Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

AB 1771-OFE Series B Analogue Output Modules

来源: | 作者:FAN | 发布时间 :2025-04-21 | 703 次浏览: | Share:

AB 1771-OFE Series B Analogue Output Modules

Module Overview:

Functionality: The 1771- OFE is an intelligent block transfer module that converts binary or quadruple BCD values supplied 

by the processor into analogue signal outputs. It has four independently isolated differential output channels with selectable scaling, data format, etc. 

It requires no external power supply and occupies only one I/O slot.


Output range: There are three versions, 1771-OFE1 is a voltage output, 1 - 5V dc, 0 - 10V dc, +10V dc can be selected through the configuration jumper; 

1771-OFE2 and 1771-OFE3 are current outputs, 4 - 20mA and 0 - 50mA respectively, and the latter two are factory-set.

Communication mode: The processor transmits data to and from the module through the BTW and 

BTR instructions in the ladder program to send output values, set modes and receive status information.


Installation steps:

Preparation for installation: Comply with the relevant EU directives, calculate the power requirement before installation 

to avoid overloading the backplane and power supply of the I/O chassis.

Module Setup: Can be installed in any slot of the I/O chassis, but avoid grouping with discrete high-density modules, 

and keep away from AC or high-voltage DC modules. Set configuration jumpers, including the 

last state configuration jumper (determines the output state in the event of a communication failure) and the voltage range configuration jumper (for 1771-OFE1)

Installation and Connections: Install the keying strip, insert the module smoothly into the chassis and secure it, and connect the 1771-WH junction arm; 

use the 1771-WC junction arm to connect to analogue equipment with the sensor cable shielded and grounded at the chassis end only.


The module is configured:

Configuration: Configure the module using a Block Transfer Write command (BTW) with a 13-word maximum 

write block containing output data, data format, and scaling information.

Data format and scaling: data format can be BCD or binary, scaling function can convert data to engineering units, 

by setting the corresponding scaling value, the maximum scaling value is 9999, the minimum is - 9999, and the maximum must be greater than the minimum.

Default Configuration: At power-on, the module microprocessor defaults to positive data words, no scaling, and BCD data format.


Programming Points:

Programming Format: The programming format is different for different processors, PLC-2, PLC-3, PLC-5 have their own characteristics, 

and the module does not allow the enable bit of the read/write instruction to be set to ON at the same time.

Programming Considerations: Including block length and scaling considerations (e.g., different settings for no-channel scaling, partial-channel scaling, 

and full-channel scaling), block transfer boundary words (PLC-2 processor), 

and module update time (8 milliseconds for BCD and scaling, and 1.6 milliseconds for binary and no scaling).


Performance

Optimisation of hardware mounting and layout: Choose the location of the modules in the I/O chassis appropriately, 

avoiding the grouping of discrete high-density modules, and keeping them away from AC or high-voltage DC modules in order 

to reduce electromagnetic interference. 

Modules that are too close to these sources of interference may result in unstable signal transmission and affect the accuracy of 

the analogue output. Installing the module in a location away from the source of interference with 

good shielding and grounding can effectively reduce the impact of electromagnetic interference 

on the performance of the module and improve the quality of signal transmission . 

Ensure that the sensor cable is properly connected and well shielded, and the cable shield is grounded only at the chassis end to reduce noise interference. 

If the shield is not properly grounded or shielded cable is not used, external noise may be coupled into the signal line, 

resulting in fluctuations or errors in the output signal. 


The use of high quality shielded cables, such as Belden 8761, and grounding in strict accordance with the specifications, 

can enhance the module's anti-interference ability and ensure the stability of the output signal.

Fine adjustment of parameter configuration: According to the actual application requirements, precisely set the output range and data format of the module. 

Different analogue devices have different requirements for input signals, and the correct choice of output range 

and data format can ensure the compatibility of the module with the device and improve the output accuracy. 

For devices requiring 0 - 10V voltage input, setting the output range of the 1771-OFE1 module to 0 - 10V and selecting the appropriate data 

format (e.g., binary or BCD) can match the output of the module with the requirements of the device, 

avoiding data conversion errors caused by incompatible formats. 


Reasonable use of the scaling function to convert data to actual engineering units can improve the readability and practicality of the data. 

When setting the scaling parameters, it should be ensured that the maximum scaling value is greater than the minimum scaling value, 

and the format of all the scaling information is consistent with the format of the module sent to the data table. 

For an application that measures temperature and converts it to voltage output, the temperature value can be accurately converted to 

the corresponding voltage signal output by precisely setting the scaling parameters, which is convenient for subsequent monitoring and control.

Improved programming strategy: Depending on the type of processor, choose the appropriate programming method and strictly follow 

the programming specifications. When using PLC - 2, PLC - 3, PLC - 5 and other processors, pay attention to the use of block transfer instructions 

and restrictions, avoid enabling the enable bit of read/write instructions at the same time to prevent data transfer errors. 

For the PLC-2 processor, programs should be written according to its specific programming structure to ensure correct data transfer and processing. 


Optimise the settings for block length and scaling by determining whether to scale all channels and how to set the scaling values according to 

the actual situation. In some applications, only some channels may need to be scaled, in which case the block length 

and scaling parameters should be set appropriately to improve data processing efficiency. 

If only two channels are scaled, the appropriate block length can be set and the scaling value can be entered accurately 

to avoid unnecessary calculations and data transfers and to improve the system operation efficiency .

Regular calibration and maintenance: Regular calibration of the module ensures the accuracy of its output. 

The calibration process includes preparatory work (e.g. switching off the power, connecting the test equipment, etc.) 

and calibration operations for each channel. 

For the voltage output version of the module, the output voltage is calibrated by adjusting the potentiometer; for the current output version of the module, 

the corresponding current calibration operation is also required. 


Regular calibration can detect and correct possible deviations of the module in time to ensure its long-term stable operation. 

Pay close attention to the running status of the module, through the indicator lights and diagnostic bits to timely detect faults and take appropriate measures. 

When the red FAULT indicator lights up, the connection, configuration and hardware status of the module should be checked according to the fault prompts, a

nd the faulty parts should be replaced in time to ensure that the module works normally. 

If the output of a channel is found to be abnormal, the cause of the fault can be determined by reading the diagnostic bit information, 

such as whether the data is out of range, whether the scaling is correct, etc., and then carry out targeted repair.

Allen Bradley 1771-OFE2 Ser. B Analog Output Module, 7.9 W

  • Metso A413177 Digital Interface Control Module
  • METSO A413222 8-Channel Isolated Temperature Input Module
  • Metso A413313 Interface Control Module
  • METSO D100532 Control System Module
  • METSO A413310 8-Channel Digital Output Module
  • METSO A413659 Automation Control Module
  • Metso D100314 Process Control Interface Module
  • METSO A413665 8-Channel Analog Output Module
  • METSO A413654 Automation Control Module
  • Metso A413325 Interface Control Module
  • METSO A413110 8-Channel Analog Input Module
  • METSO A413144 Automation Control Module
  • Metso A413160 Digital Interface Control Module
  • METSO A413152 8-Channel Digital Input Module
  • METSO A413240A Automation Control Module
  • METSO A413146 Digital Interface Control Module
  • METSO A413150 Multi-Role Industrial Automation Module
  • METSO A413125 Automation Control / I/O Module
  • Metso A413111 Interface Control Module
  • METSO A413140 Automation Control Module
  • METSO 020A0082 Pneumatic Control Valve Component
  • METSO 02VA0093 Automation Control Module
  • METSO 02VA0153 Actuator Control Module
  • METSO 02VA0190 Automation Control Module
  • Metso 02VA0193 Pneumatic Control Valve Component
  • METSO 02VA0175 Valve Actuator Module
  • METSO D100308 Industrial Control Module
  • MOOG QAIO2/2-AV D137-001-011 Analog Input/Output Module
  • MOOG D136-002-002 Servo Drive or Control Module
  • MOOG D136-002-005 Servo Drive Control Module
  • MOOG D136E001-001 Servo Control Card Module
  • MOOG M128-010-A001B Servo Control Module Variant
  • MOOG G123-825-001 Servo Control Module
  • MOOG D136-001-008a Servo Control Card Module
  • MOOG M128-010 Servo Control Module
  • MOOG T161-902A-00-B4-2-2A Servo-Proportional Control Module
  • MOTOROLA 21255-1 Electronic Component Module
  • MOTOROLA 12967-1 / 13000C Component Assembly
  • MOTOROLA 01-W3914B Industrial Control Module
  • Motorola MVME2604-4351 PowerPC VMEbus Single Board Computer
  • MOTOROLA MVME162-513A VMEbus Embedded Computer Board
  • MOTOROLA MPC2004 Embedded PowerPC Processor
  • Motorola MVME6100 VMEbus Single Board Computer
  • MOTOROLA MVME162PA-344E VMEbus Embedded Computer Board
  • MOTOROLA RSG2PMC RSG2PMCF-NK2 PMC Expansion Module
  • Motorola APM-420A Analog Power Monitoring Module
  • MOTOROLA 0188679 0190530 Component Pair
  • Motorola 188987-008R 188987-008R001 Power Control Module
  • MOTOROLA DB1-1 DB1-FALCON Control Interface Module
  • MOTOROLA AET-3047 Antenna Module
  • Motorola MVME2604761 PowerPC VMEbus Single Board Computer
  • MOTOROLA MVME761-001 VMEbus Single Board Computer
  • MOTOROLA 84-W8865B01B Electronic System Module
  • Motorola MVIP301 Digital Telephony Interface Module
  • MOTOROLA 84-W8973B01A Industrial Control Module
  • MOTOROLA MVME2431 VMEbus Embedded Computer Board
  • MOTOROLA MVME172PA-652SE VMEbus Single Board Computer
  • Motorola MVME162-223 VMEbus Single Board Computer
  • MOTOROLA BOARD 466023 Electronic Circuit Board
  • Motorola MVME333-2 6-Channel Serial Communication Controller
  • MOTOROLA 01-W3324F Industrial Control Module
  • MOTOROLA MVME335 VMEbus Embedded Computer Board
  • Motorola MVME147SRF VMEbus Single Board Computer
  • MOTOROLA MVME705B VMEbus Single Board Computer
  • MOTOROLA MVME712A/AM VMEbus Embedded Computer Board
  • MOTOROLA MVME715P VMEbus Single Board Computer
  • Motorola MVME172-533 VMEbus Single Board Computer
  • Motorola TMCP700 W33378F Control Processor Module
  • MOTOROLA MVME188A VMEbus Embedded Computer Board
  • Motorola MVME712/M VME Transition Module
  • Motorola 30-W2960B01A Industrial Processor Control Module
  • MOTOROLA FAB 0340-1049 Electronic Module
  • Motorola MVME162-210 VME Single Board Computer
  • Motorola MVME300 VMEbus GPIB IEEE-488 Interface Controller
  • MOTOROLA CPCI-6020TM CompactPCI Processor Board
  • Motorola MVME162-522A VMEbus Single Board Computer
  • MOTOROLA MVME162-512A VMEbus Single Board Computer
  • MOTOROLA MVME162-522A 01-W3960B/61C VMEbus Single Board Computer
  • MOTOROLA MVME162-220 VMEbus Embedded Computer Board
  • Motorola MVME162-13 VMEbus Single Board Computer
  • MOTOROLA MVME162-10 VMEbus Single Board Computer
  • RELIANCE 57C330C AutoMax Network Interface Module
  • RELIANCE 6MDBN-012102 Drive System Module
  • RELIANCE 0-60067-1 Industrial Drive Control Module
  • Reliance Electric 0-60067-A AutoMax Communication Module
  • RELIANCE S0-60065 System Control Module
  • RELIANCE S-D4006-F Industrial Drive Control Module
  • Reliance Electric S-D4011-E Shark I/O Analog Input Module
  • RELIANCE S-D4009-D Drive Control Module
  • RELIANCE S-D4043 Drive Control Module
  • Reliance DSA-MTR60D Digital Servo Motor Interface Module
  • RELIANCE 0-60063-2 Industrial Drive Control Module
  • RELIANCE S-D4041 Industrial Control Module
  • Reliance Electric SR3000 2SR40700 Power Module
  • RELIANCE VZ7000 UVZ701E Variable Frequency Drive Module
  • RELIANCE VZ3000G UVZC3455G Drive System Module
  • Reliance Electric S-D4039 Remote I/O Head Module
  • RELIANCE 0-57210-31 Industrial Drive Control Module
  • RELIANCE 0-56942-1-CA Control System Module
  • Reliance Electric 0-57100 AutoMax Power Supply Module
  • RELIANCE 0-54341-21 Industrial Control Module
  • RELIANCE 0-52712 800756-21B Drive Interface Board
  • KEBA PS242 - Power Supply Module
  • KEBA BL460A - Bus Coupling Module
  • KEBA K2-400 OF457/A Operating Panel
  • KEBA T200-M0A-Z20S7 Panel PC
  • KEBA K2-700 AMT9535 Touch Screen Panel
  • KEBA T20e-r00-Am0-C Handheld Terminal
  • KEBA OP350-LD/J-600 Operating Panel
  • KEBA 3HAC028357-001 DSQC 679 IRC5 Teach Pendant
  • KEBA E-32-KIGIN Digital Input Card
  • KEBA FP005 Front Panel
  • KEBA BT081 2064A-0 Module
  • KEBA FP-005-LC / FP-004-LC Front Panel
  • KEBA SI232 Serial Interface
  • KEBA T70-M00-AA0-LE KeTop Teach Pendant
  • KEBA KEMRO-BUS-8 Bus Module
  • KEBA IT-10095 Interface Terminal
  • KEBA RFG-150AWT Power Supply Unit
  • KEBA C55-200-BU0-W Control Unit
  • KEBA Tt100-MV1 Temperature Module
  • KEBA E-HSI-RS232 D1714C / D1714B Interface Module
  • KEBA E-HSI-CL D1713D Interface Module
  • KEBA D1321F-1 Input Module
  • KEBA E-32-D Digital Input Card
  • KEBA C5 DM570 Digital Module
  • KEBA XE020 71088 Module
  • KEBA E-16-DIGOUT Digital Output Card