Fault recording: Equipped with a fault recording module, it can record analog and binary data. The analog signal sampling rate is 1.2kHz, and the recording time includes pre trigger and post trigger times. It is stored in a circular buffer and can be exported for analysis.
Operation interface
LCD display: Backlit LCD display, with a single line diagram on the left and measurement values, menus, protection signals, and event records on the right. It can display up to eight switch device icons and other motor, transformer, and other icons.
Status indication: including operating status (green LED "Ready"), communication status (green LED, turns red in case of fault), alarm indication (red LED), interlock status (unused).