Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

ControlEdge HC900 Controller Communications User Guide

来源: | 作者:佚名 | 发布时间 :2023-11-27 | 535 次浏览: | Share:

4. Select the Set Controller’s Network Parameters button. Using the wizard (bottom radio button), select the PC COM port to be used, then set the controller’s new network parameters including IP address, Subnet Mask (if other than default, 255.255.255.0), and Default Gateway IP address (if required, otherwise leave at default 0.0.0.0). See your IT network administrator for proper entries. (Refer to the on-line help provided with the HC Designer software, Utilities Worksheet, Set Controller’s Network Parameters, for further details on this step).

Note: This setup will require the controller to be placed temporarily in the Program mode. After the new network parameters have been downloaded, the controller will conduct a Cold Start in its transition to RUN. This will cause an initialization if there is a current configuration in the controller.

The fixed IP address of each controller shall be set independently prior to placing on the network. See your IT systems administrator for allocating IP addresses, subnet masks, or default gateway IP address as necessary (network address filtering and routing may be necessary if the controller network access will not to be confined locally within the plant environment).

Ethernet 10/100Base-T Network Connections

Ethernet 10/100Base-T networks operating at 10/100MB/sec. are supported. A typical network arrangement is as shown below.

Setting Up the Modbus/TCP Double Register Format

The ControlEdge HC900 predominantly uses an IEEE floating point format for communicating data to software applications providing Modbus/TCP protocol communications drivers. A floating point value is sent as (2) consecutive 16-bit registers, each register of which consists of two 8-bit bytes. Some software packages require the registers and bytes to be sent in a certain order. The controller can be configured to deliver the data in four different byte orders.

The Process Control Designer software tool allows this order to be selected as follows:

1. Using the Utilities Worksheet in the HC Designer software, access the Set Controller Network Parameters button and make the selection to change the Modbus TCP Double Register Format (middle radio button).

2. With the Port selected for downloading this order (using a COM port or Network port), select the appropriate byte order format if the default (FP B) is not appropriate for the application. See Table 3-1, page 9.

3. Select Next and verify (by the response in the dialog box) that the change has been made in the controller. This order can be changed in the RUN mode.

The Modbus TCP double register transmission format selection, FP LB “Little Endian Byte-Swapped”, would be selected for interface to most third party software packages which use this format as standard. The default, FP B “Big Endian” is used with SpecView32 or Honeywell’s PlantScape/Experion/EBI software and follows the “Honeywell” default format of other control and recording products. It should be noted that most PC software packages offer a register (word) swap selection in their driver package anyway, so there should never be an incompatibility.

1.3 Modbus RTU RS232/RS485 Communication Ports

This implementation is designed to provide a popular data exchange format connecting the ControlEdge HC900 to both Honeywell and foreign master devices via the RS232 and RS485 communication ports. The Modbus RTU allows the instrument to be a citizen on a data link shared with other devices, which subscribe to the Modicon Modbus Protocol Reference Guide PI-MBUS-300 Rev. G specification.

These instruments DO NOT emulate any MODICON type device. The Modbus RTU specification is respected in the physical and data link layers. The message structure of the Modbus RTU function codes is employed and standard IEEE 32-bit floating point and integer formats are used. Data register mapping is unique to the ControlEdge HC900 and other Honeywell instruments. Section 6 describes the parameter mapping for the ControlEdge HC900.

Summary

The SP Programmer parameters are listed according to category related to program status and interaction, other programmer parameters and program segment mapping.

In the fixed map each SP Programmer is assigned to three non-contiguous sections of the map:

 SP Programmer parameters (Table 6-9)

 SP Programmer Additional parameters (Table 6-9, page 58)

 SPP Programmer segments (Table 6-10).

In a custom map the above parameters may be contiguous.

Function Code Support:

Read – Function Code 3

Write – Function Code 16 (10 Hex)

Considerations and Methods for Downloading. Operating, and Reading Status of SP Programs

A SP programmer interface can be developed (and recipes containing a SP profile can be created) in third party software using the parameters listed in the following table.

In creating a SP Programmer interface showing a number of segments, a graphic display might include a table referencing the maximum number of ramp/soak segments that you will be using for your process. The parameters to be referenced for each segment are listed in Table 6-10.

Procedure for Downloading Setpoint Profile

These steps are for programmer 1. For programmers 2, 3, 4, 5, 6, 7, and 8 adjust the register addresses accordingly by adding offset for starting addresses.

  • BENTLY 1-536067-4 Proximitor Connector Lead
  • BENTLY 3500/34 125696-01 TMR Relay Module
  • BENTLY 125704-01 3500/32M I/O Module
  • BENTLY 126632-01 Keyphasor I/O Module
  • BENTLY 3500/25 125792-01 Keyphasor Module
  • Bently Nevada 2300/25-00 Vibration Monitor
  • Bently Nevada 3500/05-01-03-00-00-00 Rack
  • Bently Nevada 3500/42M 140734-02 Monitor
  • Bently Nevada 123M4610 Accelerometer
  • Bently Nevada 3500/05-02-04-00-00-00 Rack
  • Bently Nevada 3500/53 133388-01 Overspeed Detection Module
  • Bently Nevada 3500/32 125712-01 Relay Module for Machinery Protection
  • Bently Nevada 3500/20 125744-02 Rack Interface Module
  • Bently Nevada 3500/40M 140734-01 Proximitor Monitor Module
  • Bently Nevada 3500/60 163179-01 Temperature Monitor Module
  • BENTLY 3500/22M 288055-01 Enhanced TDI Module
  • BENTLY 3500/22M 146031-01 TDI Module
  • BENTLY 133396-01 3500/22M I/O Module
  • BENTLY 3500/34 TMR RMS Interface Module
  • BENTLY 128275-01-E Proximitor I/O Module
  • Bently Nevada 128276-011 Proximity Probe
  • Bently Nevada 135489-03 Accelerometer
  • Bently Nevada 135473-01 Seismic Transducer
  • Bently Nevada 1900/55 General Purpose Monitor
  • Bently Nevada ASSY78462-01U Proximitor Assembly
  • Bently Nevada 330100-90-01 Proximity Probe for Vibration Monitoring
  • Bently Nevada 330100-90-00 Proximity Probe for Machinery Monitoring
  • Bently Nevada 132419-01 Proximitor Sensor for Vibration Monitoring
  • Bently Nevada 10244-27-50-01 Proximity Probe Extension Cable
  • Bently Nevada 22810-01-05-50-02 Proximity Probe System
  • BENTLY 330980-51-00 3300 NSv Proximitor Sensor
  • BENTLY 330130-045-00-00 3300 XL Extension Cable
  • BENTLY 1X35668 Replacement Internal Module
  • BENTLY 3300/16 Dual XY Vibration Monitor
  • BENTLY 3500/15 133292-01 High Availability Power Supply
  • Bently Nevada 3500/62 163179-03 Process Monitor
  • Allen-Bradley 80190-100-01-R*3 Output Module
  • Allen-Bradley 80190-099-01 Analog Module
  • Allen-Bradley 80190-479-01 I/O Module
  • Allen-Bradley 80190-480-01-R Control Module
  • Bently 3500/15 125840-01 Power Supply Module
  • Bently 24765-02-01 Signal Conditioner Module
  • Bently 330130-085-00-00 Extension Cable
  • Bently 3500/22M 138607-01 Vibration Monitor Module
  • Bently 146031-02 Proximity Probe Sensor
  • BENTLY 330104-00-05-10-02-CN Proximity Probe
  • BENTLY 125768-01 3500 I/O Module Interface
  • BENTLY 3500/92 136180-01 Communication Gateway
  • BENTLY 84152-01 Proximitor Sensor Cable
  • BENTLY 3300/20 Dual Driver Proximitor Housing
  • BENTLY 3300/16-11-01-03-00-00-01 16-Channel Monitor
  • DEIF PPU-3 Power Protection Unit for Genset Control
  • DEIF RMV-112D Reactive Power Divider and Voltage Matching Relay
  • DEIF OPM-1 Output Protection Module for Gensets
  • DEIF IPM-1 Integrated Protection Module for Generators
  • DEIF CM-2 Control Module for Industrial Power Systems
  • DEIF PSM-1 Power System Manager Module
  • DEIF DELOMATIC-3 DGU2 Automatic Generator Control Unit
  • DEIF DLQ144-PC-NB Power Monitoring Meter
  • DEIF DU-2/MKIII Voltage Relay Controller
  • DEIF IOM4.2 Input/Output Module for Power Management
  • DEIF SCM-1 Synchronizing Control Module
  • DEIF GPU/2/GS Genset Parallel Unit Controller
  • EMERSON PR6426/010-110 CON021 Proximity System
  • EMERSON PR6423/011-110+C0N021 Proximity Sensor System
  • DEIF LSU-112DG Load Sharing Unit
  • DEIF PCM4.4 Advanced Power Control Module
  • DEIF TAC-311DG Transducer for AC Voltage
  • DEIF SCM4.1 Engine Start Control Module
  • DEIF PCM4.3 Power Control Module
  • Emerson 2500M/AI4UNIV Universal Analog Input Module
  • Emerson PR6424/011-140 Eddy Current Sensor
  • Emerson KJ3242X1-BK1 12P4711X042 Analog Input Module
  • Emerson FX-316 960132-01 Control Processor Module
  • Emerson KJ4006X1-BD1 Power Supply Module
  • EMERSON 1C31181G01 Ovation Analog Output Module
  • EMERSON CE4003S2B6 DeltaV Analog Module
  • EMERSON KJ4001X1-CK1 DeltaV I/O Carrier Card
  • EMERSON VE4012S2B1 DeltaV I/O Module Specifications
  • EMERSON SS6501T01 DeltaV System Assembly Technical Overview
  • Emerson A6370D/DP Display
  • Emerson P188.R2 Power Supply
  • Emerson A6824R 24-Ch Relay
  • Emerson KJ2201X1-JA1 Serial
  • Emerson VE3008 Main Controller
  • Emerson VE3008 CE3008 KJ2005X1-MQ1 Controller Module
  • Emerson TPMC917 Embedded Processor Module
  • Emerson P152.R4 Industrial Control Module
  • Emerson DA7281520 P152 Power Module
  • Emerson PR6423/008-110 Eddy Current Sensor
  • EMERSON 5X00273G01 Ovation DCS Digital Output Module
  • EMERSON KJ4001X1-NB1 12P3368X012 REV:E Redundant Controller Backplane
  • EMERSON KJ4001X1-NA1 12P3373X012 REV:C Intrinsically Safe Interface
  • EMERSON KJ4001X1-BE1 12P0818X072 REV:L DeltaV I/O Carrier
  • EMERSON KJ2221X1-BA1 DeltaV SIS SISNet Repeater Module
  • EMERSON PR6423/000-131 Eddy Current Sensor
  • EMERSON 5X00790G01 Ovation Digital Output Module
  • EMERSON 5X00846G01 Ovation Analog Input Module
  • EMERSON KJ4110X1-BA1 DeltaV Power Supply Base
  • EMERSON CSI3125 A3125/022-020 Dual Channel Monitor
  • EMERSON A6740 Displacement Case Expansion Monitor
  • EMERSON A6312/06 Speed Monitoring Module
  • EMERSON KJ4001X1-BE1 DeltaV Carrier Module
  • EMERSON SE3008 KJ2005X1-MQ2 DeltaV Controller
  • EMERSON KJ4001X1-CA1 DeltaV Terminal Block
  • Emerson PR6423/00R-010 CON031 Eddy Current Probe System
  • Emerson A6824 9199-00090 Operator Workstation
  • Emerson A6410 9199-00005 Operator Workstation
  • Emerson A6110 9199-00001 Operator Workstation
  • Emerson 9199-00002 A6120 Operator Workstation
  • Emerson KJ3002X1-BF1 12P1732X042 FIELDVUE DVC6200
  • Emerson 5X00500G01 Ovation Analog Output Module
  • Emerson VE4001S2T2B4 DeltaV Controller Module
  • Emerson 5X00502G01 Ovation Analog Input Module
  • Emerson A6824R 9199-00098-13 Operator Workstation
  • EMERSON A6140 9199-00058 Dual Channel Monitor
  • EMERSON VE3007 KJ2005X1-BA1 DeltaV Controller
  • EMERSON DB1-1 Connection Termination Block
  • EMERSON PMC-IO-ADAPTER Mezzanine Interface Card
  • EMERSON L0115012 L0115032 Solenoid Valve Components
  • Emerson A6410 Large Operator Workstation
  • Emerson A6210 Operator Workstation
  • Emerson 1C31232G02 Ovation Controller Module
  • Emerson 5X00106G02 Ovation Power Supply Module
  • Emerson 5X00106G01 Ovation Power Supply Module
  • EMERSON PMC-IO-PROZESSOR High-Speed I/O Module
  • EMERSON PMC PROFINET Communication Module
  • EMERSON MVME7100-0171 VMEbus Single Board Computer