Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Effective ways to improve safety instruments in petrochemical industry

F: | Au:佚名 | DA:2023-11-24 | 296 Br: | 🔊 点击朗读正文 ❚❚ | Share:

1. Effective improvement of petrochemical safety instruments

In order to ensure the integrity of instrument system performance of equipment in petrochemical production, a comprehensive analysis is carried out on it. Through the analysis results, it is known that there are problems in safety instrument system that are not conducive to system integrity. The problems and optimization measures are analyzed in detail as follows:

1.1 Scientific design of sensor redundancy

As far as redundant configuration is concerned, it plays an important role in instrument systems and is also the main content of system design. However, not all sensors are suitable for the design of redundant configuration [1]. SIL is regarded as the main probability requirement of sensor failure, if the sensor in the safety instrument system meets this requirement, it is necessary for relevant personnel to select the integrated sensor, so as to make the safety instrument system meet the design requirements. When the sensor does not meet the requirements of SIL, the use of redundant sensors should be strengthened. However, in the application of redundant sensors, designers need to fully consider the safety of the system, while strengthening the interlocking action and frequency as the basis for rational use of the logical structure, not only to comprehensively consider the applicability of the system, but also to ensure that the instrument system has reliable security, so in practice, A two-out-of-three structure in a logical structure should be used appropriately.

1.2 Carry out a comprehensive design of the safety instrument system

SIL is the main requirement for the safety and integrity of the function of the instrument system. However, the function of the safety instrument system is not determined by one device, but by several devices during operation, which mainly include: sensors, actuators and logic controllers. At the same time, there is a corresponding relationship between each instrument, the SIL between the three and the SIL of the logical sensing has an important relationship, at this time, the relevant staff should pay more attention to, especially the failure rate of the relevant instrument, which has a certain corresponding relationship with the level of SIL. For example, in the analysis of the relevant logical control, if the control unit has a SIL level of 3, the real efficiency of the controller will be less than 0.1%, and in the case of the sensor, when its SIL level is 2, the failure rate will be less than 1%. At the same time, the corresponding execution system is analyzed, and the structure is a level 1 SIL, and the failure rate of the execution structure will be less than 10% [2]. However, in practical applications, the reliability of safety instrument system operation will be directly affected by the logic controller. In addition, according to the investigation in the production process of petrochemical enterprises, many staff are too dependent on the reliability of the logic controller, which is also the main problem in the actual production process. Due to the greater emphasis on it, they ignore the importance of the actuator. If they do not pay more attention to the failure rate level of the actuator, it will lead to problems in the function of the entire safety instrument system. It can even make the safety of the instrument lose its function. Therefore, in the design of safety instrument system, relevant designers need to analyze from an objective point of view, pay attention to the comprehensive design of the system, ensure that various instruments can meet the standard of failure rate level in the design process, provide guarantee for the improvement of the safety level of the system, and make its safety performance meet the safety level standard.

1.3 Performing Integration Configurations

In the actual design process, there will be more failure rate problems, so relevant personnel need to fully study the failure rate level of each instrument in the process of system design, and analyze the failure rate level of the whole system through the parallel relationship. For example, when the failure rate of the logic controller is level 3, which meets the specific requirements of the system, in the actual design process, the designer also controls the actual failure rate at level 3, while the failure rate of the sensor and the actuator are respectively controlled at level 2, then the failure rate of the whole system is also level 2 through calculation and analysis. In this case, according to the specific requirements of the safety instrument system, if the failure rate of the whole system is level 2, the standard of the system cannot be met. If this happens, the relevant designer should take appropriate measures to deal with it, usually using redundant configuration to improve the sensor. For example, in the application of redundant configuration, according to the characteristics of the sensor failure rate to choose the appropriate way to configure, through the analysis of the above content, the use of two-to-one redundancy method, can make the safety level of the system to be improved. At the same time, in the process of redundant configuration, the designer can also configure the actuator and solenoid valve at the same time, which should be scientifically and reasonably configured according to the characteristics of the two, so that the safety level of the entire system has been effectively improved, so that it reaches the standard of SIL3, in order to promote the safety of the system to meet the specific requirements of the staff in the production operation. Because different situations in the instrument system have different requirements for the actuator, and there are certain differences in the type and function of the actuator, different actuators have different redundant configuration methods, requirements and standards in the actual design process. For example, in the process of system design, the main performance of the actuator is to cut the interlock, and at this time, the two actuators in the system are connected in series and applied, which can effectively improve the SIL. Therefore, in the design process, the designer should make a detailed analysis according to the actual situation of the system, based on this, the selection of the actuator, and according to the functional characteristics of the actuator reasonable redundancy configuration, only in this way, can promote the improvement of the SIL level.

1.4 Strengthen the corresponding management work

Although oil care enterprises have high requirements for instrument systems, and the state also has certain standard requirements for it, according to the actual application analysis of instrument systems, it is found that there are certain problems in the safety protection work of the system, actual operation and construction, or the cognition of risks in production, and it cannot meet people's requirements. For example, in the actual design of safety instrument system, during the design process, no scientific method is adopted in the calculation and estimation of SIF, which will cause problems in redundancy configuration. The main problems are reflected in fault tolerance. In this process, the guidance of design drawings and schemes is ignored only for the completion of the design, resulting in deviations and other situations in the construction. In this case, the safety performance of the instrument system will decline. Therefore, in order to ensure the stability, safety and reliability of the instrument system during operation, relevant managers should conduct comprehensive management of the instrument system, and formulate corresponding management plans for the implementation of management work. This ensures that the safety of the instrument safety system during operation can meet the requirements of the staff.

2 Safety instrument reliability fault-tolerant design

As far as the design of instrument system is concerned, if the petrochemical system is designed, the designer should protect the instrument tested by the instrument in advance, conduct a comprehensive analysis of the process behavior involved in the operation of the instrument, evaluate the overall safety, and make a detailed division of the safety instrument system according to the evaluation content [3]. In addition, if an instrument system with a low safety level is found in the process of analysis and evaluation, the design of the instrument system should be integrated into DCS at this time, so as to reasonably control the design cost of the system. In addition, for the loop with high failure rate, its application in production not only has a greater threat, but also has a direct impact on the production order. Therefore, the safety instrument system should be designed for the loop to realize the control of the safety performance of the loop and reflect the specific function of the loop. This provides guarantee for the safety and reliability of production.




  • Omron NS5-MQ00B-V2 Touch Screen HMI
  • Siemens 6DP1280-8AB SIMADYN D Control Module
  • Schneider HJA36060U43X PowerPact H Breaker
  • WITTENSTEIN LP120X-MF2-50-1I1-3X-SPE Planetary Gear
  • Omron G9SX-GS226-T15-RT Safety Guard Relay
  • Omron CPM1A-40CDT1-D-V1 Programmable Controller
  • ABB ACH550-01-05A4-4 HVAC Drive 2.2kW
  • Schneider TSXDMZ28DT Modicon TSX Micro I/O Module
  • Siemens 6DL1131-6BH00-0EH1 ET200SP HA DI Module
  • B&R X20IF10E3-1 PROFINET IO Interface Module
  • Siemens QBE3000-D4 Transmitter
  • Inovance H3U-3624MT PLC Controller
  • Inovance AM600-CPU1608TP PLC Module
  • Omron NS8-TV00B-V2 NS8-TV00B-ECV2 HMI
  • Phoenix ILC 151 ETH PLC Module
  • National Instruments NI-9242 Analog Input Module
  • Fanuc A16B-3200-0521 Main Board
  • NLT NL8060BC26-35F 10.4 LCD Screen
  • Pilz PSEN cs1.1P 540050 Safety Switch
  • Keyence VT-SW4 VT-7SR Touch Panel
  • Siemens 6ES7 131-1BL11-0XB0 Digital Input Module
  • Mitsubishi RJ71EIP91 Ethernet IP Module
  • Siemens 3RW4047-1BB14 Soft Starter 55kW
  • Mitsubishi AJ71C21-A PLC Programmable Controller
  • NL8060BC21-06 8.4 Inch LCD Module
  • Siemens 6ES7215-1HG40-0XB0 PLC S7-1200
  • Siemens 3VA2463-5HL32-0AA0 630A Breaker
  • Saginomiya E-UJ-44030-B Control Board
  • Schmersal MV10H330-11y-M20-1348 Safety Switch
  • Fanuc A16B-1211-0301-04A Control Board
  • Siemens 6SN1123-1AB00-0AA2 LT Module
  • A100005506 Compair Delcos 3100 Control Panel
  • Omron ZFV-CA40 Smart Sensor Amplifier
  • Fanuc A16B-2200-0660 I O Board
  • Omron CJ1W-NC471 Position Control Unit
  • Siemens 6SN1112-1AA00-0AA0 Simodrive PWM Module
  • Mitsubishi GT2708 HMI Touch Panel
  • Siemens 3TK2834-1BB40 Safety Switch
  • INSYS EBW-E100 Industrial Ethernet Router
  • Schneider LC1F400 Contactor TeSys F
  • Mitsui RYP-51 PCB Control Board
  • Tamagawa TS2620N941E172 Encoder
  • Pilz PZE 9 Safety Relay
  • Omron C1000H-CPU01-V1 PLC
  • Siemens 6SL3210-1KE21-3UP1 Frequency Converter
  • Allen-Bradley 440E-L22BNSM Rope Pull Switch
  • ABB CI868K01 Interface Module
  • Stein Sohn E 083.1 PLC Rack
  • Mitsubishi GT2508-VTBD GT2508-VTBA HMI
  • ABB 3BSE018161R1 Module
  • CAREL ASD100 PGD1AY0I00 Operation Panel
  • ABB EK370-40-11 Contactor 220-230V
  • Eaton 9PX1500IRTM UPS 1500VA
  • NCV-20NGNMP Programmable Controller
  • Mitsubishi LE-40MTA-E Tension Controller
  • Fanuc A16B-3200-0429 Control Board
  • Mitsubishi GT2310-VTBA HMI Touch Screen
  • 3A99184G 1C31170G PCB Module Rev 10
  • Schneider 140NOM25200 Modicon Quantum Adapter
  • Mitsubishi NV400-SW 400A Circuit Breaker
  • Applied Materials 0190-51102 Heater Controller
  • Omron C200H-DA003 Analog Output Module
  • Yaskawa JANCD-YCP21-E DX200 CPU Board
  • IAI 12G2-60-250-P-L-C1-SP Intelligent Actuator
  • NLT NL8060BC21-11 8.4 LCD Screen
  • Omron NX502-1300 Controller Unit
  • ABB RVT-6 Power Factor Controller
  • Schneider TM258LF66DT4L PLC Controller
  • NLT NL6448BC26-27D 8.4 LCD Panel
  • NLT NL8060BC21-09 8.4 LCD Screen
  • Keyence XG-8700L Multi-camera Imaging System
  • EPC 50 3183045486 I O Motherboard
  • Nidec Emerson M701-054-00270A CT Drive
  • Therma Wave 18-011040 Controller Assembly
  • Mitsubishi Q03UDECPU PLC CPU Module
  • Allen-Bradley 2002-NX70-MWLINK PLC Module
  • AS-2P-60M-B Industrial PLC Cable
  • Yaskawa JANCD-YCP21-E DX200 CPU Board
  • PASABAN MC-2006 03 CAN PLC Card
  • Mitsubishi RJ71PB91V PROFIBUS DP Module
  • Fanuc A20B-8100-0137 PCB I O Board
  • D0-06DD2-D PLC Module DL06 PLC
  • Kepco BOP100-4M Power Supply Amplifier
  • Allen-Bradley 1785-L60B PLC-5 60 Module
  • Siemens 7MH4900-3AA01 Weighing Module
  • Pilz 773100 PNOZ m1p Safety Controller
  • Omron NS12-TS00B-V2 Graphic Operation Panel
  • EC20-4040BTA Programmable Controller PLC
  • Fanuc A16B-1212-0100-01 Power Unit CNC
  • Siemens 6ES7151-3BB23-0AB0 ET200S Interface Module
  • ATTO Control DU-01 PLC Display System
  • Keyence KV-RC8BXR Programmable Controller
  • Lenze GST04-1GVCK-063C22 Servo Motor
  • CKD AX9000GH AX9210H Control Unit
  • ABB PG6310 DC Trigger Control Board
  • Cutler Hammer 10316H621C Type L Device
  • TAIYO AA-277 EM CY TRIP PCB Card
  • Schneider BMXCPS2010 PLC Power Supply
  • Schneider TSXMRPC007M PLC PCMCIA Card
  • 101182218 Safety Stop Relay SSW301HV-230V
  • Cutler Hammer 9-1875-3 Size 6 Contactor 480V
  • Nidec UNI3401 Drive Module Control Board
  • Delta AS06XA-A PLC Module Analog Mixed IO
  • Lenze EPL 10201 13408978 Servo Drive 24V DC
  • Sigmatek CCP612-K PLC Module DI DO Module
  • Schneider ATS48D38Q Soft Starter Altistart 48
  • Fanuc A20B-3300-0472 Main CPU Board Series 30i
  • Mitsubishi A171SCPU-S3 Servo CPU Module PLC
  • ABB 1SFL597001R7011 700A 100-250V Soft Starter
  • Yaskawa JANCD-YCP21-E DX200 CPU Control Board
  • Schneider NS630N Circuit Breaker 3P 630A
  • Honeywell DPCB21010002 Rack Slot PCB
  • Mitsubishi RJ71EIP91 PLC Module
  • Siemens 3VL5763-1DC36-0AA0 Circuit Breaker
  • Siemens 6GK7542-1AX00-0XE0 Communication Module
  • Siemens 6SL3130-6AE15-0AB1 Smart Line Module
  • HMS Anybus AB7646-F Gateway
  • Honeywell 621-0020 Analog Input Module
  • Siemens 6ES7212-1HF40-0XB0 PLC Controller
  • MAK 1.00.7-36.21.00-40 PCB Module
  • ABB 3BSE006503R1 PFSA140 Power Supply
  • SAACKE F-GDSA 143303 Burner Controller
  • ABB PFSC230 25m Cable Set
  • GE HYDRAN 201Ci-1 Controller
  • ABB NINT-42C main circuit interface board
  • B&R 3AT660 6 Thermocouple Input Module
  • Honeywell EC7850A1080 Programmable Logic Controller
  • Mitsubishi A2ACPU21 CPU Module MELSEC A Series