Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Effective ways to improve safety instruments in petrochemical industry

来源: | 作者:佚名 | 发布时间 :2023-11-24 | 178 次浏览: | Share:

1. Effective improvement of petrochemical safety instruments

In order to ensure the integrity of instrument system performance of equipment in petrochemical production, a comprehensive analysis is carried out on it. Through the analysis results, it is known that there are problems in safety instrument system that are not conducive to system integrity. The problems and optimization measures are analyzed in detail as follows:

1.1 Scientific design of sensor redundancy

As far as redundant configuration is concerned, it plays an important role in instrument systems and is also the main content of system design. However, not all sensors are suitable for the design of redundant configuration [1]. SIL is regarded as the main probability requirement of sensor failure, if the sensor in the safety instrument system meets this requirement, it is necessary for relevant personnel to select the integrated sensor, so as to make the safety instrument system meet the design requirements. When the sensor does not meet the requirements of SIL, the use of redundant sensors should be strengthened. However, in the application of redundant sensors, designers need to fully consider the safety of the system, while strengthening the interlocking action and frequency as the basis for rational use of the logical structure, not only to comprehensively consider the applicability of the system, but also to ensure that the instrument system has reliable security, so in practice, A two-out-of-three structure in a logical structure should be used appropriately.

1.2 Carry out a comprehensive design of the safety instrument system

SIL is the main requirement for the safety and integrity of the function of the instrument system. However, the function of the safety instrument system is not determined by one device, but by several devices during operation, which mainly include: sensors, actuators and logic controllers. At the same time, there is a corresponding relationship between each instrument, the SIL between the three and the SIL of the logical sensing has an important relationship, at this time, the relevant staff should pay more attention to, especially the failure rate of the relevant instrument, which has a certain corresponding relationship with the level of SIL. For example, in the analysis of the relevant logical control, if the control unit has a SIL level of 3, the real efficiency of the controller will be less than 0.1%, and in the case of the sensor, when its SIL level is 2, the failure rate will be less than 1%. At the same time, the corresponding execution system is analyzed, and the structure is a level 1 SIL, and the failure rate of the execution structure will be less than 10% [2]. However, in practical applications, the reliability of safety instrument system operation will be directly affected by the logic controller. In addition, according to the investigation in the production process of petrochemical enterprises, many staff are too dependent on the reliability of the logic controller, which is also the main problem in the actual production process. Due to the greater emphasis on it, they ignore the importance of the actuator. If they do not pay more attention to the failure rate level of the actuator, it will lead to problems in the function of the entire safety instrument system. It can even make the safety of the instrument lose its function. Therefore, in the design of safety instrument system, relevant designers need to analyze from an objective point of view, pay attention to the comprehensive design of the system, ensure that various instruments can meet the standard of failure rate level in the design process, provide guarantee for the improvement of the safety level of the system, and make its safety performance meet the safety level standard.

1.3 Performing Integration Configurations

In the actual design process, there will be more failure rate problems, so relevant personnel need to fully study the failure rate level of each instrument in the process of system design, and analyze the failure rate level of the whole system through the parallel relationship. For example, when the failure rate of the logic controller is level 3, which meets the specific requirements of the system, in the actual design process, the designer also controls the actual failure rate at level 3, while the failure rate of the sensor and the actuator are respectively controlled at level 2, then the failure rate of the whole system is also level 2 through calculation and analysis. In this case, according to the specific requirements of the safety instrument system, if the failure rate of the whole system is level 2, the standard of the system cannot be met. If this happens, the relevant designer should take appropriate measures to deal with it, usually using redundant configuration to improve the sensor. For example, in the application of redundant configuration, according to the characteristics of the sensor failure rate to choose the appropriate way to configure, through the analysis of the above content, the use of two-to-one redundancy method, can make the safety level of the system to be improved. At the same time, in the process of redundant configuration, the designer can also configure the actuator and solenoid valve at the same time, which should be scientifically and reasonably configured according to the characteristics of the two, so that the safety level of the entire system has been effectively improved, so that it reaches the standard of SIL3, in order to promote the safety of the system to meet the specific requirements of the staff in the production operation. Because different situations in the instrument system have different requirements for the actuator, and there are certain differences in the type and function of the actuator, different actuators have different redundant configuration methods, requirements and standards in the actual design process. For example, in the process of system design, the main performance of the actuator is to cut the interlock, and at this time, the two actuators in the system are connected in series and applied, which can effectively improve the SIL. Therefore, in the design process, the designer should make a detailed analysis according to the actual situation of the system, based on this, the selection of the actuator, and according to the functional characteristics of the actuator reasonable redundancy configuration, only in this way, can promote the improvement of the SIL level.

1.4 Strengthen the corresponding management work

Although oil care enterprises have high requirements for instrument systems, and the state also has certain standard requirements for it, according to the actual application analysis of instrument systems, it is found that there are certain problems in the safety protection work of the system, actual operation and construction, or the cognition of risks in production, and it cannot meet people's requirements. For example, in the actual design of safety instrument system, during the design process, no scientific method is adopted in the calculation and estimation of SIF, which will cause problems in redundancy configuration. The main problems are reflected in fault tolerance. In this process, the guidance of design drawings and schemes is ignored only for the completion of the design, resulting in deviations and other situations in the construction. In this case, the safety performance of the instrument system will decline. Therefore, in order to ensure the stability, safety and reliability of the instrument system during operation, relevant managers should conduct comprehensive management of the instrument system, and formulate corresponding management plans for the implementation of management work. This ensures that the safety of the instrument safety system during operation can meet the requirements of the staff.

2 Safety instrument reliability fault-tolerant design

As far as the design of instrument system is concerned, if the petrochemical system is designed, the designer should protect the instrument tested by the instrument in advance, conduct a comprehensive analysis of the process behavior involved in the operation of the instrument, evaluate the overall safety, and make a detailed division of the safety instrument system according to the evaluation content [3]. In addition, if an instrument system with a low safety level is found in the process of analysis and evaluation, the design of the instrument system should be integrated into DCS at this time, so as to reasonably control the design cost of the system. In addition, for the loop with high failure rate, its application in production not only has a greater threat, but also has a direct impact on the production order. Therefore, the safety instrument system should be designed for the loop to realize the control of the safety performance of the loop and reflect the specific function of the loop. This provides guarantee for the safety and reliability of production.




  • FOXBORO P0926KK PLC system functional module
  • FOXBORO P0924AW wireless pressure transmitter
  • FOXBORO P0916NK differential pressure transmission cable
  • FOXBORO P0916JQ PLC module
  • FOXBORO P0916JP I/A series control module
  • FOXBORO P0916GG Digital Input Module
  • FOXBORO P0916DV I/A series digital input module
  • FOXBORO P0916DC Terminal Cable
  • FOXBORO P0916DB I/A series PLC module
  • FOXBORO P0914ZM recognition module
  • FOXBORO P0902YU control module
  • FOXBORO P0901XT Process Control Unit
  • FOXBORO P0800DV fieldbus extension cable
  • FOXBORO P0800DG Standard Communication Protocol Module
  • FOXBORO P0800DB Universal I/O Module
  • FOXBORO P0800DA Industrial Control Module
  • FOXBORO P0800CE control module
  • FOXBORO P0700TT Embedded System
  • FOXBORO P0500WX Control System Module
  • FOXBORO P0500RY Terminal Cable Assembly
  • FOXBORO P0500RU control module
  • FOXBORO P0500RG Terminal Cable
  • FOXBORO P0400ZG Node Bus NBI Interface Module
  • FOXBORO P0400GH fieldbus power module
  • FOXBORO FBM207B Voltage Monitoring/Contact Induction Input Module
  • FOXBORO FBM205 Input/Output Interface Module
  • FOXBORO FBM18 Industrial Controller Module
  • FOXBORO FBM12 Input/Output Module
  • FOXBORO FBM10 Modular Control System
  • FOXBORO FBM07 Analog/Digital Interface Module
  • FOXBORO FBM05 redundant analog input module
  • FOXBORO FBM02 thermocouple/MV input module
  • FOXBORO FBI10E fieldbus isolator
  • FOXBORO DNBT P0971WV Dual Node Bus Module
  • FOXBORO CP30 Control Processor
  • FOXBORO CM902WX Communication Processor
  • FOXBORO AD202MW Analog Output Module
  • FOXBORO 14A-FR Configuration and Process Integration Module
  • FOXOBORO 130K-N4-LLPF Controller
  • FUJI FVR004G5B-2 Variable Frequency Drive
  • FUJI FVR008E7S-2 High Efficiency Industrial Inverter
  • FUJI FVR008E7S-2UX AC driver module
  • FUJI RPXD2150-1T Voltage Regulator
  • FUJI NP1PU-048E Programmable Logic Control Module
  • FUJI NP1S-22 power module
  • FUJI NP1AYH4I-MR PLC module/rack
  • FUJI NP1BS-06/08 Programmable Controller
  • FUJI NP1X3206-A Digital Input Module
  • FUJI NP1Y16R-08 Digital Output Module
  • FUJI NP1Y32T09P1 high-speed output module
  • FUJI NP1BS-08 Base Plate​
  • FUJI A50L-2001-0232 power module
  • FUJI A50L-001-0266 # N Programmable Logic Control Module
  • GE GALIL DMC9940 Advanced Motion Controller
  • GE DMC-9940 Industrial Motion Control Card
  • GE IS200AEADH4A 109W3660P001 Input Terminal Board
  • GE IC660HHM501 Portable Genius I/O Diagnostic Display
  • GE VMIVME 4140-000 Analog Output Board
  • GE VMIVME 2540-300 Intelligent Counter
  • GE F650NFLF2G5HIP6E repeater
  • GE QPJ-SBR-201 Circuit Breaker Module
  • GE IC200CHS022E Compact I/O Carrier Module
  • GE IC695PSD140A Input Power Module
  • GE IC695CHS016-CA Backboard
  • GE IC800SS1228R02-CE Motor Controller
  • GE IS215WEMAH1A Input/Output Communication Terminal Board
  • GE CK12BE300 24-28V AC/DC Contactor
  • GE CK11CE300 contactor
  • GE DS3800NB1F1B1A Control Module
  • GE VMIVME2540 Intelligent Counter
  • GE 369B1859G0022 High Performance Turbine Control Module
  • GE VME7865RC V7865-23003 350-930007865-230003 M AC contactor
  • GE SR489-P5-H1-A20 Protection Relay
  • GE IS200AEPGG1AAA Drive Control Module
  • GE IS215UCCCM04A Compact PCI Controller Board
  • GE VME7768-320000 Single Board Computer
  • GE SR489-P5-LO-A1 Generator Protection Relay
  • GE IS215WETAH1BB IS200WETAH1AGC Input/Output Interface Module
  • GE D20 EME210BASE-T Ethernet Module
  • GE IS200EXHSG3REC high-speed synchronous input module
  • GE IS200ECTBG1ADE exciter contact terminal board
  • GE VPROH2B IS215VPROH2BC turbine protection board
  • GE F650BFBF2G0HIE feeder protection relay
  • GE SLN042 IC086SLN042-A port unmanaged switch
  • GE SR489-P1-HI-A20-E Generator Management Relay
  • GE IS400JPDHG1ABB IS410JPDHG1A track module
  • GE IS410STAIS2A IS400STAIS2AED Industrial Control Module
  • GE IS410STCIS2A IS400STCIS2AFF Industrial Control Module
  • GE DS200DCFBG2BNC DS200DCFBG1BNC DC Feedback Board
  • GE VME5565 VMIVME-5565-11000 332-015565-110000 P Reflective Memory
  • GE VMIVME-7807 VMIVMME-01787-414001 350-00010078007-414001 D module
  • GE IS220PDOAH1A 336A4940CSP2 Discrete Output Module
  • GE VMIVME-4150 Analog Output Module
  • GE WESDAC D20 PS Industrial Power Module
  • GE 369B1860G0031 servo drive module
  • GE 369B1859G0021 Input/Output Module
  • GE 208D9845P0008 Motor Management Relay
  • GE IS420UCSCH1A-F.V0.1-A Independent Turbine Controller
  • GE D20EME10BASE-T 820-0474 Ethernet Interface Module
  • GE DS200DCFBG2BNC MRP445970 DC Feedback Board
  • GE IC800SSI228RD2-EE servo motor controller
  • GE IS200JPDMG1ACC S1AT005 Digital Input/Output (I/O) Module
  • GE IS200TSVCH1AED servo input/output terminal board
  • GE IS200TTURH1CCC S1DF00Z Terminal Turbine Plate
  • GE IS200TSVCH1ADC S1CX01H servo input-output board
  • GE IS200TRPGH1BDD S1C5029 Trip Solenoid Valve Control Board
  • GE IS220YAICS1A L Analog Input/Output Module
  • GE UCSC H1 IS420UCSCH1A-F-VO.1-A Controller Module
  • GE UCSC H1 IS420UCSCH1A-B Communication Processing Module
  • GE IC697VDD100 Digital Input Module
  • GE V7768-320000 3509301007768-320000A0 Controller Module
  • GE IS410TRLYS1B Relay Output Module
  • GE IS415UCVGH1A V7666-111000 VME Control Card
  • GE IC800SSI216RD2-CE servo motor controller
  • GE VMIVME-5565-010000 332-01565-010000P Reflective Memory
  • GE IC695ALG508-AA Analog Input Module
  • GE IC660EPM100J Power Monitoring and Control Module
  • GE RS-FS-9001 362A1052P004 Redundant Fan System Module
  • GE IS220UCSAH1AK independent processor module
  • GE 369-HI-0-M-0-0-0-E Motor Management Relay
  • GE CIFX50-C0 interface board
  • GE SR469-P5-H-A20-T Motor Management Relay
  • GE WES5120 2340-21005 power module
  • GE WES5120 2340-21003 Control Module
  • GE D20MIC10BASE-T 820-0756 Ethernet Module
  • GE WES13-3 5167-001-0210 Mechanical Relay Output Module
  • GE WES13-3 2508-21001 Control Board Module
  • GE D20ME 526-2005-216943 Input/Output Module