DEIF AGC 100 series generator set controller

F: | Au:FAN | DA:2026-03-24 | 356 Br: | 🔊 点击朗读正文 ❚❚ | Share:

DEIF AGC-100 Generator Set Controller: Complete Installation and Wiring Guide

The DEIF AGC-100 series is an economical controller designed specifically for generator control, integrating functions such as generator protection, automatic start/stop, synchronization, grid connection, and power management. This series of controllers is widely used in backup power sources, mobile generator sets, and industrial self owned power stations due to its compact size, flexible configuration, and reliable performance. This article is based on the AGC-100 installation manual, systematically explaining the installation requirements, terminal functions, wiring specifications, and communication configuration of the equipment, providing comprehensive technical guidance for installation engineers and switchgear manufacturers.


Product Overview

1. Series model

The AGC-100 series includes multiple models to adapt to different application scenarios:

Model Function Description

AGC 112 Island mode operation, controlling the generator circuit breaker

AGC 113 automatic mains fault switching mode, controlling the generator circuit breaker and main circuit breaker

AGC 145 power management mode, controlling the generator circuit breaker and main circuit breaker

AGC 146 power management mode, controlling the generator circuit breaker, main circuit breaker, and bus tie circuit breaker

2. Main characteristics

Integrated measurement: Three phase true RMS measurement, parameters such as voltage, current, frequency, power, etc

Protection functions: reverse power, overcurrent, overvoltage, undervoltage, overclocking, underflocking, etc

Engine interface: speed sensor input, charging generator monitoring, start/stop control

Communication interface: Modbus RTU, CAN bus (J1939 engine communication)

Scalability: Supports external I/O modules and additional operation panels

3. Certification and Standards

Compliant with EN 61010-1 electrical safety standard

Compliant with EN 61000-6-1/2/3/4 electromagnetic compatibility standards

UL/cUL certification (applicable to UL508 listed generator components)

Protection level: IP52 (standard), optional IP65 (with sealing gasket and additional buckle)


Installation requirements and mechanical dimensions

1. Installation method

AGC-100 is designed for embedded installation on the front of the panel. The standard configuration comes with 8 fixed buckles to achieve IP52 protection level. If IP65 protection is required, an optional L (including 12 buckles and gaskets) must be ordered.

2. Panel opening size

The size of the panel opening is:

Height: 151.00 mm (+1.00 mm)

Width: 211.00 mm (+1.00 mm)

The imperial unit is 5.94 inches x 8.31 inches (+0.04 inches)

3. Tightening torque

Partial torque

Panel door installation 0.15-0.20 Nm (1.4-1.8 lb in)

Plug terminal 0.5 Nm (4.4 lb in)

AOP-1/AOP-2 panel installation 0.7 Nm (6.2 lb in)

Sub-D connector screw 0.2 Nm (1.8 lb in)

DC-DC converter terminal 0.5 Nm (4.4 lb in)

Terminal definition and functional description

The AGC-100 is equipped with multiple terminal blocks at the rear, including power supply, digital input, analog input, speed input, relay output, voltage and current measurement, communication interface, etc.

1. Power and status output (terminals 1-4)

Terminal functional technical parameters

1. Positive pole of power supply 6-36 V DC (UL/cUL: 7.5-32.7 V DC)

2. Negative GND of power supply

3-4 state output/configurable 1 A @ 24 V DC/V AC, resistive load

Terminal 3-4 is the output of the microprocessor watchdog, and the relay is engaged during normal operation; Relay release in case of power failure or microprocessor malfunction.

2. Multi functional input (terminals 5-8)

Terminal Function Description

5 common terminals for terminals 6-8

6 multifunctional inputs 1 can be configured as 4-20mA input, digital input Pt1000

7 Multi functional inputs 2 Same as above

8 Multi functional inputs 3 Same as above

These inputs can be configured as remote alarm suppression, operation mode switching, analog monitoring, or temperature sensor inputs.

3. Digital input (terminals 9-15)

Terminal Function Description

9 common end for terminals 10-15

10-15 digital input 1-6 12/24V DC bidirectional optocoupler, configurable

Digital input can be used for emergency stop, start enable, operation feedback, mode selection, alarm confirmation and other functions.

4. Speed input (terminals 16-18)

Terminal Function Description

16 RPM input (MPU) magneto electric speed sensor (2-wire)

17 RPM-GND speed sensor common terminal

18 RPM input (W/L) magneto electric, PNP, NPN or charging generator W terminal input

The speed input supports various signal sources such as magneto electric sensors, Hall effect sensors, and charging generator W terminals.

5. Relay output (terminals 19-27)

Terminal Function Contact Capacity

19 Public end (emergency stop) -

20 Emergency stop input and common terminal -

21-23 relay output 1-3 2 A @ 30 V DC/V AC

24-25 relay output 4 8 A @ 30 V DC/V AC

26-27 relay output 5 8 A @ 30 V DC/V AC

The relay output can be configured as: running coil, stopping coil, starting preparation, starting motor, closing, opening, alarm horn, status OK, etc. Supports dual system engines (independent operation coil and stop coil).

6. Three phase voltage and current input (terminals 28-48)

Main voltage input:

Terminal 28: L1

Terminal 29: N

Terminal 30: L2

Terminal 32: L3

Generator voltage input:

Terminal 33: L1

Terminal 34: N

Terminal 36: L2

Terminal 38: L3

Generator current input:

Terminal 39-40: L1 current (s1/s2)

Terminal 41-42: L2 current (s1/s2)

Terminal 43-44: L3 current (s1/s2)

Circuit breaker relay:

Terminal 45-46: Generator circuit breaker (normally open, 2A @ 30V DC/250V AC)

Terminal 47-48: Main circuit breaker (normally closed, optional M19 for normally open)

7. Communication interface (terminals 49-59)

Modbus RS-485:

Terminal 49: B (-)

Terminal 50: GND

Terminal 51: A (+)

CAN bus (port A):

Terminal 53: CAN-H

Terminal 54: COM

Terminal 55: CAN-L

Optional CAN bus (port B):

Terminals 57-59: Used for AOP-2 additional operation panel or external I/O module (optional H8)


Wiring specifications

1. DC power supply wiring

The auxiliary power input needs to be protected by a 2A slow melting fuse

Power supply voltage range: 6-36 V DC

Suggest using DEIF DCP-2 power supply or equivalent products

2. Digital input wiring

The digital input is a bidirectional optocoupler type, and the typical input circuit is as follows:

Input conduction voltage: 8-36 V DC

Input shutdown voltage:<2 V DC

Typical input impedance: 4.7 k Ω

3. Circuit breaker control

AGC-100 supports three types of circuit breakers:

Circuit breaker type closing output opening output

Pulse type requires

Continuous type required or not

Compact models require

Select the circuit breaker type through PC configuration software and allocate the corresponding relay output in the I/O configuration.

4. Monitoring of charging generator (D+and W terminals)

AGC-100 supports two monitoring methods for charging generators:

Method 1: Connect the D+terminal to terminal 12

Connect the positive terminal of the battery through a REX resistor (12V system: 47 Ω/4W; 24V system: 100 Ω/6W)

When starting, the current flows through REX to assist in exciting the generator

After the generator generates electricity, the voltage at terminal 12 increases, cutting off the excitation current and providing operational feedback

Method 2: Connect the W terminal to the speed input (terminal 18)

Directly monitor the AC frequency of the charging generator

Provide speed signal and operational status feedback

5. AC measurement wiring

Three phase system (AGC 112):

The generator voltage is directly connected to terminals 33-38

The generator current is connected to terminals 39-44 through CT

Suitable for islanded operation mode

Three phase AMF system (AGC 113):

Simultaneously connect the main voltage (terminals 28-32) to the generator voltage

Suitable for automatic mains power fault switching applications

Single phase system:

Connect the voltage to L1 and N

Current connection to L1 CT

Phase separation system:

Voltage connection to L1, L2, and N

Connect current to L1 and L2 CT

6. Power management wiring (AGC 145/146)

AGC 145 (Main Circuit Breaker):

Connect the main voltage, generator voltage, and current

Relay output controls generator circuit breaker and main circuit breaker

AGC 146 (main circuit breaker+bus tie circuit breaker):

In addition to the main circuit breaker, additionally control the bus tie circuit breaker

Suitable for power management between two busbars

Communication interface configuration

1. Modbus RTU

Interface: RS-485, 2-wire system

Supporting protocols: Modbus RTU or ASCII

Maximum bus length: 300 meters

Cable recommendation: Belden 3106A or equivalent (22 AWG shielded twisted pair, shielding coverage ≥ 95%)

Terminal resistor: When the bus length exceeds 30 meters, 120 Ω terminal resistors need to be installed at both ends

2. CAN bus engine communication

Interface: CAN J1939

Maximum bus length: 300 meters

Cable recommendation: Belden 3106A or equivalent (22 AWG shielded twisted pair, shielding coverage ≥ 95%)

Terminal resistor: 120 Ω terminal resistors need to be installed at both ends of the bus

3. External I/O modules

Connected via CAN bus, supports optional H8 external I/O module

Bus length ≤ 300 meters

Use Belden 3106A or equivalent cable

When sharing the bus with AOP-2, the total terminal resistance should be 120 Ω

4. Additional operation panel AOP-2

Connect through CAN port B

Comes with DC-DC converter and 2 x 1 meter RJ12 connection cable

Maximum bus length: 300 meters

Use Belden 3106A or equivalent cable


Summary of Technical Specifications

1. Electrical parameters

Project Parameters

Auxiliary power supply 6-36 V DC (UL/cUL: 7.5-32.7 V DC)

Maximum power consumption of 8W

Measurement voltage range 100-25000 V (primary side)

Measure current range 5-9000 A (primary side, through CT)

Measurement frequency 30-70 Hz

Accuracy Class 1.0

2. Input/output specifications

Project Parameters

Digital input 12/24V DC bidirectional optocoupler, input impedance 4.7k Ω

Multi functional input 4-20mA, digital input Pt1000

Speed input magneto electric, PNP, NPN, W terminals

Relay output (low power) 2A @ 30V DC/V AC

Relay output (high power) 8A @ 30V DC/V AC

Status output 1A @ 24V DC/V AC

3. Environmental conditions

Project Parameters

Working temperature -25 ℃ to+70 ℃

Storage temperature -40 ℃ to+70 ℃

Humidity 95% RH (non condensing)

Protection level IP52 (standard), IP65 (optional L)

4. Precautions for UL application

The controller is only applicable to generator components that have been certified by UL

Power supply voltage range: 7.5-32.7 V DC

Use 60/75 ° C copper wire

Installed on the flat surface of Type 1 casing

Compliant with NEC (USA) or CEC (Canada) specifications


Installation precautions

1. Safety Warning

Installation work can only be carried out by authorized electrical personnel

It is strictly prohibited to touch the AC measurement input terminal when the equipment is live

Pay attention to electrostatic protection during installation

The factory setting is the average value, and adjustments must be made according to the actual generator set before operation

2. Wiring requirements

All AC measurement circuits must be protected by 2A slow melting fuses

When the relay output drives inductive loads, a noise suppression circuit must be installed

Modbus and CAN buses must use shielded twisted pair cables, with the shielding layer grounded at one end

Bus terminal resistors must be installed according to specifications

3. Check after installation

Confirm that all terminals are securely connected and the torque meets the requirements

Confirm the size of the panel opening and the installation of the buckle in place

Confirm that the power polarity is correct and the voltage range meets the specifications

Confirm that the communication cable wiring is correct and the terminal resistor has been installed


Summary of Application Value

The AGC-100 generator controller provides a cost-effective solution for generator control with its compact design, flexible configuration, and reliable performance. Its main value lies in:

Easy installation: standard panel embedded installation, regular hole size, simple buckle fixation

Clear terminals: The terminal block has clear functional zoning, complete labeling, and is easy to connect

Flexible configuration: supports multiple operating modes (islanding, AMF, power management) to adapt to different application scenarios

Rich interfaces: digital input, multifunctional input, speed input, relay output, communication interfaces are all available

Communication capability: Supports Modbus RTU and CAN J1939, can be connected to the upper computer monitoring system

Scalability: Supports external I/O modules and additional operation panels to meet complex system requirements

Environmental adaptation: Wide working temperature range, IP52/IP65 protection level, suitable for various installation environments

  • Basler DECS-200-2L Digital Excitation Control
  • Basler BE1-47N Voltage Phase Sequence Relay
  • Basler AEC63-7 Analog Excitation Controller 220-277V
  • Basler BE1-50/51B-107 Overcurrent Relay
  • Basler Electric BE1‑32R BE1‑E1P‑BON0F Protective Relay
  • Basler BE1-25 Solid State Time Overcurrent Relay M1EA6PA5S1F
  • Basler MVC 232 Manual Voltage Control Module 90 37000 103 60VAC 55VDC
  • Basler RAL6144-16GM Racer GigE Line Scan Camera
  • Basler SSR 63-12 Static Voltage Regulator
  • Basler BE1-51A Overcurrent Relay
  • Basler BE1-87T Solid State Protective Relay
  • Basler SR4A2B01B3A Static Voltage Regulator
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler TRR00696 Transformer 1KVA 115V
  • Basler DECS-100-B15 AVR Replacement
  • Basler BE1-27 Under-Voltage Relay
  • Basler ACA2000-50GM Interface Module
  • Basler AEC63-7 Analog Excitation Controller
  • Basler PRS 250 Veri-Sync Relay
  • Basler SR4A-2B15B3A Static Voltage Regulator
  • Basler BE1-32R Power Relay
  • Basler SR8A-2B06B3E Static Voltage Regulator
  • Basler BE1-81 O/U Frequency Relay
  • Basler BE1-51A-K2E-W6M-B1N0F Overcurrent Relay
  • Basler BE1-851 Overcurrent Relay G3A1S1 – 48-125V AC/DC
  • Basler BEI-51 Overcurrent Relay – NSN 5945-01-293-2363
  • Basler Electric L301KC Protective Relay – L301KC
  • Basler DECS-100-B15 Automatic Voltage Regulator – Generator AVR
  • Basler SR4A-2B15B3A Static Voltage Regulator – SR4A2B15B3A
  • Basler UF 312 Under Frequency Protective Module – 9094700100
  • Basler Electric MVC 232 Manual Control Module – 60VAC 55VDC 20A
  • Basler PRS 250 Veri-Sync Relay – Generator Synchronizing Relay
  • Basler DECS-100-A05 Digital Regulator Review
  • Basler AEM-2020 Analog Expansion Module Specs
  • Basler DECS-100-B15 Digital Excitation Specs
  • Basler Electric 9125600106 Regulator Component
  • Basler BE1-51A-K1E-W6M-B1N0F Overcurrent Relay
  • Basler MVC-301 MVC 300 Excitation Controller
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler 9-2849-00-101 Control Module
  • Basler BE1-51A Overcurrent Relay
  • Basler BE1-51/27R Overcurrent Relay
  • Basler BE1-51 Overcurrent Relay
  • Basler SR8A-2B15B3A Static Voltage Regulator
  • Basler BE32965001 Transformer and Timer Board
  • Basler 9174700100 EL200-7 Excitation Limiter
  • Basler BE2000E AVR Voltage Regulator
  • Basler BE1-87G Differential Relay
  • Basler BE21834001 Generator Control Module
  • Basler DECS-100-B15 AVR
  • Basler D90 96801 100 PCB Card
  • Basler XR2002F Voltage Regulator (110 VAC, 48-480 Hz)
  • Basler SR8A-2B14B3A Regulator
  • Basler 9561500100 Module
  • Basler DECS-400 BE1-11 System
  • Basler DECS-100-B15 Excitation Control
  • Basler SCP 210 Frequency Controller
  • Basler SR4A-2B15B3A Static Voltage Regulator
  • Basler BE1-32R Power Relay
  • Basler PIA2400-17GM Power Interface Adapter
  • Basler MVC 232 Manual Voltage Control Module
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler 5MW AVR Generator Voltage Regulator
  • Basler VR63-4B Voltage Regulator
  • Basler DECS-100-A05 AVR for Engine Generator
  • Basler DECS-100-B15 Automatic Voltage Regulator
  • Basler BE1-32R Directional Power Relay
  • Basler BE1-87B Differential Relay
  • Basler UFOV 260A Protective Module
  • Basler 9-2614-02-100 PCB Rev M
  • Basler DECS-100-B15 Digital AVR
  • Basler 9284900103 PS DECS-400N
  • Basler D4N3H1U Intertie Protection
  • Basler DECS-100-B15 A15 AVR
  • Basler KR4F Voltage Regulator
  • Basler BE26434 T14 Transformer
  • Basler SR8A-2B15B3A Regulator
  • Westinghouse 774B472A12 AR Relay
  • Basler DECS-100-B15 AVR
  • Basler XR2002F Regulator 110V
  • Basler SR125-E Static Regulator
  • Basler SSR 125-12 Regulator
  • Basler MOC2599 Motor Pot
  • Basler BE1-DFPR Feeder Relay
  • Basler CBS 305 Current Boost
  • Basler BE1-25 AutoSync
  • Basler MVC 300 Voltage Control
  • Basler BE3-25A AutoSync
  • Basler KR7FF Static Regulator
  • Basler 90-49000-100 Regulator
  • Basler 880 kVA Dry Type Transformer Specs
  • Basler Electric BE1-25 Sync-Check Relay Specs
  • Basler SSR 125-12 Voltage Regulator Specs
  • Basler Electric BE1-851 Overcurrent Relay Review
  • Basler Electric 149D930G02 Control Sub-Assembly
  • Basler Electric BE1-81O/UT Frequency Relay Specs
  • Basler Electric BE1-51/27C Overcurrent Relay
  • Basler Electric 149D956G02 Industrial Component
  • Basler Electric BE1-51A Overcurrent Relay Specs
  • Basler Electric BE1-40Q Loss of Excitation Relay
  • Basler DECS-200 Excitation Control System
  • Basler DECS-200 Voltage Regulator 56-277V AC / 125V DC
  • Basler BE1-87T Transformer Differential Relay
  • Basler RDP-110-S1 Protection Relay
  • Basler BE1-700V Digital Protective Relay
  • Basler BE1-951 Overcurrent Protection System
  • Basler DECS-300 Digital Excitation Control
  • Basler DECS-200 Digital Excitation Control
  • Basler DECS-200-1C Excitation Control System
  • Basler DECS-200-1L Digital Excitation Control
  • Basler Electric BE1-GPS Generator Protection System
  • Basler Electric DECS-200-1C Digital Excitation Controller
  • Basler Electric DECS125-15 Excitation Control with Power Module
  • Basler Electric BE1-87G Differential Relay
  • Basler Electric BE1-11 Protection System I5A3M2P2N0EA00
  • Basler Electric DECS-200-1C Excitation Control System
  • Basler Electric BE1-11g Generator Protection Relay
  • Basler Electric DECS 125-15-B2C1 V2.0.9 Excitation Control
  • Basler Electric BE1-81O/UT3ED1JA7N2F Frequency Relay
  • Basler Electric BE1-81O/UT3EE1YB7N1F Frequency Relay
  • Basler Electric DECS-200-1L Digital Excitation Control System
  • Basler DECS125-15-B2C1 Excitation Control
  • Basler 9507900205 SSR Retrofit Voltage Regulator
  • Basler BE2000E Digital Voltage Regulator
  • Basler BE1-GPS Generator Protection System
  • Basler DECS-250-CN1CN1N Digital Excitation Control
  • Basler DGC-2020 Genset Controller
  • Basler BE1-81O UT3ED1LA7N0F Frequency Relay (Variant)