Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

AB 1771-OFE Series B Analogue Output Modules

F: | Au:FAN | DA:2025-04-21 | 1092 Br: | 🔊 点击朗读正文 ❚❚ | Share:

AB 1771-OFE Series B Analogue Output Modules

Module Overview:

Functionality: The 1771- OFE is an intelligent block transfer module that converts binary or quadruple BCD values supplied 

by the processor into analogue signal outputs. It has four independently isolated differential output channels with selectable scaling, data format, etc. 

It requires no external power supply and occupies only one I/O slot.


Output range: There are three versions, 1771-OFE1 is a voltage output, 1 - 5V dc, 0 - 10V dc, +10V dc can be selected through the configuration jumper; 

1771-OFE2 and 1771-OFE3 are current outputs, 4 - 20mA and 0 - 50mA respectively, and the latter two are factory-set.

Communication mode: The processor transmits data to and from the module through the BTW and 

BTR instructions in the ladder program to send output values, set modes and receive status information.


Installation steps:

Preparation for installation: Comply with the relevant EU directives, calculate the power requirement before installation 

to avoid overloading the backplane and power supply of the I/O chassis.

Module Setup: Can be installed in any slot of the I/O chassis, but avoid grouping with discrete high-density modules, 

and keep away from AC or high-voltage DC modules. Set configuration jumpers, including the 

last state configuration jumper (determines the output state in the event of a communication failure) and the voltage range configuration jumper (for 1771-OFE1)

Installation and Connections: Install the keying strip, insert the module smoothly into the chassis and secure it, and connect the 1771-WH junction arm; 

use the 1771-WC junction arm to connect to analogue equipment with the sensor cable shielded and grounded at the chassis end only.


The module is configured:

Configuration: Configure the module using a Block Transfer Write command (BTW) with a 13-word maximum 

write block containing output data, data format, and scaling information.

Data format and scaling: data format can be BCD or binary, scaling function can convert data to engineering units, 

by setting the corresponding scaling value, the maximum scaling value is 9999, the minimum is - 9999, and the maximum must be greater than the minimum.

Default Configuration: At power-on, the module microprocessor defaults to positive data words, no scaling, and BCD data format.


Programming Points:

Programming Format: The programming format is different for different processors, PLC-2, PLC-3, PLC-5 have their own characteristics, 

and the module does not allow the enable bit of the read/write instruction to be set to ON at the same time.

Programming Considerations: Including block length and scaling considerations (e.g., different settings for no-channel scaling, partial-channel scaling, 

and full-channel scaling), block transfer boundary words (PLC-2 processor), 

and module update time (8 milliseconds for BCD and scaling, and 1.6 milliseconds for binary and no scaling).


Performance

Optimisation of hardware mounting and layout: Choose the location of the modules in the I/O chassis appropriately, 

avoiding the grouping of discrete high-density modules, and keeping them away from AC or high-voltage DC modules in order 

to reduce electromagnetic interference. 

Modules that are too close to these sources of interference may result in unstable signal transmission and affect the accuracy of 

the analogue output. Installing the module in a location away from the source of interference with 

good shielding and grounding can effectively reduce the impact of electromagnetic interference 

on the performance of the module and improve the quality of signal transmission . 

Ensure that the sensor cable is properly connected and well shielded, and the cable shield is grounded only at the chassis end to reduce noise interference. 

If the shield is not properly grounded or shielded cable is not used, external noise may be coupled into the signal line, 

resulting in fluctuations or errors in the output signal. 


The use of high quality shielded cables, such as Belden 8761, and grounding in strict accordance with the specifications, 

can enhance the module's anti-interference ability and ensure the stability of the output signal.

Fine adjustment of parameter configuration: According to the actual application requirements, precisely set the output range and data format of the module. 

Different analogue devices have different requirements for input signals, and the correct choice of output range 

and data format can ensure the compatibility of the module with the device and improve the output accuracy. 

For devices requiring 0 - 10V voltage input, setting the output range of the 1771-OFE1 module to 0 - 10V and selecting the appropriate data 

format (e.g., binary or BCD) can match the output of the module with the requirements of the device, 

avoiding data conversion errors caused by incompatible formats. 


Reasonable use of the scaling function to convert data to actual engineering units can improve the readability and practicality of the data. 

When setting the scaling parameters, it should be ensured that the maximum scaling value is greater than the minimum scaling value, 

and the format of all the scaling information is consistent with the format of the module sent to the data table. 

For an application that measures temperature and converts it to voltage output, the temperature value can be accurately converted to 

the corresponding voltage signal output by precisely setting the scaling parameters, which is convenient for subsequent monitoring and control.

Improved programming strategy: Depending on the type of processor, choose the appropriate programming method and strictly follow 

the programming specifications. When using PLC - 2, PLC - 3, PLC - 5 and other processors, pay attention to the use of block transfer instructions 

and restrictions, avoid enabling the enable bit of read/write instructions at the same time to prevent data transfer errors. 

For the PLC-2 processor, programs should be written according to its specific programming structure to ensure correct data transfer and processing. 


Optimise the settings for block length and scaling by determining whether to scale all channels and how to set the scaling values according to 

the actual situation. In some applications, only some channels may need to be scaled, in which case the block length 

and scaling parameters should be set appropriately to improve data processing efficiency. 

If only two channels are scaled, the appropriate block length can be set and the scaling value can be entered accurately 

to avoid unnecessary calculations and data transfers and to improve the system operation efficiency .

Regular calibration and maintenance: Regular calibration of the module ensures the accuracy of its output. 

The calibration process includes preparatory work (e.g. switching off the power, connecting the test equipment, etc.) 

and calibration operations for each channel. 

For the voltage output version of the module, the output voltage is calibrated by adjusting the potentiometer; for the current output version of the module, 

the corresponding current calibration operation is also required. 


Regular calibration can detect and correct possible deviations of the module in time to ensure its long-term stable operation. 

Pay close attention to the running status of the module, through the indicator lights and diagnostic bits to timely detect faults and take appropriate measures. 

When the red FAULT indicator lights up, the connection, configuration and hardware status of the module should be checked according to the fault prompts, a

nd the faulty parts should be replaced in time to ensure that the module works normally. 

If the output of a channel is found to be abnormal, the cause of the fault can be determined by reading the diagnostic bit information, 

such as whether the data is out of range, whether the scaling is correct, etc., and then carry out targeted repair.

Allen Bradley 1771-OFE2 Ser. B Analog Output Module, 7.9 W

  • ABB SACO 64D4 Digital Annunciator Unit 64-Channel Alarm System
  • EMERSON FloBoss S600+ P154 PRV Board 7381540 Prover Module
  • EMERSON FloBoss S600+ P155 PSU Board 7161550 Power Supply
  • EMERSON FloBoss S600+ P153 Front Panel 7181530 Display Keypad
  • EMERSON FloBoss S600+ P148 Dual Pulse Mezzanine 7181483 Module
  • EMERSON FloBoss S600+ P144 I/O Board 7281440 Analog Digital Module
  • EMERSON FloBoss S600+ P152 CPU Board 7381520 Main Processor
  • EMERSON FloBoss S600+ Base Unit 8176003 Flow Computer Chassis
  • Lauer PCS100FZ XX1.1031.SHX PLC HMI Operator Panel
  • Lauer Weber PCS095.S PG 195.203.3 Operator Panel HMI
  • Lauer Pcs Light PG 080.308.E Operator Panel HMI Console
  • Lauer Pcs Light PG 080.308.E Operator Panel HMI
  • Lauer PCS590p Pg 59X.000.0 PROFIBUS-DP HMI Panel
  • Lauer PCS095.1 095.408.A Operator Panel HMI
  • Lauer PCS009.m 109.203.1 Operator Panel PCS009
  • Lauer Pcs Light PG 080.308.F PLC HMI Operator Panel
  • Lauer Pcs 095.s 195.203.3 Operator Panel – Industrial HMI
  • Lauer LCA 200 (200-V02093) Starline Mini Operator Terminal – Compact HMI
  • Lauer PCS 110FZ Operating Screen – Compact Industrial Display
  • Lauer LCA200 022/581 Operator Terminal – Industrial HMI Panel
  • Lauer AST-150A Front Cover with Touch – Replacement Bezel for Industrial Panels
  • Lauer PCS8010 035/28B Operator Panel – Industrial HMI
  • Lauer PCS260FZ Membrane Keyboard Replacement
  • Lauer PCS plus MPI PCS090.m Operator Console
  • Lauer PCS 806 EEPROM Memory Module
  • Lauer VPC S95e 410 Control Panel System Controller
  • Lauer PG095.507.A Operator Panel PCS095 HMI
  • Lauer PCS8010 035/28B Operator Panel HMI Console
  • Lauer Pcs 810 Interface Module – 01676-B8 Communication Unit
  • Lauer PCS950 Keyboard – Replacement Keypad for Operator Panels
  • Lauer LCA200-V00880 Operator Terminal – Industrial HMI Panel
  • Lauer Pz 095 Operator Panel – PG095.507.A Branson Label HMI
  • Lauer PCS095 Operator Panel – PG095.408.A Industrial HMI
  • Lauer PCS095 Display Control Unit – PG095.508.B Industrial HMI
  • Lauer PCS009.S Membrane Keyboard – Replacement Keypad for Operator Panels
  • Lauer LHT-T100t-Ne Control Panel – V16-10-10 Industrial HMI
  • Rohwedder PQ1206 Control Panel – PCS095 PG 095.508.A HMI
  • Lauer 19557-D4 Text Display – Industrial Alphanumeric Terminal
  • Lauer PCS950 Control Panel PG950.103.0
  • Lauer VPC Monitor 112TE Industrial Display
  • Lauer PCS 609 Topline Micro Operator Panel
  • Lauer PCS110FZ PG1001 Operator Panel Control Console
  • KBA BAB50312 Operating Terminal – RGF 518297 Press Control Panel
  • Lauer 4x40 Alphanumeric Display – Industrial Text Terminal
  • Lauer PCS830-3 Operator Panel – Industrial HMI Terminal
  • Lauer PCS900 (900.202.6 / 060695) Operator Panel – Metronic Series Industrial HMI
  • Lauer PG095.507.A Operator Panel – Compact Industrial HMI
  • Lauer LCA 265 Text Display – Alphanumeric Control Unit
  • Lauer VPC S95e 410 V101.C Control Unit – VPC System Controller
  • Lauer PCS 200 Control Console – PG 200.011.4 Operator Panel
  • Lauer PCS 8010 Operator Panel – Industrial HMI Terminal
  • Lauer 047/00 Power Supply Module – Industrial DC Unit
  • Lauer PCS600FZ Operator Panel PCS Systems Control Console
  • Lauer LCA 265 Text Display Control Unit
  • Lauer WOP-iT X550tm 06539 Operator Panel HMI
  • Lauer AST-150A Cover with Touch 4PIN 251X322mm
  • Lauer 035/18F Systeme Lauer Operator Panel Display
  • Lauer LCA200 022/581 Text Display Console
  • Lauer PCS8110 035/38A Operator Panel HMI Console
  • Lauer 035/18F LS Systems Operator Panel HMI Display
  • Lauer MT212 USB Control Panel 24V DC 1A 15VA
  • Lauer PCS 810 System Communication Module – Industrial Network Interface
  • Lauer Pz 095 Operator Panel – PG 095.508.A Industrial HMI
  • Lauer 06134 Embedded Industrial PC – Compact Fanless Computer
  • Lauer EPC640TC Front Cover – Replacement Bezel for Industrial Panel
  • Lauer PCS 600 Euroterminal Control Panel – 00480-B3 Compact HMI
  • Lauer LCA 180 Text Monitor – Compact Alphanumeric Display for Industrial Control
  • Lauer VK212B.5.0.1.0.LAU VPC Control Panel – Industrial HMI
  • Lauer PCs090 Topline Control Panel – PG090.205.B Operator Interface
  • Lauer PCs 811 Interbus S Module – PG 811.000.3 Fieldbus Interface
  • BACHMANN IPC1410 Membrane Keypad – Replacement Switch Keyboard
  • Lauer LCA 640.1 Operator Terminal – Compact Text/Graphic Display
  • Lauer PCS 8010 Operator Panel – Versatile Industrial Terminal
  • Lauer AIO 110 C6FBXP openAutomation – All-in-One Industrial Controller
  • Lauer PCS009.S Membrane Keyboard – Replacement Keypad for Operator Panels
  • Lauer 035/18F LS Systems Power Supply – Industrial DC Module
  • Lauer PCS095.5 PCS095.417.A Operator Panel
  • Lauer WOP IT X 550KTC Mobile Panel – Wireless Operator Terminal
  • Lauer PCS 810 E Interface Assembly – 2W/6ES5 491 0LB11
  • Lauer P090b/L033/02a Interface Module – Compact I/O and Power Unit
  • Lauer LP035/18 Power Supply Module – Industrial DC Power Unit
  • Lauer PCs 090 Topline Control Console – 090.205.B Operator Panel
  • Lauer VT215e.II.NTR VPC Control Panel – Take Off Line HMI
  • Lauer P090b/L033/03 Interface Module – Power and I/O Unit
  • Lauer EPC X 550 TC Panel PC – Industrial Touch Computer
  • Lauer Mt212.Lau Industrial Monitor – 24V DC 15VA Display
  • Lauer PCS 810 Communication Module – System Communication Unit
  • Lauer PCS811 Interbus-S Interface Module – Version 811.000.3
  • Lauer PCS810-1 Interface Module – PCS810-100186-C5
  • Lauer TP21AM/731030 Teach Pendant – Handheld Operator Terminal
  • Lauer LP035/18 Power Supply Module – Industrial DC Power Unit
  • Lauer LCA 200.202.2 Mini Control Unit Display
  • Pulsotronic 8450-00 Power Supply for Lauer Systems
  • Lauer Starline Midi LCA300.0 Text Display Console
  • Lauer PCS9000 035/27C Operator Panel HMI Display Unit
  • Lauer PCS900 PG900.202.6 Operator Panel Control Console
  • Lauer PCS090 PG090.000.4 Operator Panel Control Console
  • Lauer LCA265 Text Display Industrial Information Console
  • Lauer PCS 200FZ Control Panel Industrial Operator Console
  • Lauer PCS810-3 Interface Module Communication Board
  • Lauer PCS009 009.204.2 Operator Panel HMI Control Console
  • Lauer A-110-C6FBXP Industrial Display Monitor
  • Lauer VPCM 310 Key Control Panel Industrial Keyboard Interface
  • Lauer PCS830.0 Operator Panel – Mid-Range HMI for Versatile Applications
  • Lauer PCS950 PG 950.100.6 Operator Panel – High-End HMI for Complex Systems
  • Lauer LCA041 Text Display – Compact Alphanumeric Terminal
  • Lauer VT215B.II VPC Control Panel – Compact Versatile HMI
  • Lauer LCA 245 Text View 245.100.1 – Alphanumeric Display for Simple Control
  • Lauer PCS600FZ Operator Panel – Enhanced HMI with Extended Features
  • Lauer PCS600 PX 600.002.1 Operator Panel – Compact HMI with High Performance
  • Lauer VPC VK212b.II.LAU Control Panel – Robust HMI for Heavy Industry
  • Lauer PCS 810-1 Operator Terminal – Advanced HMI for Mid-Size Systems
  • Lauer 07182-F5 Control Panel LCA 245 – Industrial HMI for Complex Automation
  • Lauer PSC830-31 Interface Module Industrial Communication Board
  • Lauer PCS806.0 Interface Module Industrial Automation Component
  • Lauer LCA 200.102.1 Text Display LCA Starline Mini Console
  • Lauer Panel VPCT MT215L Industrial Touch Panel Display
  • Lauer Suetron Panel TP21AM/731030 Teach Pendant Industrial Touch Panel
  • Lauer PG090.000.4 120592 Control Panel PCS090 Topline Operator Panel
  • Lauer PCS 830 Interface Module Industrial Communication Board
  • Lauer PCS830-1 Interface Module TTY Communication Board
  • Lauer PCS9000 035/27C Operator Panel HMI Display Unit
  • Lauer EPC-PM-1500tc Industrial PC Embedded Computer Specifications
  • Lauer PCS804.1 Operator Terminal – Compact Industrial HMI
  • Lauer VPC VK212b.II.LAU Control Panel – Rugged Operator Interface
  • Lauer PCS090 PG090.208.E Topline Mini – Compact HMI Panel
  • Lauer PCS090 PG090.205.B Topline Operator Panel – High Performance HMI
  • Lauer P090b/L033/00a Interface Module – Reliable Automation I/O