Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

ControlEdge HC900 Controller Communications User Guide

F: | Au:佚名 | DA:2023-11-27 | 709 Br: | 🔊 点击朗读正文 ❚❚ | Share:

4. Select the Set Controller’s Network Parameters button. Using the wizard (bottom radio button), select the PC COM port to be used, then set the controller’s new network parameters including IP address, Subnet Mask (if other than default, 255.255.255.0), and Default Gateway IP address (if required, otherwise leave at default 0.0.0.0). See your IT network administrator for proper entries. (Refer to the on-line help provided with the HC Designer software, Utilities Worksheet, Set Controller’s Network Parameters, for further details on this step).

Note: This setup will require the controller to be placed temporarily in the Program mode. After the new network parameters have been downloaded, the controller will conduct a Cold Start in its transition to RUN. This will cause an initialization if there is a current configuration in the controller.

The fixed IP address of each controller shall be set independently prior to placing on the network. See your IT systems administrator for allocating IP addresses, subnet masks, or default gateway IP address as necessary (network address filtering and routing may be necessary if the controller network access will not to be confined locally within the plant environment).

Ethernet 10/100Base-T Network Connections

Ethernet 10/100Base-T networks operating at 10/100MB/sec. are supported. A typical network arrangement is as shown below.

Setting Up the Modbus/TCP Double Register Format

The ControlEdge HC900 predominantly uses an IEEE floating point format for communicating data to software applications providing Modbus/TCP protocol communications drivers. A floating point value is sent as (2) consecutive 16-bit registers, each register of which consists of two 8-bit bytes. Some software packages require the registers and bytes to be sent in a certain order. The controller can be configured to deliver the data in four different byte orders.

The Process Control Designer software tool allows this order to be selected as follows:

1. Using the Utilities Worksheet in the HC Designer software, access the Set Controller Network Parameters button and make the selection to change the Modbus TCP Double Register Format (middle radio button).

2. With the Port selected for downloading this order (using a COM port or Network port), select the appropriate byte order format if the default (FP B) is not appropriate for the application. See Table 3-1, page 9.

3. Select Next and verify (by the response in the dialog box) that the change has been made in the controller. This order can be changed in the RUN mode.

The Modbus TCP double register transmission format selection, FP LB “Little Endian Byte-Swapped”, would be selected for interface to most third party software packages which use this format as standard. The default, FP B “Big Endian” is used with SpecView32 or Honeywell’s PlantScape/Experion/EBI software and follows the “Honeywell” default format of other control and recording products. It should be noted that most PC software packages offer a register (word) swap selection in their driver package anyway, so there should never be an incompatibility.

1.3 Modbus RTU RS232/RS485 Communication Ports

This implementation is designed to provide a popular data exchange format connecting the ControlEdge HC900 to both Honeywell and foreign master devices via the RS232 and RS485 communication ports. The Modbus RTU allows the instrument to be a citizen on a data link shared with other devices, which subscribe to the Modicon Modbus Protocol Reference Guide PI-MBUS-300 Rev. G specification.

These instruments DO NOT emulate any MODICON type device. The Modbus RTU specification is respected in the physical and data link layers. The message structure of the Modbus RTU function codes is employed and standard IEEE 32-bit floating point and integer formats are used. Data register mapping is unique to the ControlEdge HC900 and other Honeywell instruments. Section 6 describes the parameter mapping for the ControlEdge HC900.

Summary

The SP Programmer parameters are listed according to category related to program status and interaction, other programmer parameters and program segment mapping.

In the fixed map each SP Programmer is assigned to three non-contiguous sections of the map:

 SP Programmer parameters (Table 6-9)

 SP Programmer Additional parameters (Table 6-9, page 58)

 SPP Programmer segments (Table 6-10).

In a custom map the above parameters may be contiguous.

Function Code Support:

Read – Function Code 3

Write – Function Code 16 (10 Hex)

Considerations and Methods for Downloading. Operating, and Reading Status of SP Programs

A SP programmer interface can be developed (and recipes containing a SP profile can be created) in third party software using the parameters listed in the following table.

In creating a SP Programmer interface showing a number of segments, a graphic display might include a table referencing the maximum number of ramp/soak segments that you will be using for your process. The parameters to be referenced for each segment are listed in Table 6-10.

Procedure for Downloading Setpoint Profile

These steps are for programmer 1. For programmers 2, 3, 4, 5, 6, 7, and 8 adjust the register addresses accordingly by adding offset for starting addresses.

  • Basler SR32A2B05B3E Static Voltage Regulator
  • Basler Electric BE1-59N Ground Fault Overvoltage Relay
  • Basler Electric 9110000113 Excitation Module
  • Basler Electric 90-72300-114 Control Accessory
  • Basler Electric PRS-250 Protection Relay System
  • Basler Electric BE1-50/51M-109 Overcurrent Relay
  • Basler Electric SR4A1B10B3E Static Voltage Regulator
  • Basler Electric CBS 212 Current Boost System
  • Basler Electric SR32A2B05B3E Static Voltage Regulator
  • Basler Electric MOC2207 Motor Operated Potentiometer
  • Basler Electric SR4A1B05A3E Static Voltage Regulator
  • Basler Electric BE1-32R Power Relay B2EE1PA0N1F
  • Basler BEI-81 Underfrequency Relay
  • Basler CBS 212A Current Boost System
  • Basler SSR 63-12 Static Voltage Regulator
  • Basler DGC-2020 Digital Genset Controller
  • Basler BE1-32 Reverse Power Relay
  • Basler BE1-50/51B-207 Overcurrent Relay
  • Basler BE1-951 Overcurrent Protection System
  • Basler 9073800-103 Power Supply
  • Basler SCA1300-32FC CCD Camera
  • Basler 9073800-103 Power Supply
  • Basler SCA1300-32FC CCD Camera
  • Basler L304KC Protective Relay
  • Basler BE3-25-1S1N4 Time Overcurrent Relay
  • Basler 9032300113 Excitation Support System
  • Basler BE1-59N Ground Overvoltage Relay
  • Basler MVC-300 Manual Voltage Control Unit
  • Basler MOC2102 Potentiometer
  • Basler BE1-87G Generator Differential Relay
  • Basler Electric DECS-200 Digital Excitation Control System
  • Basler Electric DECS 125-15-B2C5 Digital Excitation System
  • Basler Electric PLA2400-12GM Power Supply
  • Basler Electric BE1-50/51B-235 Overcurrent Relay
  • Basler Electric BE1-27/59 Undervoltage Overvoltage Relay
  • Basler Electric CEM-2020 Contact Expansion Module
  • Basler Electric BE1-32R Solid State Power Relay
  • Basler Electric BE1-700 Digital Generator Management Relay
  • Basler Electric BE1-59N Ground Fault Overvoltage Relay
  • Basler Electric BE10493002 Protection Module
  • Basler Electric BEI-79A1AA5CA3M1F Digital Annunciator
  • Basler Electric SSR 32-12 Static Voltage Regulator
  • Basler Electric BE1-CDS240 Current Differential System
  • Basler Electric BE1-67 Directional Overcurrent Relay
  • Basler Electric 9121000106 DECS-100 Voltage Controller
  • Basler Electric BEI-871 Interface Module
  • Basler Electric 8650C72 Exciter Control Module
  • Basler Electric RDP-110-S1 Generator Annunciator
  • Basler Electric BE1-32O/U Directional Power Relay
  • Basler Electric BE2000E AVR Voltage Regulator
  • BASLER ELECTRIC BE1-50F2EA1PA0N0F Instantaneous Overcurrent Relay
  • BASLER ELECTRIC BE1-81T1EE1WA0N1F Underfrequency Relay
  • Basler BE1-67 Directional Overcurrent Relay
  • Basler BE1-25/79TR Reclosing Relay
  • Basler CEM-2020 Contact Expansion Module
  • Basler BE1-11 Overcurrent Protection Relay
  • Basler BE1-GPS Generator Protective Relay
  • BASLER ELECTRIC MVC-300 MANUAL VOLTAGE CONTROL UNIT 9121000106
  • Basler Electric KR2FF Voltage Regulator 9 1163 00 109
  • BASLER ELECTRIC BE1-87G-G1E-A1K-A0N0F Generator Differential Relay
  • Basler BE1-47NE3EA1PA0N2F Phase Sequence Relay
  • Basler BE1-81-T1E-E1C-B0N1F Frequency Relay
  • Basler DECS125-15 Excitation Control
  • Basler BE1-25 Sync-Check Relay
  • Basler BE1-50/51B Overcurrent Relay
  • Basler BE1-40Q Loss of Excitation Relay
  • Basler BE1-50/51M-104 Overcurrent Relay
  • Basler SSE-N 250-9 KW Shunt Exciter Assembly
  • Basler BE1-87T Transformer Differential Relay
  • Basler BE1-60 Solid State Protective Relay
  • Basler DECS125-15 Excitation Control System
  • Basler SR4A-2B15B3A Static Voltage Regulator
  • Basler BE150BF Overcurrent Relay
  • BASLER ELECTRIC BE1A1HF1JD1S2F Overcurrent Relay
  • Basler BE1-81O Under/Over Frequency Relay
  • Basler EDM-200 Exciter Diode Monitor
  • Basler DECS125-15-B2C5 Excitation Control
  • Basler 9261402100 PCB Board
  • Basler 9252000107 Overcurrent Relay
  • Basler BE1-87T Solid State Protective Relay
  • Basler Electric Phase Directional Overcurrent Relay BE1-Z2JA0N2F
  • Basler SSR125-12 Static Voltage Regulator
  • Basler Electric KR7F VOLTAGE REGULATOR 9116200100
  • BASLER ELECTRIC BE1-59N-A8E-E1L-N0S1F Ground Overvoltage Relay
  • Basler SR8A2B06B3A Static Voltage Regulator
  • BASLER ELECTRIC BE1-81O/UT3EE1KA7N1F Under/Over Frequency Relay
  • Basler MOC2107 Output Module
  • Basler 9125600102 Control Module
  • BASLER ELECTRIC BE1-81T1EE1EA2N0F
  • Basler BE3-25A Time Overcurrent Relay
  • Basler Electric CBS 212 Current Boost System 9 2650 00 100 120/240 VAC 50/60Hz
  • Basler Electric BE1-27 Under Voltage Relay A3EC1JA0N5F
  • Basler BE1-32R Power Relay B2EE1PA0N1F
  • Basler DECS100-B15 Automatic Voltage Regulator
  • Basler SR8A-2B15B3A Static Voltage Regulator
  • Basler AVC63-4 Analog Voltage Regulator
  • Basler UFOV 260 A Overvoltage Module
  • Basler SR4A-2B16B3A Static Voltage Regulator
  • Basler SR4A-2B16B3E Static Voltage Regulator
  • Basler SCA1300-32GM CCD Camera
  • Basler BE34062001 G18 Transformer
  • Basler BE1-87T Transformer Differential Relay
  • Basler 9 2849 00 101 DECS Power Module
  • Basler RAL6144-16GM Line Scan Camera
  • Basler 9269101107 Voltage Regulator Board
  • Basler BE1-851 Overcurrent Relay
  • Basler SR32A-2B13B3E Static Voltage Regulator
  • Basler 9 2007 00 100 Current Boost System CBS 305
  • Basler DECS-100-B11 Automatic Voltage Regulator
  • Basler BE127 Under Voltage Relay
  • Basler 3300C03B1028-G01 Spike Suppressor
  • Basler SSR 125-12 Static Voltage Regulator
  • Basler SCA1300-32GM CCD Camera Lens Enclosure
  • Basler BE32965001 Transformer Timer Kit
  • Basler D90 96801 100 PCB Card
  • Basler BE1-81-T1E-E1C-A0N1F / 9106400 Underfrequency Relay
  • Pro-Face Basler AGP3600-T1-D24 HMI Touch
  • Basler SR4A2B10B1A Static Voltage Regulator
  • Basler SR8A2B05B3A Static Voltage Regulator
  • Basler BE1-25 Time Overcurrent Relay M1FA6PA4S0F
  • Basler SR4A2B05B3E Static Voltage Regulator
  • Basler DECS-200-2L Digital Excitation Control
  • Basler BE303280001 Control Transformer
  • Basler 9262103004 Voltage Regulator Board For Basler DECS-400
  • Basler ICRM-7 Inrush Current Reduction Module
  • Basler BE1-32R Power Relay
  • BASLER ELECTRIC KR4F VOLTAGE REGULATOR 9042600100 600V 50/60Hz
  • Basler 9222600101 Power Module