Engine interface power supply (terminal 98/99): independent power supply, maximum 5W, isolated from the main power supply.
6.3 Environment and Machinery
Working temperature: -25~70 ℃ (-25~60 ℃ with N option included, UL limit 55 ℃).
Storage temperature: -40~70 ℃.
Altitude: 0-4000m, derating is required for distances above 2000m (voltage ≤ 480V for 3W4 wiring, ≤ 690V for 3W3).
Vibration and Shock: Meets IEC 60068-2-6 and IACS UR E10, capable of withstanding 30g/11ms shock (durability).
Protection level: IP20 for the host and IP40 for the display unit (up to IP54 with added sealing gasket, meeting marine requirements).
6.4 Input/Output Characteristics
Digital input: Bidirectional optocoupler, conduction threshold 8-36V DC, turn off<2V, typical impedance 4.7k Ω.
Relay output: 250V AC/30V DC, 5A (resistive), capable of continuous 2A or short-term 4A (5s/15s duty cycle).
Analog output (optional): 0-20mA or ± 20mA, active output (internal power supply), maximum load of 500 Ω, update rate of 250ms (transmission) or 100ms (regulation).
Multi functional input (slot # 7): can connect Pt100/Pt1000, 0-20mA, RMI (0-1700 Ω), 0-40V DC, with an accuracy of ± 1%, and has the ability to detect wire breakage.
Selection and configuration examples
DEIF divides GPUs into three basic models (variants):
01: With display unit, standard delivery (including 3-meter cable).
02: No display unit (suitable for integration into existing display systems).
03: Equipped with display unit and option F1 (2-channel analog transmission output).
On this basis, users can add the desired options, such as:
Synchronization function required → Add G2
Need engine control → add M4 (hardware board) and Y1/Y7 (display layout)
Modbus communication required → add H2
High precision measurement at level 0.5 is required → add Q1
IP54 protection is required → add L (indicating sealing gasket)
Selection example (from manual):
2912110030-03 GPU-3 Marine03 M4 Y1 H2
Indicating display, F1 output, engine control board, engine+circuit breaker display layout, Modbus RTU communication.
Debugging, Configuration, and Maintenance Tips
PC Tool: DEIF provides Multi line 2 PC Utility software (USB connection) for free, which can monitor all measurement values online, modify parameters, update firmware, and customize logic using M-Logic editor.
Parameter download and backup: It is recommended to upload and save the complete parameter file before debugging for quick recovery in case of failure.
Synchronization parameter setting: If synchronization is enabled, it is necessary to carefully set the pressure difference, frequency difference, closing lead angle, etc. to avoid impact.
Broken wire monitoring resistor: When the digital input enables broken wire monitoring, the external contacts must be connected in parallel with a 270 Ω± 10% resistor, otherwise the system will report a "broken wire" fault.
Shielding and grounding: Communication lines, MPU lines, and analog signal lines should use shielded twisted pair cables, with the shielding layer grounded at one end, and the terminal resistance (such as 120 Ω for CAN) connected as needed.
Regular self check: GPU -3 power on self check, and relay/output testing can also be manually triggered through the menu during operation to ensure circuit integrity.