Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

AB 1771-OFE Series B Analogue Output Modules

来源: | 作者:FAN | 发布时间 :2025-04-21 | 842 次浏览: | 🔊 Click to read aloud ❚❚ | Share:

AB 1771-OFE Series B Analogue Output Modules

Module Overview:

Functionality: The 1771- OFE is an intelligent block transfer module that converts binary or quadruple BCD values supplied 

by the processor into analogue signal outputs. It has four independently isolated differential output channels with selectable scaling, data format, etc. 

It requires no external power supply and occupies only one I/O slot.


Output range: There are three versions, 1771-OFE1 is a voltage output, 1 - 5V dc, 0 - 10V dc, +10V dc can be selected through the configuration jumper; 

1771-OFE2 and 1771-OFE3 are current outputs, 4 - 20mA and 0 - 50mA respectively, and the latter two are factory-set.

Communication mode: The processor transmits data to and from the module through the BTW and 

BTR instructions in the ladder program to send output values, set modes and receive status information.


Installation steps:

Preparation for installation: Comply with the relevant EU directives, calculate the power requirement before installation 

to avoid overloading the backplane and power supply of the I/O chassis.

Module Setup: Can be installed in any slot of the I/O chassis, but avoid grouping with discrete high-density modules, 

and keep away from AC or high-voltage DC modules. Set configuration jumpers, including the 

last state configuration jumper (determines the output state in the event of a communication failure) and the voltage range configuration jumper (for 1771-OFE1)

Installation and Connections: Install the keying strip, insert the module smoothly into the chassis and secure it, and connect the 1771-WH junction arm; 

use the 1771-WC junction arm to connect to analogue equipment with the sensor cable shielded and grounded at the chassis end only.


The module is configured:

Configuration: Configure the module using a Block Transfer Write command (BTW) with a 13-word maximum 

write block containing output data, data format, and scaling information.

Data format and scaling: data format can be BCD or binary, scaling function can convert data to engineering units, 

by setting the corresponding scaling value, the maximum scaling value is 9999, the minimum is - 9999, and the maximum must be greater than the minimum.

Default Configuration: At power-on, the module microprocessor defaults to positive data words, no scaling, and BCD data format.


Programming Points:

Programming Format: The programming format is different for different processors, PLC-2, PLC-3, PLC-5 have their own characteristics, 

and the module does not allow the enable bit of the read/write instruction to be set to ON at the same time.

Programming Considerations: Including block length and scaling considerations (e.g., different settings for no-channel scaling, partial-channel scaling, 

and full-channel scaling), block transfer boundary words (PLC-2 processor), 

and module update time (8 milliseconds for BCD and scaling, and 1.6 milliseconds for binary and no scaling).


Performance

Optimisation of hardware mounting and layout: Choose the location of the modules in the I/O chassis appropriately, 

avoiding the grouping of discrete high-density modules, and keeping them away from AC or high-voltage DC modules in order 

to reduce electromagnetic interference. 

Modules that are too close to these sources of interference may result in unstable signal transmission and affect the accuracy of 

the analogue output. Installing the module in a location away from the source of interference with 

good shielding and grounding can effectively reduce the impact of electromagnetic interference 

on the performance of the module and improve the quality of signal transmission . 

Ensure that the sensor cable is properly connected and well shielded, and the cable shield is grounded only at the chassis end to reduce noise interference. 

If the shield is not properly grounded or shielded cable is not used, external noise may be coupled into the signal line, 

resulting in fluctuations or errors in the output signal. 


The use of high quality shielded cables, such as Belden 8761, and grounding in strict accordance with the specifications, 

can enhance the module's anti-interference ability and ensure the stability of the output signal.

Fine adjustment of parameter configuration: According to the actual application requirements, precisely set the output range and data format of the module. 

Different analogue devices have different requirements for input signals, and the correct choice of output range 

and data format can ensure the compatibility of the module with the device and improve the output accuracy. 

For devices requiring 0 - 10V voltage input, setting the output range of the 1771-OFE1 module to 0 - 10V and selecting the appropriate data 

format (e.g., binary or BCD) can match the output of the module with the requirements of the device, 

avoiding data conversion errors caused by incompatible formats. 


Reasonable use of the scaling function to convert data to actual engineering units can improve the readability and practicality of the data. 

When setting the scaling parameters, it should be ensured that the maximum scaling value is greater than the minimum scaling value, 

and the format of all the scaling information is consistent with the format of the module sent to the data table. 

For an application that measures temperature and converts it to voltage output, the temperature value can be accurately converted to 

the corresponding voltage signal output by precisely setting the scaling parameters, which is convenient for subsequent monitoring and control.

Improved programming strategy: Depending on the type of processor, choose the appropriate programming method and strictly follow 

the programming specifications. When using PLC - 2, PLC - 3, PLC - 5 and other processors, pay attention to the use of block transfer instructions 

and restrictions, avoid enabling the enable bit of read/write instructions at the same time to prevent data transfer errors. 

For the PLC-2 processor, programs should be written according to its specific programming structure to ensure correct data transfer and processing. 


Optimise the settings for block length and scaling by determining whether to scale all channels and how to set the scaling values according to 

the actual situation. In some applications, only some channels may need to be scaled, in which case the block length 

and scaling parameters should be set appropriately to improve data processing efficiency. 

If only two channels are scaled, the appropriate block length can be set and the scaling value can be entered accurately 

to avoid unnecessary calculations and data transfers and to improve the system operation efficiency .

Regular calibration and maintenance: Regular calibration of the module ensures the accuracy of its output. 

The calibration process includes preparatory work (e.g. switching off the power, connecting the test equipment, etc.) 

and calibration operations for each channel. 

For the voltage output version of the module, the output voltage is calibrated by adjusting the potentiometer; for the current output version of the module, 

the corresponding current calibration operation is also required. 


Regular calibration can detect and correct possible deviations of the module in time to ensure its long-term stable operation. 

Pay close attention to the running status of the module, through the indicator lights and diagnostic bits to timely detect faults and take appropriate measures. 

When the red FAULT indicator lights up, the connection, configuration and hardware status of the module should be checked according to the fault prompts, a

nd the faulty parts should be replaced in time to ensure that the module works normally. 

If the output of a channel is found to be abnormal, the cause of the fault can be determined by reading the diagnostic bit information, 

such as whether the data is out of range, whether the scaling is correct, etc., and then carry out targeted repair.

Allen Bradley 1771-OFE2 Ser. B Analog Output Module, 7.9 W

  • Siemens Ams-M35-K202 C8451-A20-A53-7
  • Omron FH-2050 Automation Controller
  • Omron CJ1W-NCF71 Position Control Unit
  • PILZ 777750 Safety Relay
  • BES58-P0CA0P-CD0H3PB0 Encoder 85409
  • Siemens 3VL5763-1DC36-0AA0 Molded Case Breaker
  • FANUC A16B-3200-0010 CPU Card
  • HINE DESIGN R94-1164 PLC Control Box 144760
  • Siemens PCU 50.5-C 6FC5210-0DF52-2AA0
  • PILZ PNOZ M0P Safety Relay 773110
  • Fanuc A20B-2101-0820 Control Circuit Board
  • Siemens 3SK1121-1AB40 Safety Relay
  • Pilz 772120 Safety Relay Expansion Module
  • Mitsubishi AX71 Input Module 16 Point
  • Siemens 6ES7350-1AH03-0AE0 S7-300 Extension
  • Fanuc A16B-3200-0010 CPU Card
  • Omron CJ1W-SCW22 Serial Communication Unit
  • Siemens 6SN1118-0DM21-0AA0 Control Module
  • Renishaw PHC10-3PLUS Controller Module
  • ABB AX521 1SAP250100R0001 Module
  • Omron NA5-9W001B-V1 PLC Module HMI
  • Infineon FF1000R17IE4 IGBT Power Module
  • Omron CJ1W-DA08C Analog Output Module
  • Omron CJ1G CPU45H CJ1H CPU66H CJ1G CPU43H CJ1W PA202
  • Omron CJ1W-DA041 Analog Output Module
  • Inductotherm 170-8031 PLC Control Module
  • Fuji Electric FPB56HR-A10 Programmable Logic Controller
  • Siemens 6SN1145-1BA01-0BA1 Infeed Regenerative Module
  • PILZ 777949 PSWZ X1P Safety Relay
  • Schneider 140NOM25200 DIO Head-end Adaptor
  • Siemens PXC5.E003 Controller BPZ
  • Schneider BMXEHC0800 Fast Counting Module 10kHz
  • Schneider BMXART0814 Isolated Thermocouple Inputs
  • Schneider BMXNOE0100 Ethernet Module 10 100 RJ45
  • LMX06-NS05 Sensor Industrial Proximity Switch
  • Siemens 6SN1145-1BB00-0FA1 Power Supply 156kW
  • Pro-face GP2500-LG41-24V HMI Graphic Panel
  • Keyence CV-3001 Vision System CV3OO1
  • Siemens 6GK5204-2BB10-2AA3 Ethernet Module
  • Pro-face PFXSP5500TPD 10.4in HMI LCD Display
  • Eu Automation 140DRA84000 Modicon Quantum Module
  • Siemens 6FC5210-0DF31-2AA0 Sinumerik PCU 50.3-C
  • Siemens 6SL3040-1NC00-0AA0 Sinumerik NX10.3 Extension
  • Gould AS-884A-111 Modicon 884 Controller
  • Allen Bradley 1336E-BRF30-AA-EN-HA2-L5 Impact Drive
  • Siemens 6FC5110-0BB02-0AA1 Sinumerik 840D CPU Card
  • Pilz 773500 PNOZmulti Expansion Module
  • Siemens 6ES7350-1AH03-0AE0 S7-300 Counter Module
  • Siemens 6FC5110-0DB01-0AA1 Sinumerik 840D Card
  • HPM 1D703-0040 Command 9000 VGA Console Board
  • OMRON CJ1W-PTS52 Temperature Unit
  • Sacs Technique PCD4.M12 Module
  • OMRON CJ1M-CPU11-ETN Ethernet CPU
  • OMRON CJ1M-CPU23 PLC CPU Unit
  • OMRON NX-SID800 Safety Input Unit
  • GE Fanuc Series 90-30 PLC
  • OMRON CJ1W-NCF71 Position Control
  • OMRON CJ1W-AD081-V1 Analog Input
  • OMRON FZ-S2M Vision Camera
  • OMRON R88D-UEP20V Servo Driver
  • OMRON F500-C10-ETN Vision Controller
  • OMRON CS1W-DA041 Analog Output Module
  • PRO-FACE GP577R-TC41-24VP HMI Panel
  • TRUTZSCHLER RAK 1 492-58.430.000 PLC Module
  • OMRON NX-OD5256 Output Module
  • Siemens 6AG1214-1AG40-4XB0 PLC
  • OMRON CJ1W-AD081-V1 Analog Unit
  • OMRON C500-CPU11-E PLC CPU
  • OMRON NX-ECC201 EtherCAT Coupler
  • OMRON F300-A20S Camera Interface
  • Mitsubishi 80173-109-01 PLC Module
  • Fanuc A16B-2200-0141 PCB Board
  • Lenze EPL10200 PLC Module
  • OMRON CJ1M-CPU13 PLC CPU Unit
  • Yaskawa SGMPH-04AAA61D-OY Motor
  • OMRON NX-SOD400 Safety Output
  • Control Techniques V1800 Flux Vector Drive
  • Yaskawa SGDH-04AE-OY Servo Drive
  • OMRON NT-DRT21 DeviceNet Interface
  • OMRON C500-RM001-V1 Remote I/O Master
  • OMRON C500-AD006 Analog Input Module
  • OMRON 3G3MV-A4055 Inverter Drive
  • OMRON F150-C15E-3 Vision Mate Controller
  • OMRON CS1G-CPU44H PLC CPU
  • GE Fanuc DS6800CCIE1E1D CPU Module
  • Omron CP1L-M30DR-A PLC CP1W-CIF01 CPU Unit
  • Heraeus 585923 2M130 M8 Electrode Assembly Sensor
  • Omron C40P-EDT1-D C Series PLC Controller
  • Yaskawa SGMGH-09DCA6F-OY Servo Motor SGDH Driver
  • Datalogic SG-BWS-T4-MT Safety Control Unit Category 4
  • Pro-face PFXLM4301TADDC HMI Controller LT-4301M
  • Mitsubishi FX1N-60MR-DS PLC Main Unit 60 I/O
  • Omron NJ501-1320 Sysmac Database Connection CPU
  • Omron CJ1W-ETN21 Ethernet Unit CJ Series Module
  • Siemens 6ES7517-3AP00-0AB0 CPU 1517-3 PN/DP
  • Pasaban MTC-3052 Fast I/O PLC Module
  • Mitsubishi FX3U-128MR/ES-A PLC
  • OMRON CS1W-CLK21 Controller Link Unit
  • Yokogawa ADV151-E63 Digital Input Module
  • Allen Bradley MPL-B680B-M-X227 Motor
  • OMRON CJ1W-NC413 4-Axis Position Unit
  • Yaskawa SGMGH-30DCA6H-OY Servo Motor
  • Bosch 1070075337-101 Output Card
  • OMRON CQM1-CPU45-EV1 PLC CPU Unit
  • Siemens 6SE7090-0XX84-0AG1 CU3 Control Module
  • OMRON CQM1-TC101 Temperature Control Module
  • MOOG OEM-1030-422 Wind Energy PLC Controller
  • OMRON ZFX-C15 Vision Sensor
  • Square D 8702SCO2V02 Reversing Contactor
  • OMRON C20-LK201-EV1 PLC Link Adapter
  • OMRON NB7W-TW01B HMI PLC
  • Siemens 7ME6920-1AA10-1AA0 Flow Transmitter
  • Allen Bradley 1791-8BR Block I/O Module
  • OMRON CQM1-AD041 Analog Input Module
  • OMRON CJ1M-CPU21 PLC Module
  • Omron Z500-MC10E-001 Laser Profile Controller
  • Omron NA5-7W001B-V1 NA Series Programmable Terminal HMI
  • Allen-Bradley 1606-XLS960EE Power Supply 960W 24VDC
  • GE DS3800NEPB1F1E Power Excitation Board Mark IV
  • Yaskawa SGDH-04AE-OY Sigma-II Servo Drive 400W
  • Allen-Bradley 2711P-RBT7 PanelView Plus 7 Bezel
  • CCS PD3-3024-3-EI Digital Control Unit 3 Channel
  • Yaskawa CPU301 MP3300 Controller JAPMC-CP3301-2-E
  • Omron C40P-EDR-D PLC C Series P Type Controller
  • Omron NX-SID800 Safety Input Unit 8 PNP 24VDC
  • ABB SCC-C 23070-0-10232110 gas cooler
  • Sick LGTN101-521 CPU Module
  • Okuma 1911-2836 PLC Circuit Board