Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Honeywell Beam Smoke Detector Guide

F: | Au:FAN | DA:2026-04-15 | 269 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Honeywell TC847A1004 Reflective Beam Smoke Detector: A Complete Guide to Selection, Installation, Debugging, and Troubleshooting

Introduction: Challenges of smoke detection in tall spaces and advantages of beam detectors

In large commercial courtyards, church domes, hangars, warehouses, sports arenas, and enclosed parking lots, traditional point type smoke detectors are difficult to work effectively due to smoke stratification effects and installation and maintenance difficulties. The beam type smoke detector detects smoke by emitting a beam of infrared light and measuring the attenuation of the light intensity at the receiving end, which can cover a protection range of tens to hundreds of meters. However, traditional dual ended radiation detectors require precise alignment of the transmitter and receiver, which is time-consuming and costly to install and debug.

Honeywell's TC847A1004 single ended reflective beam smoke detector integrates the transmitter and receiver into the same unit, requiring only one reflector to be installed, greatly simplifying the installation and alignment process. This detector is compatible with Honeywell's FlashScan ®  Or CLIP mode intelligent fire alarm controller, as well as FS90, XLS200, XLS1000 (CLIP mode only). Its working temperature range is wide from -22 ° F to 131 ° F (-30 ° C to 55 ° C), suitable for extreme temperature environments. This article will provide engineers with a detailed technical guide from selection comparison, installation and debugging, sensitivity setting, troubleshooting to maintenance testing.


Core features and technological advantages of the product

1.1 Single ended reflective design

Unlike traditional dual ended detectors, TC847A1004 integrates the transmitter and receiver into the same housing, with only one reflector installed on the opposite side. This brings the following advantages:

The installation time has been significantly reduced: there is no need to align two independent units, only one reflector needs to be aligned.

Simplified wiring: Only power supply and signal circuit connection are needed at the detector end, and the reflector does not require any electrical connection.

Easy maintenance: All debugging and testing operations are completed on the detector end.

1.2 Six optional sensitivity levels

The detector provides six sensitivity settings (specific settings are implemented through the controller):

Grade shading percentage display reading applicable distance range

Level 1 25% 25 16.4-120 ft (5-36.6 m)

Level 2 30% 30 25~150 ft (7.6~45.7 m)

Level 3 40% 40 60-220 ft (18.3-67 m)

Level 4 50% 50 80-328 ft (24.4-100 m)

Acclimate ®  Level 1 30%~50% A1 80~150 ft (24.4~45.7 m)

Acclimate ®  Level 2 40%~50% A2 80~200 ft (24.4~67 m)

Acclimate ®  The mode utilizes advanced software algorithms to automatically adjust the optimal sensitivity within a specified range according to environmental changes, especially suitable for places with large fluctuations in environmental smoke.

1.3 Built in Sensitivity Test Function (Integral Sensitivity Test)

TC847A1004 has a test filter driven by a servo motor inside. When activated through RTS151 or RTS151KEY remote testing station, the filter will automatically move into the optical path, simulating a certain degree of shading to verify the detector's response capability. This design enables users to meet the annual maintenance and testing requirements of NFPA 72 without physically contacting the detector. Attention: The servo motor requires external 24 VDC power supply, not SLC circuit power supply.

1.4 Automatic Gain Control (AGC)

The built-in automatic gain control circuit can compensate for signal attenuation caused by dust accumulation, extend the effective working cycle of the detector in polluted environments, and reduce false alarms and maintenance frequency.

1.5 Visual Alignment Assistance

The detector integrates an optical sight and a two digit digital signal strength display. Accurate adjustment can be achieved by observing the signal strength reading without the need for specialized tools.


Detailed explanation of technical specifications

2.1 Scope of Protection

Standard range: 16-230 feet (5-70 meters)

Expansion range: 230-328 feet (70-100 meters), requiring the optional long-distance kit BEAM LRK

2.2 Adjusting the angle

The optical components of the detector can be adjusted horizontally and vertically by ± 10 ° independently of the housing. This provides flexibility for installation on sloping ceilings or uneven walls.

2.3 Environmental specifications

Working temperature: -22 ° F to 131 ° F (-30 ° C to 55 ° C)

Humidity: 10% to 93% relative humidity, no condensation

Anti condensation heating kit: optional BEAMHK (for detector) and BEAMHKR (for reflector) to prevent condensation from forming (note: the heating kit does not change the rated operating temperature range, only prevents condensation)

2.4 Electrical specifications

Parameter values

Operating voltage (SLC) 15-32 VDC

Standby current (average) ≤ 2 mA @ 24 V

Alarm current ≤ 8.5 mA

Fault current ≤ 4.5 mA

Alignment mode current ≤ 20 mA

External power supply (for testing motors) 15-32 VDC, 0.5 A maximum

Remote alarm output 15-32 VDC, 6-15 mA (built-in 2.2k Ω current limit)

2.5 Mechanical dimensions

Detector: 10.0 "H x 7.5" W x 3.3 "D (254 x 191 x 84 mm)

Standard reflector: 7.9 "x 9.1" (200 x 230 mm)

Long distance reflector: 15.7 "× 18.1" (400 × 460 mm)

Shipping weight: 3.7 lbs (1.68 kg)

2.6 Indicator light status

Normal: Green LED flashing

Alarm: The red LED is constantly on, and the remote alarm output is activated

Fault: The yellow LED is constantly on (fault conditions include: shading rate ≥ 96%, alignment mode, improper initial alignment, self compensation limit reached)

Installation and Alignment: A Step by Step Guide

3.1 Preparation before installation

Choose installation location: Ensure that there are no permanent obstacles in the optical path. Personnel, equipment, or decorations must not frequently pass through the straight path between the detector and the reflector.

Spacing requirements: According to NFPA 72, the horizontal spacing between adjacent beam detectors should not exceed 60 feet (18.3 m), and the distance between the beam and the sidewall should not exceed half of this spacing.

Mirror installation: The mirror should be installed on a flat and sturdy surface, ensuring verticality. For long distances (>230 ft), large-sized reflectors from the BEAMLRK kit are required.

3.2 Detector Installation

The detector can be installed on the ceiling or wall. For special installation requirements:

BEAMMMK Multi Installation Kit: Provides ceiling or wall installation capability and increases angle adjustment range.

Surface mounting kit BEAMSMK: used for direct surface mounting.

Heavy duty multi installation kit 6500-MMK: suitable for places with high vibration (needs to be used in conjunction with 6500-SMK).

3.3 Optical alignment steps

Connect the SLC power supply and external test motor power supply (if used).

Place the detector in alignment mode (usually through dialing or controller commands).

Roughly align the center of the reflector through an optical sight.

Observe the two digit display (signal strength reading). The larger the value, the stronger the received signal.

Fine tune the horizontal/vertical angle of the detector to achieve the maximum reading (usually ≥ 90).

Fix the adjustment screw and exit the alignment mode.

Attention: In alignment mode, the detector will not sound an alarm and the fault LED may light up, which is a normal phenomenon.

3.4 Wiring precautions

The detector uses a pluggable terminal block, which needs to be unplugged from the circuit board before wiring. After the wiring is completed, reinsert it.

SLC circuit: The polarity of the wiring terminals (usually marked as+and -) is independent.

External power supply: To supply power to the servo motor, a 15-32 VDC power supply is required (pay attention to the positive and negative poles).

Remote alarm output: can be connected to remote indicator lights or relays, with output current limited to 6-15 mA.

Remote testing station: RTS151 or RTS151KEY can be remotely activated and reset by connecting with two or three wires.


Matching sensitivity settings with distance limitations

The sensitivity setting must be performed when the detector is not in the fine alignment step (i.e. when the two digit display is not lit). Operation steps:

Open the detector casing.

Find the sensitivity button (see the "Switch Locations" image in the document).

Short press the sensitivity button once, and the two digit display will light up and show the current setting (for example, "25" means 25% shading).

Continue holding down the button, and the settings will loop until the desired values (25, 30, 40, 50, A1, A2) are displayed.

Release the button and it will automatically turn off after a few seconds.

Key rule: Not all sensitivity settings are applicable to any installation distance. You must refer to the table in the document to select:

25% blackout: only suitable for 16.4-120 ft (5-36.6 m)

30% blackout: only suitable for 25-150 ft (7.6-45.7 m)

40% blackout: only suitable for 60-220 ft (18.3-67 m)

50% blackout: only suitable for 80-328 ft (24.4-100 m)

Acclimate ®  1 (A1): Only applicable for 80-150 ft (24.4-45.7 m)

Acclimate ®  2 (A2): Only applicable for 80-200 ft (24.4-67 m)

Violation of regulations can result in false positives or false negatives. For example, using 25% sensitivity at a distance of 200 ft is not allowed because the signal attenuation exceeds the threshold before the smoke reaches sufficient concentration.

Troubleshooting: Common Problems and Solutions

5.1 Continuous display fault of detector (yellow LED constantly on)

Possible cause inspection and resolution

The light path is completely blocked (≥ 96% shading). Check if there are any objects (such as chandeliers, flags, tools) that completely block the light beam

The detector is in alignment mode and should not be in alignment mode during normal operation

Inappropriate initial alignment, low signal strength. Re perform optical alignment to ensure that the digital signal strength reading reaches the maximum value (usually>90)

The self compensation limit has been reached (AGC cannot compensate for dust accumulation) to clean the optical window and reflector; If it still doesn't work, the detector may need to be replaced

Serious contamination on the surface of the reflector. Clean the surface of the reflector

Check the fixing of the mirror for misalignment or looseness, and realign it

5.2 False alarm

Possible cause inspection and resolution

Sensitivity setting too high (overly sensitive) Choose a more suitable sensitivity based on actual distance (such as changing from 30% to 40%)

There are intermittent obstructions in the light path (such as moving people, vehicles, equipment). Adjust the installation position or add protective fences

Consider using Acclimate for environmental smoke sources such as welding and forklift exhaust ®  Mode allows the detector to automatically adapt to the environment

Dirty mirrors or optical windows cause signal attenuation. After cleaning, observe whether the signal strength recovers

5.3 Unable to activate remote testing function

Possible cause inspection and resolution

Test if the external power supply of the motor is not connected or the voltage is insufficient. Measure the external 24 VDC power supply to ensure that the voltage is between 15-32 V and the current capacity is ≥ 0.5 A

Remote testing station wiring error: Refer to the wiring diagram and reconnect RTS151 (usually 2-wire or 3-wire)

Use a multimeter to measure the resistance of the motor coil (which should not be zero or infinite) for servo motor faults. If there is a problem, replace the detector

5.4 Unstable signal strength readings

Possible cause inspection and resolution

Install the base vibration (if there are large fans or compressors nearby) and use the 6500-MMK heavy-duty multi installation kit to strengthen the fixation

Loosen the reflector and re tighten it

There is strong hot air flow or steam in the environment. Adjust the installation position or add protective covers


Maintenance and testing: meet NFPA 72 year inspection requirements

6.1 Annual testing using built-in test filters

According to NFPA 72 requirements, beam smoke detectors need to undergo sensitivity testing annually. The traditional method requires manual use of filters to block the light path, while the built-in testing function of TC847A1004 automates this process:

Connect an external 24 VDC power supply to the test motor terminals.

Activate the remote testing station (RTS151) or through controller commands.

The servo motor moves the filter into the optical path and simulates the predetermined shading rate.

The detector should enter an alarm state, the red LED should light up, and the controller should receive an alarm signal.

After the test is completed, reset the detector (which can be done through a remote testing station or controller) and remove the filter from the optical path.

Advantages: No need for high-altitude operations, no need for physical contact detectors, safe and efficient.

6.2 Cleaning of reflectors and optical windows

Frequency: Every six months or depending on the level of environmental dust.

Method: Use a soft cloth and mild glass cleaner to avoid scratching the mirror surface.

Attention: After cleaning, the signal strength reading should be checked, and if there is a decrease, it needs to be realigned.

6.3 Maintenance of Heating Kit

If BEAMHK (detector heater) or BEAMHKR (reflector heater) is installed, it should be checked regularly:

Is the power supply voltage of the heater normal (15-32 VDC).

Observe whether the optical window condenses in a low temperature and high humidity environment. If condensation occurs, it indicates that the heater may be malfunctioning.


Accessories and replacement options

When the original detector is discontinued or needs to be upgraded, TC847A1004 and its accessories provide a flexible replacement solution.

7.1 Main accessory models

Model Usage

TC847A1004/TC847A1004A standard detector (A is ULC certified version)

BEAM LRK Long Distance Kit (for 70-100 m)

BEAMMMK Multi Installation Kit (Ceiling or Wall Installation, Increased Adjustment Angle)

BEAMSMK surface mounting kit

BEAMHK detector heating kit (anti condensation)

BEAMHKR reflector heating kit (anti condensation)

RTS151/RTS151A remote testing station (A is ULC certified version)

RTS151KEY/RTS151KEYA remote testing station with key lock

6500-MMK heavy-duty multi installation kit (anti vibration)

6500-SMK surface mounting kit (for use with 6500-MMK)

7.2 Precautions when replacing old models

Controller compatibility: Confirm if the fire alarm controller supports FlashScan ®  Or CLIP mode. TC847A1004 provides more features and faster response in FlashScan mode.

Distance matching: If the installation distance of the old system exceeds 230 feet, the BEAMLRK kit must be purchased, otherwise the detector will not work properly.

Power requirements: The old system may not have provided an external 24 VDC power supply for the test motor. When replacing, an independent power module (15-32 VDC, 0.5 A) needs to be added.

Installation hole position: Check if the installation base of the old detector is compatible with TC847A1004. If necessary, use BEAMSMK or BEAMMMK for adaptation.

Mirror replacement: If using a long distance, it is necessary to replace it with a large-sized mirror (15.7 "× 18.1") at the same time.

7.3 Selection Suggestions

For standard tall spaces (height 10-30 meters, span ≤ 70 meters), choose the TC847A1004 standard configuration.

For ultra long spans (70-100 meters), TC847A1004+BEAMLRK must be selected.

For extremely cold or high humidity environments such as cold storage and outdoor canopies, install BEAMHK and BEAMHKR to prevent mirror condensation.

For places with high vibration, such as near large stamping equipment or along railway lines, use the 6500-MMK heavy-duty installation kit.

  • OMRON CJ1W-MD261 Mixed I/O Module
  • Omron NJ301-1100 PLC CPU eCat EIP Specs
  • Omron F500-C15-ETN Vision System PLC Module
  • Modicon M241-24IO TM/T2UK PLC with Ethernet
  • SIXNET YS-800-001 RTU PLC Module
  • BEMAC UST-202-D Interface Board 1307D V08B2
  • Yaskawa JANCD-MMOIC-02 Drive Circuit Board
  • ABB 3BSE005028R1 SDCS-COM-1 Comm Board
  • Omron 3G3MX2-A4110 A4150 Inverter Drives Specs
  • KEYENCE CA-E100 PLC Module
  • GE IC693ALG223-GB Analog Input Module Specs
  • ABB BAILEY IMMFP01 Multi Function Processor System
  • SIEMENS 6FC5372 0AA00 0AA1 NCU 7202 Controller
  • Modicon TM241CE4 40I O Transistor Programmable Controller
  • SIEMENS 6ES7 315 2EH13 0AB0 CPU 3152 PN DP
  • NORIS A1 91 PCB Card Rack Module System
  • SIEMENS 6ES7 313 5BE01 0AB0 Compact CPU
  • SCHNEIDER ELECTRIC S144B MICROLOGIC 60A Trip Unit
  • CNI PLC269 v3 Control Module Board Rev H
  • ABB BAILEY IIMCP02 Processor Module
  • OMRON NT20S ST121 EV3 Operator Interface Terminal
  • OMRON NS-CA001 Video Input Unit
  • GE Fanuc IC695CHS012 RX3i Backplane
  • Allen Bradley 2711E-K14C6 PanelView 1400e Terminal
  • Siemens Sinamics CCB 10000432.71 Power Cell
  • Siemens 6SL3210-1SE21-8UA0 Power Module PM340
  • Yaskawa CIMR-F7A20P4 AC Drive
  • Beckhoff EP1918-0002 EtherCAT Box I/O Module
  • OMRON CQM1-TC001 Temperature Control Module
  • GE Fanuc SGHA36AT0400 Industrial Contactor
  • OMRON NJ501-1500 PLC Machine Automation Controller
  • Mitsubishi MAZAK QX084 Power Supply MELDAS 500 CNC
  • B&R 0AC808.9 PLC Automation Module
  • OMRON CP1H-XA40DT1-D PLC Module
  • G&W Electric PLC15 5111 011 15kV Capnut Assembly
  • GE DS200SLCCG3AGH PCB Circuit Board
  • Siemens SINUMERIK 6FC3981-4FD PLC Extension
  • OMRON F300-DC I/O Image Processing Unit
  • FANUC A06B-0314-B002 AC Servo Motor
  • GC-S84 Programmable Controller Logic Module
  • PASABAN MONTELEC MTC3001-DC Drive Control PLC
  • Allen Bradley 100E460EJ11 Auxiliary Contactor
  • Bosch Rexroth 1070075337-101 Card Parameters
  • HMS Anybus AB7646-F Gateway Specifications
  • Bosch 062633-303401 CNC Servo PLC Card
  • TI 500-5023 Series PLC Power Supply
  • Siemens C98043-A7002-L1-12 Circuit Board
  • Omron E5CC-RX3A5M-000 Controller
  • CN-8032-L Profinet Network Adapter Module
  • Siemens 3TK2804-0BB4 Safety Relay Details
  • Toledo TTLM-2-1M I/O Load Module
  • NORIS A1-91 PLC Rack Board Specifications
  • Mitsubishi A3ACPUR21 MELSEC PLC CPU Module
  • Beckhoff EP7041‑3002 EtherCAT Box Digital Input Module
  • REER EOS2E 1053 EOS2R 1053 Safety Light Curtain
  • Mitsubishi Q80BD-J71BR11 MELSECNET/H Interface Board
  • Omron 3G3IV-B4220-EV2 VFD 400V 22kW
  • Allen-Bradley 96844671 1785-LT3 PLC-5/12 Processor Module
  • Pasaban MTC3001-DC Drive Control PLC Module
  • Omron CJ1M-CPU11 V4.0 PLC CPU Module
  • ABB CM579-PNIO B3 Communication Module
  • B&R X20 AI 4221 Analog Module
  • Siemens 6SY7000-0AC80 PLC Module
  • GE 531X300CCHAFM5 Control Card
  • AB 810-A15C Inverse Time Relay
  • WITTENSTEIN LP120X-MF2-20 Planetary Gear
  • Mitsubishi Kakoki E-01B-4130 PLC I/O Modules
  • ABB DSQC643 Safety Control Board
  • Siemens G26004-A2105-P100-2 PCB
  • OMRON F350-C10E Image Processing Unit
  • FUJI UG430H-TS1 HMI Touch Panel
  • Westronics CB100188-01 Rev F Board
  • Siemens 7MH4900-3AA01 Weighing Module
  • Gilbert & Nash Tracker 2000 Control Cabinet
  • OMRON CJ1M-CPU22 CPU Unit
  • OMRON F3SJ-E0625P25 Light Curtain
  • Siemens 3VA2340-5HL32-0AA0 Breaker
  • Mitsubishi Melsec A61P A2NCPU PLC System
  • Aeco 158-02 DSP-02 PCB Card
  • FUJI NP1PS-32R CPU Module
  • Siemens 6SL3040-1MA01-0AA0 Control Unit CU320-2 PN
  • Fuji RYE.75D PLC Driver AC Drive
  • Electro Cam PS-6144-24-P16M09-L-MB Programmable Limit Switch
  • Siemens C98043-A7001-L2-4 CUD1 Control Board
  • Pilz 312070 PSSu H PLC1 FS SN SD Safety Module
  • Siemens Plc42q4200atsn Circuit Breaker Fuse Box
  • GE Fanuc IC695ALG708-AB Analog Output Module Rx3i
  • Siemens 6SE7036-5GK84-1JC2 IGD8 Gate Driver Board
  • Charmilles 813078 852029 PLC PCB Robocut 2 CNC EDM
  • Siemens 6SL3130-1TE24-0AA0 Smart Line Module
  • Pasaban MTC3001-DC Drive Control PLC Module
  • Modicon AS-P890-000 Remote I/O Processor Power Supply
  • Siemens PXC100-PE96.A PXC Modular Controller
  • TOYO KEIKI P:CARD5 AVH-R YH-212 Industrial Control Card
  • Omron NS5-SQ00B-V2 HMI Touch Screen 5.7 Inch
  • Sciemetric SigPOD 1202-0H00 Data Acquisition Module
  • GE Fanuc IC693CPU331W CPU Module Series 90-30
  • Square D 8903SVO11V02 Lighting Contactor 200A
  • Beckhoff C9900-P224 Power Supply Unit 24V 10A
  • HSD PE323 PLC I/O Module
  • Pillar AB6406-11A Power Control Board
  • GE Fanuc IC693CPU331W CPU Module
  • FANUC A61L-0001-0072 LCD Monitor
  • AB 20D-D-011-A-0-EYNANANE Drive
  • AB 1785-L20B PLC-5/20 Processor
  • Siemens SIREC P/PA Recorder 7ND3021
  • Siemens D2E160-AH01-17 Fan Blower
  • Eaton 101073735-001 LEG Module
  • AB 1404-M605B-ENT Powermonitor 3000
  • OMRON CJ1W-MAD42 Analog I/O
  • Omron CJ1M-CPU13 V3.0 PLC CPU Module
  • Pe323 HSD PLC Module Industrial Controller
  • Pasaban MTC3001-DC Drive Control PLC Module
  • Mitsubishi R02CPU PLC Module MELSEC iQ-R
  • B&R X20DC2395 Digital Output Module 32 Ch
  • Hoffman A30N24ALP Enclosure with PLC Addons
  • Rieter PLC with RMC 24/5V 10 RMC188-1 RMC RIO-1
  • Allen-Bradley 1790D-TN4V0 CompactBlock LDX Base Block 4 AI
  • National Instruments NI 9242 Analog Input Module 4-Channel
  • ABB AO820 3BSE008546R1 Analog Output Module
  • Moeller XVC-101-C192K-K82 PLC
  • AB 440F-C4000P MatGuard Controller
  • AB 1692-ZRCLSS Protection Module
  • Schneider S48896 PLC Module
  • FANUC A02B-0303-C205 I/O Module
  • AB 1785-LT4 PLC-5/10 Processor
  • AB 1746-NO8V SLC 500 Analog Output
  • OMRON CQM1-TC001 Temperature Unit