement frequency 30-70 Hz
Accuracy Class 1.0
2. Input/output specifications
Project Parameters
Digital input 12/24V DC bidirectional optocoupler, input impedance 4.7k Ω
Multi functional input 4-20mA, digital input Pt1000
Speed input magneto electric, PNP, NPN, W terminals
Relay output (low power) 2A @ 30V DC/V AC
Relay output (high power) 8A @ 30V DC/V AC
Status output 1A @ 24V DC/V AC
3. Environmental conditions
Project Parameters
Working temperature -25 ℃ to+70 ℃
Storage temperature -40 ℃ to+70 ℃
Humidity 95% RH (non condensing)
Protection level IP52 (standard), IP65 (optional L)
4. Precautions for UL application
The controller is only applicable to generator components that have been certified by UL
Power supply voltage range: 7.5-32.7 V DC
Use 60/75 ° C copper wire
Installed on the flat surface of Type 1 casing
Compliant with NEC (USA) or CEC (Canada) specifications
Installation precautions
1. Safety Warning
Installation work can only be carried out by authorized electrical personnel
It is strictly prohibited to touch the AC measurement input terminal when the equipment is live
Pay attention to electrostatic protection during installation
The factory setting is the average value, and adjustments must be made according to the actual generator set before operation
2. Wiring requirements
All AC measurement circuits must be protected by 2A slow melting fuses
When the relay output drives inductive loads, a noise suppression circuit must be installed
Modbus and CAN buses must use shielded twisted pair cables, with the shielding layer grounded at one end
Bus terminal resistors must be installed according to specifications
3. Check after installation
Confirm that all terminals are securely connected and the torque meets the requirements
Confirm the size of the panel opening and the installation of the buckle in place
Confirm that the power polarity is correct and the voltage range meets the specifications
Confirm that the communication cable wiring is correct and the terminal resistor has been installed
Summary of Application Value
The AGC-100 generator controller provides a cost-effective solution for generator control with its compact design, flexible configuration, and reliable performance. Its main value lies in:
Easy installation: standard panel embedded installation, regular hole size, simple buckle fixation
Clear terminals: The terminal block has clear functional zoning, complete labeling, and is easy to connect
Flexible configuration: supports multiple operating modes (islanding, AMF, power management) to adapt to different application scenarios
Rich interfaces: digital input, multifunctional input, speed input, relay output, communication interfaces are all available
Communication capability: Supports Modbus RTU and CAN J1939, can be connected to the upper computer monitoring system
Scalability: Supports external I/O modules and additional operation panels to meet complex system requirements
Environmental adaptation: Wide working temperature range, IP52/IP65 protection level, suitable for various installation environments