Eaton MTL F809F Plus DTM Operating Instructions

F: | Au:FANS | DA:2026-10-21 | 63 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:

Segment TB: Voltage, Noise, Signal Amplitude, and Number of Devices

Duan TB is the core of on-site troubleshooting. The default low limit for segment voltage is 18V and the high limit is 32V, which should be adjusted according to the actual fieldbus power data sheet. Check the power carrier output, distribution, and wiring for low voltage alarm; High voltage warning for power module and load.

Noise is divided into three levels: low frequency from 25Hz to 3.8kHz, in band from 5kHz to 55kHz, and high frequency from 90kHz to 350kHz. Each level is further divided into average and peak values. The default pre alarm/warning limit for average noise is low-frequency 150/150mV, in band 75/75mV, high-frequency 150/150mV; the default peak value is 65535mV, which is equivalent to disabling to avoid false alarms in the factory state. The typical average noise level on site is below 20mV, with peak values typically below 50 to 60mV. Peaks resembling "spikes" may be caused by lightning strikes, equipment start stop, welding, or temporary short circuits, and short-term disturbances may not necessarily affect the bus; If the average noise continues to rise, it indicates the presence of permanent noise sources such as frequency converters, poor shielding, or parallel AC cables. Therefore, the average noise limit should be stricter than the peak limit.

The troubleshooting sequence for noise alarms is very fixed: check whether the shielding layer of each on-site device is cut short and wrapped properly, and do not have multiple grounding points; Check the shielding connections and grounding inside the on-site junction box, intermediate junction box, and marshalling cabinet; Confirm that the AC power cable is not close to the Fieldbus cable; Confirm terminal fastening; High frequency noise also needs to be checked for welding operations, frequency converter grounding, and nearby high-power radio stations. Attention should also be paid to the grounding of the 5W ERP radio, welding, and frequency converter within a range of 1.5m for in band noise. The short to shield alarm "Short to shield+/- ve" may be caused by the addition of a handheld communicator. If Emerson 475 is used on site, the maximum number of devices should be increased by 1 to avoid false alarms; Otherwise, check for shielding cutting, grounding, floating power supply, and water ingress in cables/junction boxes/equipment.

The default low limit of the device signal amplitude is 150mV, the high limit is 1200mV, the alarm delay is 10mV, and the high limit is at least 20mV higher than the low limit. IEC 61158-2 specifies a range of 750 to 1000mV under testing conditions, but the actual range on site can be from 550 to 1200mV. After debugging, it is recommended to set the low limit of the device to 75% of the current value and the high limit to 125% to make the alarm more realistic while retaining margin. If only one device has a low signal, check the branch cable, branch connector, water inlet, and the device itself; If multiple or all devices are low, check if there are more than two terminals, water ingress, or mainline issues on the segment.

The default low limit for the live list of devices is 0, and the high limit is 32, which is equivalent to no alarm. Connecting a handheld communicator will increase the number of devices. If you do not want to alarm, you can increase the high limit by 1. When DCS itself can detect equipment loss, F809F may repeatedly report a low number of devices, and the default limit value can be retained. The segment retransmission rate is equal to the number of retransmissions divided by the total number of Pass Token requests in LAS, calculated based on the past calendar month; The segment retransmission count can be reset separately, but it will not reset the device retransmission. Resetting the segment count does not affect the retransmission rate, as the retransmission rate is calculated based on the total number of device retransmissions, making it easier to observe newly occurring retransmissions.

The segment diagnosis also provides a "Graph Overview" radar chart, with green areas indicating safe zones and black lines indicating measured values. The black line entering the outer yellow area indicates exceeding the high limit, the outer blue area indicates exceeding the high limit, the inner blue area indicates below the low limit, and the inner yellow area indicates below the low limit. This chart is suitable for quickly determining whether a certain segment is voltage, noise, signal amplitude, or retransmission rate deviation, but it cannot replace checking each parameter item by item.


Device TB: Address LAS、 Signal and retransmission

The device node displays the device address, device tag, signal level, number of retransmissions, and retransmission rate. Addresses 16 to 247 are permanent addresses, 248 to 251 are temporary addresses, and 252 to 255 are used for temporary devices or handheld devices. The devices currently serving as LAS will be labeled with [LAS] after their names, and the backup Link Master cannot be identified solely through bus observation, so the navigation tree will not be marked separately. The typical signal level of the device is between 550 and 1200mV, and retransmission refers to the number of times the device fails to return the Pass Token in a timely manner after LAS sends it and tries again; The retransmission rate is the number of retransmissions divided by the total number of PT requests in LAS.

  • Bonfiglioli RPS Log 100 Data Logging Module
  • Bonfiglioli VF49P1P71B14 Gearbox
  • Bonfiglioli W86U Right Angle Gear Reducer
  • Bonfiglioli W63 U P71B5 Gear Reducer
  • Bonfiglioli W63UP90B5 Gearmotor
  • Bonfiglioli VER/S 400-150 Inverter
  • Bonfiglioli F202 H30 P80 Gearbox
  • Bonfiglioli W75UD307P90B14 Gearbox
  • Bonfiglioli MPC1004S000D MP 080 Planetary Gearbox
  • Bonfiglioli Vectron ACU 401-29A Inverter
  • Bonfiglioli MPB1010S0001 Gearbox
  • Bonfiglioli VF 44 P1 70 Speed Reducer Gearbox
  • Bonfiglioli BRA400-034 BF1 Brake Chopper
  • Bonfiglioli VF49P110P71B14B3 Worm Gearbox
  • Bonfiglioli VF30 A P63B14 Gearmotor with SITI Motor
  • Bonfiglioli ACT 201-09 FA Active Frequency Inverter
  • Bonfiglioli ACU 401-25A Frequency Inverter
  • Bonfiglioli VF30 44A2100 Worm Gearbox
  • Bonfiglioli BXTFC 63B-2 Brake Motor
  • Bonfiglioli AGL402-18 2 FA Frequency Inverter
  • Bonfiglioli EM-RES 02 Expansion Module
  • Bonfiglioli BTD5-1160-30-400-FD24-K Module
  • Bonfiglioli VF44F146P63B14B3 Gearbox
  • Bonfiglioli VF49PIP71B14B3 Gearbox
  • Bonfiglioli KP 500 Control Unit
  • Bonfiglioli VF49 P1 HSRB Gear Reducer
  • Bonfiglioli W63UP71B5 Gearbox
  • Bonfiglioli AGL402-15 2FA Inverter
  • Bonfiglioli ACT 201-05 FA Inverter
  • Bonfiglioli Vectron ACT 400-007 FC Inverter
  • Bonfiglioli ACT 201-09 FA Frequency Inverter
  • Bonfiglioli W63U Gear Unit
  • Bonfiglioli BC 220 Motor with VF44 Gear Reducer
  • Bonfiglioli MP 080 2 15 STD 110B1 CD Gear Unit
  • Bonfiglioli MVF49A14071B5 Worm Gearbox
  • Bonfiglioli ACT401-23A Frequency Inverter Drive
  • Bonfiglioli VF44 P1 20 Worm Gearbox
  • Bonfiglioli 8XNC64040003 Gearmotor BXN 63MB 4
  • Bonfiglioli CM-485 T RS-485 Communication Module
  • Bonfiglioli AGL402-233FA Frequency Inverter
  • Bonfiglioli BCR8-1150-30-400-FD24-K Module
  • Bonfiglioli EM-I/O 04 Module
  • Bonfiglioli BXTFC 63B-2 Brake Motor
  • Bonfiglioli VF63/F1 Right Angle Gearbox
  • Bonfiglioli SIACT513010001 ACT 401-13FA Frequency Inverter
  • Bonfiglioli BN 63 B2 Motor with GMP100
  • Bonfiglioli C31 3P P53 PV Helical Speed Reducer
  • Bonfiglioli MPD1007S0002X MP 105 Planetary Gearbox
  • Bonfiglioli ACT 410-13 2 A Inverter
  • Bonfiglioli M1SD4 Gearmotor
  • Bonfiglioli ACT410-15 2 FA Frequency Inverter
  • Bonfiglioli C31 3 P P63 PV Helical Reducer
  • Bonfiglioli W63U19 Gearmotor with M2SB4 Motor
  • Bonfiglioli W63UP71B5B3 Worm Gearbox
  • Bonfiglioli 2KB2 060-0405-A00003 Motor Bearing
  • Bonfiglioli ACT 401-22A Frequency Inverter
  • Bonfiglioli ACU 401-29A Frequency Inverter
  • Bonfiglioli ACU401-19FA Frequency Inverter
  • Bonfiglioli ACU 201-07 FA Frequency Inverter
  • Bonfiglioli ACT401-33A Frequency Inverter 37kW
  • Bonfiglioli ACU 401-09 FA Inverter
  • Bonfiglioli RAN 8 S A 1 Gear Reducer
  • Bonfiglioli WR63U300P71B5B3KA Gearbox
  • Bonfiglioli 509 424 700 Inverter
  • Bonfiglioli AS 16/P P71 Gear Reducer
  • Bonfiglioli VF44F1P71B14 Gearbox
  • Bonfiglioli AGL402-13 1 FA Inverter
  • Bonfiglioli ACT 401-45A Main Board
  • Bonfiglioli W 110U 100 Gearbox
  • Bonfiglioli VF 49/F Gearbox
  • Bonfiglioli AGL402-09 1FA Inverter
  • Bonfiglioli ANG 410-19 3 FA Inverter
  • Bonfiglioli ANG 410-33 6A Inverter
  • Bonfiglioli W86UN56C Gearbox
  • Bonfiglioli 2KB2 060-0405 Motor
  • Bonfiglioli VF49P P71B14B3 Gearbox
  • Bonfiglioli SA 400-150 Inverter
  • Bonfiglioli TQF 070 Planetary Gearbox
  • Bonfiglioli ACT 401-19 A Inverter
  • Bonfiglioli ACT 401-13FA Inverter
  • Bonfiglioli W 63 U 24 Gearbox
  • Bonfiglioli BN 80 B4 Electric Motor
  • Bonfiglioli A 30 2 UH35 Gearbox
  • Bonfiglioli ACT 401-09 FA Inverter
  • Bonfiglioli EM-SYS DS179675010 Communication Module
  • Bonfiglioli AGL402-15 2 FA Inverter
  • Bonfiglioli W63UF115P90B5B3 Gear Reducer
  • Bonfiglioli 2KB2 060-0405-A00003 Bearing
  • Bonfiglioli VF 44 A 10 P63 B5 B3 Gearbox
  • Bonfiglioli ACU401-13FA Frequency Inverter
  • Bonfiglioli ACT 201-11FA Inverter
  • Bonfiglioli AGL402-15 2 FA Inverter
  • Bonfiglioli AGL402-07 1 FA Inverter
  • Bonfiglioli ACU 410-19 3 A Inverter
  • Bonfiglioli A 10 2 UH25 P71 Gearmotor
  • Bonfiglioli ACT 401-13 FA Inverter
  • Bonfiglioli ACU 410-15 2 FA Inverter
  • Bonfiglioli ACU 410-27 5 A Inverter
  • Bonfiglioli BN 63B 4 B5 Motor
  • Bonfiglioli AGL402-18 2 FA Frequency Inverter
  • Bonfiglioli W86-UF1-P90B5 Worm Gear Reducer
  • Bonfiglioli MP 080 80 STD 80A1 Planetary Gearbox
  • Bonfiglioli BN90S4 Motor
  • Bonfiglioli A413 UH40 Gear Motor
  • Bonfiglioli VF 63 Gear Reducer
  • Bonfiglioli ACU 201-05 FA Inverter
  • Bonfiglioli ACT 401-13FA Inverter
  • Bonfiglioli LC 120 1 10 STD 110A1 CD 24 KE Gear Unit
  • Bonfiglioli Fuji GVX2000-11-TSL2 Inverter
  • Bonfiglioli ACU 401-05 FA Inverter
  • Bonfiglioli W86UP100B5 Gearbox
  • Bonfiglioli MP 130.1.5.10 Gear Unit
  • Bonfiglioli ACT W401-29C Vector Inverter
  • Bonfiglioli BE 71A 4 Gearmotor
  • Bonfiglioli BN 71B 4 Asynchronous Motor
  • Bonfiglioli W110U100P90B5B3 Gear Reducer
  • Bonfiglioli VF 49 F1 7 P71 B5 B3 Gearbox
  • Bonfiglioli MP 080 2 16 STD 50D Gear Unit
  • Bonfiglioli VF 44 A 10 P63 B5 B3 Worm Gearbox
  • Bonfiglioli ACU401-13FA Frequency Inverter
  • Bonfiglioli CM-EtherCAT DS179675207 Module
  • Bonfiglioli 8AF2400CK BX 90 L A 4 Motor
  • Bonfiglioli BRA 400-045 BF2 Inverter
  • Bonfiglioli TQF 070 Planetary Servo Gearbox
  • Bonfiglioli B-SYN-04-0780 Servomotor
  • Bonfiglioli TA45.50-25.0-D-0S Shaft Gearbox
  • Bonfiglioli AS 20 F 21.19 071 B5 Helical Gearbox
  • Bonfiglioli 07/63 EE B5 Gear Unit