Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

AB 1771-OFE Series B Analogue Output Modules

F: | Au:FAN | DA:2025-04-21 | 1110 Br: | 🔊 点击朗读正文 ❚❚ | Share:

AB 1771-OFE Series B Analogue Output Modules

Module Overview:

Functionality: The 1771- OFE is an intelligent block transfer module that converts binary or quadruple BCD values supplied 

by the processor into analogue signal outputs. It has four independently isolated differential output channels with selectable scaling, data format, etc. 

It requires no external power supply and occupies only one I/O slot.


Output range: There are three versions, 1771-OFE1 is a voltage output, 1 - 5V dc, 0 - 10V dc, +10V dc can be selected through the configuration jumper; 

1771-OFE2 and 1771-OFE3 are current outputs, 4 - 20mA and 0 - 50mA respectively, and the latter two are factory-set.

Communication mode: The processor transmits data to and from the module through the BTW and 

BTR instructions in the ladder program to send output values, set modes and receive status information.


Installation steps:

Preparation for installation: Comply with the relevant EU directives, calculate the power requirement before installation 

to avoid overloading the backplane and power supply of the I/O chassis.

Module Setup: Can be installed in any slot of the I/O chassis, but avoid grouping with discrete high-density modules, 

and keep away from AC or high-voltage DC modules. Set configuration jumpers, including the 

last state configuration jumper (determines the output state in the event of a communication failure) and the voltage range configuration jumper (for 1771-OFE1)

Installation and Connections: Install the keying strip, insert the module smoothly into the chassis and secure it, and connect the 1771-WH junction arm; 

use the 1771-WC junction arm to connect to analogue equipment with the sensor cable shielded and grounded at the chassis end only.


The module is configured:

Configuration: Configure the module using a Block Transfer Write command (BTW) with a 13-word maximum 

write block containing output data, data format, and scaling information.

Data format and scaling: data format can be BCD or binary, scaling function can convert data to engineering units, 

by setting the corresponding scaling value, the maximum scaling value is 9999, the minimum is - 9999, and the maximum must be greater than the minimum.

Default Configuration: At power-on, the module microprocessor defaults to positive data words, no scaling, and BCD data format.


Programming Points:

Programming Format: The programming format is different for different processors, PLC-2, PLC-3, PLC-5 have their own characteristics, 

and the module does not allow the enable bit of the read/write instruction to be set to ON at the same time.

Programming Considerations: Including block length and scaling considerations (e.g., different settings for no-channel scaling, partial-channel scaling, 

and full-channel scaling), block transfer boundary words (PLC-2 processor), 

and module update time (8 milliseconds for BCD and scaling, and 1.6 milliseconds for binary and no scaling).


Performance

Optimisation of hardware mounting and layout: Choose the location of the modules in the I/O chassis appropriately, 

avoiding the grouping of discrete high-density modules, and keeping them away from AC or high-voltage DC modules in order 

to reduce electromagnetic interference. 

Modules that are too close to these sources of interference may result in unstable signal transmission and affect the accuracy of 

the analogue output. Installing the module in a location away from the source of interference with 

good shielding and grounding can effectively reduce the impact of electromagnetic interference 

on the performance of the module and improve the quality of signal transmission . 

Ensure that the sensor cable is properly connected and well shielded, and the cable shield is grounded only at the chassis end to reduce noise interference. 

If the shield is not properly grounded or shielded cable is not used, external noise may be coupled into the signal line, 

resulting in fluctuations or errors in the output signal. 


The use of high quality shielded cables, such as Belden 8761, and grounding in strict accordance with the specifications, 

can enhance the module's anti-interference ability and ensure the stability of the output signal.

Fine adjustment of parameter configuration: According to the actual application requirements, precisely set the output range and data format of the module. 

Different analogue devices have different requirements for input signals, and the correct choice of output range 

and data format can ensure the compatibility of the module with the device and improve the output accuracy. 

For devices requiring 0 - 10V voltage input, setting the output range of the 1771-OFE1 module to 0 - 10V and selecting the appropriate data 

format (e.g., binary or BCD) can match the output of the module with the requirements of the device, 

avoiding data conversion errors caused by incompatible formats. 


Reasonable use of the scaling function to convert data to actual engineering units can improve the readability and practicality of the data. 

When setting the scaling parameters, it should be ensured that the maximum scaling value is greater than the minimum scaling value, 

and the format of all the scaling information is consistent with the format of the module sent to the data table. 

For an application that measures temperature and converts it to voltage output, the temperature value can be accurately converted to 

the corresponding voltage signal output by precisely setting the scaling parameters, which is convenient for subsequent monitoring and control.

Improved programming strategy: Depending on the type of processor, choose the appropriate programming method and strictly follow 

the programming specifications. When using PLC - 2, PLC - 3, PLC - 5 and other processors, pay attention to the use of block transfer instructions 

and restrictions, avoid enabling the enable bit of read/write instructions at the same time to prevent data transfer errors. 

For the PLC-2 processor, programs should be written according to its specific programming structure to ensure correct data transfer and processing. 


Optimise the settings for block length and scaling by determining whether to scale all channels and how to set the scaling values according to 

the actual situation. In some applications, only some channels may need to be scaled, in which case the block length 

and scaling parameters should be set appropriately to improve data processing efficiency. 

If only two channels are scaled, the appropriate block length can be set and the scaling value can be entered accurately 

to avoid unnecessary calculations and data transfers and to improve the system operation efficiency .

Regular calibration and maintenance: Regular calibration of the module ensures the accuracy of its output. 

The calibration process includes preparatory work (e.g. switching off the power, connecting the test equipment, etc.) 

and calibration operations for each channel. 

For the voltage output version of the module, the output voltage is calibrated by adjusting the potentiometer; for the current output version of the module, 

the corresponding current calibration operation is also required. 


Regular calibration can detect and correct possible deviations of the module in time to ensure its long-term stable operation. 

Pay close attention to the running status of the module, through the indicator lights and diagnostic bits to timely detect faults and take appropriate measures. 

When the red FAULT indicator lights up, the connection, configuration and hardware status of the module should be checked according to the fault prompts, a

nd the faulty parts should be replaced in time to ensure that the module works normally. 

If the output of a channel is found to be abnormal, the cause of the fault can be determined by reading the diagnostic bit information, 

such as whether the data is out of range, whether the scaling is correct, etc., and then carry out targeted repair.

Allen Bradley 1771-OFE2 Ser. B Analog Output Module, 7.9 W

  • SIGMATEK Krauss Maffei PC301-K 01-310-301-K Industrial PC
  • SIGMATEK SDD310-23 VARAN Servo Drive
  • SIGMATEK CDM 163 and CIC 011 C-DIAS Input Modules
  • SIGMATEK MDP 101-1 Power Module
  • SIGMATEK CM5V020 Wiring Circuit with CTMS020
  • SIGMATEK CCP521 C-DIAS Processor Module
  • SIGMATEK MDP 101-K Power Module
  • SIGMATEK ETEK C-IPC 733MHz VIA Eden 7000
  • SIGMATEK DCP 643 DIAS PLC CPU Module
  • SIGMATEK TAE121 12-200-121 Operator Terminal
  • Sigmatek TMS012-T Injection Moulding Technology Module
  • Sigmatek MDD 121-1 Controller
  • Sigmatek CDM167 Module
  • Sigmatek DCP082 DIAS Central Unit
  • Sigmatek ETT731 Built-In Terminal Touch
  • Sigmatek CCP521 C-DIAS Processor Module
  • Sigmatek Krauss Maffei PC301-K Control Cabinet PC
  • Sigmatek CIC-21 C-DIAS CAN Module
  • Sigmatek CIO-011 Multi I O Module
  • Sigmatek 01-450-152D C-IPC 152 Industrial PC
  • SIGMATEK 01-450-024 C-IPC 128MB VIA 733MHz
  • SIGMATEK CCL-081 C-DIAS Processor Module
  • SIGMATEK CP311 20-004-311 Module
  • SIGMATEK EP00000262 SLIDES MIDI I O-V3 Controller
  • SIGMATEK TMS012-T Slides Technology Module
  • SIGMATEK MDD111-1 Drive Axis Module
  • SIGMATEK MDP101-1 PLC Module
  • SIGMATEK CP111 S-DIAS Processor Module
  • DEMAG ErgoControl Sigmatek NC4 Display Unit
  • SIGMATEK DCP642 Module
  • Sigmatek Demag NC4 9617.067.03 Control Module
  • Sigmatek DCP 643 Central Processing Unit
  • Sigmatek VI 021 S-SLIDES VARAN Interface Module
  • Sigmatek SDD340-46 Servo Drive 14kVA
  • Sigmatek DSI021 Slide Siemens Interface
  • Sigmatek CCL912 C-SLIDES CPU PSU Module
  • Sigmatek ETV1521 VARAN Control Panel
  • Sigmatek ET322 Operator LCD Terminal
  • Sigmatek MDD1111 DIAS Drive Module
  • Sigmatek CAM123 Module
  • SIGMATEK CP111 VARAN Ethernet Controller
  • SigmaTek MDD 111 Axle Module
  • SIGMATEK CIO013 C-DIAS I O Module
  • SIGMATEK AKM52K-ANC2GBB0 Servomotor 640VDC
  • SIGMATEK ETT321 01-230-321 Touch Screen
  • SIGMATEK NC4Kompakt 01-250-010-D Safety Controller
  • SIGMATEK CIO011 C-DIAS Multi I O Module
  • SIGMATEK MDD 121-1 Drive Axis Module
  • SIGMATEK CDM163 Control Module
  • Sigma-Tek 4000HR-3 Heading Reference Directional Gyro
  • Sigmatek DIAS DAI 883 Analog Input Module
  • Sigmatek 0332.554.03 Printed Circuit Board Card
  • Sigma Tek 5000B-36 Attitude Gyro 8130
  • Demag NC4 0332.554.03 Sigmatek Control Board
  • Sigmatek IPC Pentium 300 CF Industrial PC
  • Sigmatek MDP 102 PLC Module
  • Sigmatek DTO163 Digital Output Module
  • Sigmatek PCT151 Touch IPC 15 Panel and I-PC C300
  • Sigmatek CCL911 CD Processor Module
  • Sigmatek SCP011 S-DIAS Safety CPU Module
  • Sigmatek SE051 Network Splitter Module
  • Sigmatek CIO011 C-DIAS I O Module
  • Sigmatek SE051 Ethernet Splitter
  • Sigmatek CCL911 CD Processor Module
  • Sigmatek SDD310-4 DIAS Drive 14kVA
  • Sigmatek CTMS020 C-DIAS Technology Module
  • Sigmatek CTMS020 CD Technology Module
  • Sigmatek CTO167 C-SLIDES Digital Output Module
  • Sigmatek C-IPC 152 Industrial PC
  • Sigmatek SDD310-4 SLIDES Drive 310
  • SIGMATEK MDP 102-1 DIAS Power Module
  • SIGMATEK SCP111 S-DIAS Safety CPU Industrial
  • SIGMATEK CAO081 Analog Output Module
  • SIGMATEK DCC080L Control Module
  • SIGMATEK MDP101-1 Power Module
  • SIGMATEK SCP111 S-DIAS Safety CPU
  • SIGMATEK PC325-K Industrial PC
  • SIGMATEK ETT 731 Operator Terminal
  • SIGMATEK DSV011 SLIDES Hub Module 05-023-011
  • SIGMATEK 12-780-012 R8-IPC Industrial Computer
  • Sigmatek SE051 Ethernet Splitter
  • Sigmatek DAI 883 DIAS Analog Module
  • Sigma Tek 4000B-30 Directional Gyro
  • Sigmatek CP112 S-DIAS Processor Module
  • Sigmatek SDD310 DIAS Drive
  • Sigmatek SDD120-23 DIAS Drive 14kVA
  • Sigmatek C-IPC 152 Industrial PC
  • Sigmatek CIV513 VARAN Control Module
  • Sigmatek DCP 082 Processor Module
  • Sigmatek C-IPC Industrial PC 01-450-023 GEB
  • SIGMATEK PC572 Operating Terminal
  • SIGMATEK DCC041 DIAS Compact Controller HW 6.10
  • SIGMATEK C-IPC 152 1GB Celeron M440 Controller
  • SIGMATEK 01-310-322-K PC322-K Industrial PC
  • SIGMATEK TAE732-P Touch Screen Operator Panel
  • SIGMATEK 01-018-100 Control Module
  • SIGMATEK DDI-164 Digital Input Module
  • Sigma-Tek 5000B-36 Artificial Horizon
  • SIGMATEK 12-780-012 R8-IPC Geode LX800 Computer
  • SIGMATEK CTMS 020 Servo Drive
  • Sigmatek MDD121-1 Controller
  • Sigmatek ETV1021-L VARAN Terminal
  • Sigmatek DST022 DIAS Module
  • Sigmatek CCP512-K C-Dias Processor Module
  • Sigmatek SRO 021 Relay Output Module
  • Sigmatek SDI 101 Digital Input Module
  • Sigmatek IPC 221 Industrial PC
  • Sigmatek DNC-305 Digital Input Module
  • Sigmatek SDD335 DIAS Drive
  • Sigmatek C-IPC Industrial Controller
  • SIGMATEK 01-450-031 C-IPC 256MB LX800 Computer
  • SIGMATEK SDD310-3 DIAS Drive 310
  • SIGMATEK DSV011 SLIDES Hub Module 05-023-011
  • SIGMATEK CNC031 CD Analog Module 12-011-031
  • SIGMATEK 01-450-031 C-IPC 256MB LX800
  • SIGMATEK 01-450-026 C-IPC VIA 733MHz Controller
  • SIGMATEK DCP-643 DIAS CPU Module with DKL-003
  • SIGMATEK MDD111-L DIAS Drive Axis Module
  • SIGMATEK SDD310-23-L DIAS Drive 310
  • SIGMATEK Viscotec ETV0551 Touch Panel
  • SIGMATEK PC321K Industrial Computer
  • SIGMATEK MDP 102-1 SLIDES Power Module
  • SIGMATEK TAE-151 12-200-151 Light Terminal
  • SIGMATEK CP102 20-004-102P6995B HMI Panel
  • SIGMATEK CAM-123 12-017-123-C Analog Mixing Module
  • SIGMATEK DCC041 DIAS Compact Controller
  • SIGMATEK DVI021 and DKL015 DIAS Power Module
  • SIGMATEK SDD340-46 SDD Series Servo Drive