Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

ControlEdge HC900 Controller Communications User Guide

F: | Au:佚名 | DA:2023-11-27 | 674 Br: | 🔊 点击朗读正文 ❚❚ | Share:

1. Introduction

1.1 Overview

Communication interfaces

The ControlEdge HC900 controller provides Modbus communication support on three communication interfaces.

 Network port: Modbus TCP on an Ethernet connection

 Serial Port S1 RS232/RS485 selectable port. (Default RS232.): Modbus RTU

 Serial Port S2 RS232/RS485 selectable port. (Default RS485.): Modbus RTU

View or print addresses

You can print out the Modbus addresses of various parameters of the configuration (signal tags, PID loops, SP programmer, etc.) using the HC Designer report functions. With HC Designer Ver. 2.1 and later, these reports may also be exported to .csv files for view/manipulation in a spreadsheet and possible import to other HMI applications.

Fixed map or custom map

The type of addressing available: fixed or custom.

1.2 Modbus/TCP Interface

Introduction

ControlEdge HC900 controllers support the Modbus/TCP (also called Modbus TCP/IP or Modbus Ethernet) protocol for communications with third party HMI and SCADA software via a direct Ethernet TCP/IP connection.

The controller’s Ethernet 10/100Base-T Host port is used for the Modbus/TCP connection. Ethernet TCP allows multiple concurrent connections to hosts for data interchange. The ControlEdge HC900 (C30/C50) supports 5 concurrent host connections using Modbus/TCP protocol messaging via this port; ControlEdge HC900 (C70/C70R) supports 10.

Interface Preparation

ATTENTION

To access the controller you must have a current Process Control Designer configuration file available. Some data is referenced relative to number, such as Signal Tags and Variables.

Other principal blocks, such as PID blocks, have offsets for parameter access dependent on the order in which the blocks were placed on the Function Block Diagram.

It is strongly recommended that you upload the controller configuration using the Process Control Designer configuration tool to assure that you have a current configuration.

The Process Control Designer tool provides a series of reports for use in Modbus Address identification. The "Tag Information" report lists the variables and Signal Tags in numeric order along with their Modbus Addresses. A "Block Modbus Address" report lists the starting addresses for all principal blocks configured, identifying the offset.

Modbus/TCP Protocol

Modbus/TCP protocol, developed by Groupe Schneider’s Modicon Division, is a popular, open standard for data interchange over Ethernet TCP/IP networks using a Modbus RTU command structure.

It is simply an encapsulation of Modicon’s Modbus RTU protocol within a TCP/IP frame as shown below, which includes header information and the Modbus frame.

The Open Modbus/TCP Specification is followed with respect to the physical, data link, and network layers. The message structure within the Modbus frame uses standard Modbus RTU function codes.

The Address part of the Modbus frame is not used (set to 00) since there is no sub-addressing intended or required. The controller IP address is the identifying address, set independently at the controller.

The error checking is supported by TCP/IP network protocols and not part of the Modbus frame.

The Transaction Identifiers and Protocol Identifiers in the header are normally all 0’s (4 bytes total) while the Length field identifies the number of bytes in the Modbus frame. The controller will transmit the correct number of bytes for the remainder of the frame. However, the controller does not check this field for messages received.

The standard IEEE 32-bit floating point and 16-bit integer formats are used.

Parameter Addressing

The definition in Table 6-1 is the fixed map overview listing starting and ending addresses.

Greater detail for parameter addressing relating to a particular function class (e.g, loops, setpoint programmer, signal tags) is in referenced sub-sections. Function Codes 1, 2, 3, 4, 5, 6, 8, 16 (10h), and 17 (11h) are supported (see Table 4-1 Modbus/TCP and Modbus RTU Function Codes Definitions).

Examples for read or write access to parameters supported by the various function codes are provided in Sections 4.3 through 4.11.

ControlEdge HC900 Ethernet Communications Setup

See the ControlEdge HC900 Control (HC) Designer Users Guide, Doc. # 51-52-25-110 or respective HC Designer Help Files for setting up the following network parameters:

IP Address, Subnet Mask (optional), Default Gateway IP Address (optional)

1. Be sure the PC, HMI panel, or other Host device has a Network Interface Card (NIC) with an IP address (fixed or DHCP served) that allows access to controllers on the same or other subnet. Consult your IT department or network administrator for allocating IP addresses to the controllers as required.

2. You will need to set each controller’s IP address prior to network connection since every ControlEdge HC900 controller is shipped with the default IP address of 192.168.1.254. Placing multiple controllers on the same network before they have been given unique IP addresses will cause problems.

3. On the PC, use the Utilities Worksheet in the HC Designer software to set up the serial RS-232 connection to the controller at the desired baud rate. This will require a null modem cable.

4. Select the Set Controller’s Network Parameters button. Using the wizard (bottom radio button), select the PC COM port to be used, then set the controller’s new network parameters including IP address, Subnet Mask (if other than default, 255.255.255.0), and Default Gateway IP address (if required, otherwise leave at default 0.0.0.0). See your IT network administrator for proper entries. (Refer to the on-line help provided with the HC Designer software, Utilities Worksheet, Set Controller’s Network Parameters, for further details on this step).

Note: This setup will require the controller to be placed temporarily in the Program mode. After the new network parameters have been downloaded, the controller will conduct a Cold Start in its transition to RUN. This will cause an initialization if there is a current configuration in the controller.

The fixed IP address of each controller shall be set independently prior to placing on the network. See your IT systems administrator for allocating IP addresses, subnet masks, or default gateway IP address as necessary (network address filtering and routing may be necessary if the controller network access will not to be confined locally within the plant environment).

Ethernet 10/100Base-T Network Connections

Ethernet 10/100Base-T networks operating at 10/100MB/sec. are supported. A typical network arrangement is as shown below.

Setting Up the Modbus/TCP Double Register Format

The ControlEdge HC900 predominantly uses an IEEE floating point format for communicating data to software applications providing Modbus/TCP protocol communications drivers. A floating point value is sent as (2) consecutive 16-bit registers, each register of which consists of two 8-bit bytes. Some software packages require the registers and bytes to be sent in a certain order. The controller can be configured to deliver the data in four different byte orders.

The Process Control Designer software tool allows this order to be selected as follows:

1. Using the Utilities Worksheet in the HC Designer software, access the Set Controller Network Parameters button and make the selection to change the Modbus TCP Double Register Format (middle radio button).

2. With the Port selected for downloading this order (using a COM port or Network port), select the appropriate byte order format if the default (FP B) is not appropriate for the application. See Table 3-1, page 9.

3. Select Next and verify (by the response in the dialog box) that the change has been made in the controller. This order can be changed in the RUN mode.

The Modbus TCP double register transmission format selection, FP LB “Little Endian Byte-Swapped”, would be selected for interface to most third party software packages which use this format as standard. The default, FP B “Big Endian” is used with SpecView32 or Honeywell’s PlantScape/Experion/EBI software and follows the “Honeywell” default format of other control and recording products. It should be noted that most PC software packages offer a register (word) swap selection in their driver package anyway, so there should never be an incompatibility.

1.3 Modbus RTU RS232/RS485 Communication Ports

This implementation is designed to provide a popular data exchange format connecting the ControlEdge HC900 to both Honeywell and foreign master devices via the RS232 and RS485 communication ports. The Modbus RTU allows the instrument to be a citizen on a data link shared with other devices, which subscribe to the Modicon Modbus Protocol Reference Guide PI-MBUS-300 Rev. G specification.

These instruments DO NOT emulate any MODICON type device. The Modbus RTU specification is respected in the physical and data link layers. The message structure of the Modbus RTU function codes is employed and standard IEEE 32-bit floating point and integer formats are used. Data register mapping is unique to the ControlEdge HC900 and other Honeywell instruments. Section 6 describes the parameter mapping for the ControlEdge HC900.

Summary

The SP Programmer parameters are listed according to category related to program status and interaction, other programmer parameters and program segment mapping.

In the fixed map each SP Programmer is assigned to three non-contiguous sections of the map:

 SP Programmer parameters (Table 6-9)

 SP Programmer Additional parameters (Table 6-9, page 58)

 SPP Programmer segments (Table 6-10).

In a custom map the above parameters may be contiguous.

Function Code Support:

Read – Function Code 3

Write – Function Code 16 (10 Hex)

Considerations and Methods for Downloading. Operating, and Reading Status of SP Programs

A SP programmer interface can be developed (and recipes containing a SP profile can be created) in third party software using the parameters listed in the following table.

In creating a SP Programmer interface showing a number of segments, a graphic display might include a table referencing the maximum number of ramp/soak segments that you will be using for your process. The parameters to be referenced for each segment are listed in Table 6-10.

Procedure for Downloading Setpoint Profile

These steps are for programmer 1. For programmers 2, 3, 4, 5, 6, 7, and 8 adjust the register addresses accordingly by adding offset for starting addresses.

Table 6-7 is for downloading using Function Codes 3, 4, 6, 16.

If using a custom map, you need to know the addresses of the parameters referred to in this procedure. Use HC Designer to print a report showing the Modbus registers of the SP Programmers


  • OMRON CJ1W-MD261 Mixed I/O Module
  • Omron NJ301-1100 PLC CPU eCat EIP Specs
  • Omron F500-C15-ETN Vision System PLC Module
  • Modicon M241-24IO TM/T2UK PLC with Ethernet
  • SIXNET YS-800-001 RTU PLC Module
  • BEMAC UST-202-D Interface Board 1307D V08B2
  • Yaskawa JANCD-MMOIC-02 Drive Circuit Board
  • ABB 3BSE005028R1 SDCS-COM-1 Comm Board
  • Omron 3G3MX2-A4110 A4150 Inverter Drives Specs
  • KEYENCE CA-E100 PLC Module
  • GE IC693ALG223-GB Analog Input Module Specs
  • ABB BAILEY IMMFP01 Multi Function Processor System
  • SIEMENS 6FC5372 0AA00 0AA1 NCU 7202 Controller
  • Modicon TM241CE4 40I O Transistor Programmable Controller
  • SIEMENS 6ES7 315 2EH13 0AB0 CPU 3152 PN DP
  • NORIS A1 91 PCB Card Rack Module System
  • SIEMENS 6ES7 313 5BE01 0AB0 Compact CPU
  • SCHNEIDER ELECTRIC S144B MICROLOGIC 60A Trip Unit
  • CNI PLC269 v3 Control Module Board Rev H
  • ABB BAILEY IIMCP02 Processor Module
  • OMRON NT20S ST121 EV3 Operator Interface Terminal
  • OMRON NS-CA001 Video Input Unit
  • GE Fanuc IC695CHS012 RX3i Backplane
  • Allen Bradley 2711E-K14C6 PanelView 1400e Terminal
  • Siemens Sinamics CCB 10000432.71 Power Cell
  • Siemens 6SL3210-1SE21-8UA0 Power Module PM340
  • Yaskawa CIMR-F7A20P4 AC Drive
  • Beckhoff EP1918-0002 EtherCAT Box I/O Module
  • OMRON CQM1-TC001 Temperature Control Module
  • GE Fanuc SGHA36AT0400 Industrial Contactor
  • OMRON NJ501-1500 PLC Machine Automation Controller
  • Mitsubishi MAZAK QX084 Power Supply MELDAS 500 CNC
  • B&R 0AC808.9 PLC Automation Module
  • OMRON CP1H-XA40DT1-D PLC Module
  • G&W Electric PLC15 5111 011 15kV Capnut Assembly
  • GE DS200SLCCG3AGH PCB Circuit Board
  • Siemens SINUMERIK 6FC3981-4FD PLC Extension
  • OMRON F300-DC I/O Image Processing Unit
  • FANUC A06B-0314-B002 AC Servo Motor
  • GC-S84 Programmable Controller Logic Module
  • PASABAN MONTELEC MTC3001-DC Drive Control PLC
  • Allen Bradley 100E460EJ11 Auxiliary Contactor
  • Bosch Rexroth 1070075337-101 Card Parameters
  • HMS Anybus AB7646-F Gateway Specifications
  • Bosch 062633-303401 CNC Servo PLC Card
  • TI 500-5023 Series PLC Power Supply
  • Siemens C98043-A7002-L1-12 Circuit Board
  • Omron E5CC-RX3A5M-000 Controller
  • CN-8032-L Profinet Network Adapter Module
  • Siemens 3TK2804-0BB4 Safety Relay Details
  • Toledo TTLM-2-1M I/O Load Module
  • NORIS A1-91 PLC Rack Board Specifications
  • Mitsubishi A3ACPUR21 MELSEC PLC CPU Module
  • Beckhoff EP7041‑3002 EtherCAT Box Digital Input Module
  • REER EOS2E 1053 EOS2R 1053 Safety Light Curtain
  • Mitsubishi Q80BD-J71BR11 MELSECNET/H Interface Board
  • Omron 3G3IV-B4220-EV2 VFD 400V 22kW
  • Allen-Bradley 96844671 1785-LT3 PLC-5/12 Processor Module
  • Pasaban MTC3001-DC Drive Control PLC Module
  • Omron CJ1M-CPU11 V4.0 PLC CPU Module
  • ABB CM579-PNIO B3 Communication Module
  • B&R X20 AI 4221 Analog Module
  • Siemens 6SY7000-0AC80 PLC Module
  • GE 531X300CCHAFM5 Control Card
  • AB 810-A15C Inverse Time Relay
  • WITTENSTEIN LP120X-MF2-20 Planetary Gear
  • Mitsubishi Kakoki E-01B-4130 PLC I/O Modules
  • ABB DSQC643 Safety Control Board
  • Siemens G26004-A2105-P100-2 PCB
  • OMRON F350-C10E Image Processing Unit
  • FUJI UG430H-TS1 HMI Touch Panel
  • Westronics CB100188-01 Rev F Board
  • Siemens 7MH4900-3AA01 Weighing Module
  • Gilbert & Nash Tracker 2000 Control Cabinet
  • OMRON CJ1M-CPU22 CPU Unit
  • OMRON F3SJ-E0625P25 Light Curtain
  • Siemens 3VA2340-5HL32-0AA0 Breaker
  • Mitsubishi Melsec A61P A2NCPU PLC System
  • Aeco 158-02 DSP-02 PCB Card
  • FUJI NP1PS-32R CPU Module
  • Siemens 6SL3040-1MA01-0AA0 Control Unit CU320-2 PN
  • Fuji RYE.75D PLC Driver AC Drive
  • Electro Cam PS-6144-24-P16M09-L-MB Programmable Limit Switch
  • Siemens C98043-A7001-L2-4 CUD1 Control Board
  • Pilz 312070 PSSu H PLC1 FS SN SD Safety Module
  • Siemens Plc42q4200atsn Circuit Breaker Fuse Box
  • GE Fanuc IC695ALG708-AB Analog Output Module Rx3i
  • Siemens 6SE7036-5GK84-1JC2 IGD8 Gate Driver Board
  • Charmilles 813078 852029 PLC PCB Robocut 2 CNC EDM
  • Siemens 6SL3130-1TE24-0AA0 Smart Line Module
  • Pasaban MTC3001-DC Drive Control PLC Module
  • Modicon AS-P890-000 Remote I/O Processor Power Supply
  • Siemens PXC100-PE96.A PXC Modular Controller
  • TOYO KEIKI P:CARD5 AVH-R YH-212 Industrial Control Card
  • Omron NS5-SQ00B-V2 HMI Touch Screen 5.7 Inch
  • Sciemetric SigPOD 1202-0H00 Data Acquisition Module
  • GE Fanuc IC693CPU331W CPU Module Series 90-30
  • Square D 8903SVO11V02 Lighting Contactor 200A
  • Beckhoff C9900-P224 Power Supply Unit 24V 10A
  • HSD PE323 PLC I/O Module
  • Pillar AB6406-11A Power Control Board
  • GE Fanuc IC693CPU331W CPU Module
  • FANUC A61L-0001-0072 LCD Monitor
  • AB 20D-D-011-A-0-EYNANANE Drive
  • AB 1785-L20B PLC-5/20 Processor
  • Siemens SIREC P/PA Recorder 7ND3021
  • Siemens D2E160-AH01-17 Fan Blower
  • Eaton 101073735-001 LEG Module
  • AB 1404-M605B-ENT Powermonitor 3000
  • OMRON CJ1W-MAD42 Analog I/O
  • Omron CJ1M-CPU13 V3.0 PLC CPU Module
  • Pe323 HSD PLC Module Industrial Controller
  • Pasaban MTC3001-DC Drive Control PLC Module
  • Mitsubishi R02CPU PLC Module MELSEC iQ-R
  • B&R X20DC2395 Digital Output Module 32 Ch
  • Hoffman A30N24ALP Enclosure with PLC Addons
  • Rieter PLC with RMC 24/5V 10 RMC188-1 RMC RIO-1
  • Allen-Bradley 1790D-TN4V0 CompactBlock LDX Base Block 4 AI
  • National Instruments NI 9242 Analog Input Module 4-Channel
  • ABB AO820 3BSE008546R1 Analog Output Module
  • Moeller XVC-101-C192K-K82 PLC
  • AB 440F-C4000P MatGuard Controller
  • AB 1692-ZRCLSS Protection Module
  • Schneider S48896 PLC Module
  • FANUC A02B-0303-C205 I/O Module
  • AB 1785-LT4 PLC-5/10 Processor
  • AB 1746-NO8V SLC 500 Analog Output
  • OMRON CQM1-TC001 Temperature Unit