Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

ControlEdge HC900 Controller Communications User Guide

F: | Au:佚名 | DA:2023-11-27 | 924 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:

1. Introduction

1.1 Overview

Communication interfaces

The ControlEdge HC900 controller provides Modbus communication support on three communication interfaces.

 Network port: Modbus TCP on an Ethernet connection

 Serial Port S1 RS232/RS485 selectable port. (Default RS232.): Modbus RTU

 Serial Port S2 RS232/RS485 selectable port. (Default RS485.): Modbus RTU

View or print addresses

You can print out the Modbus addresses of various parameters of the configuration (signal tags, PID loops, SP programmer, etc.) using the HC Designer report functions. With HC Designer Ver. 2.1 and later, these reports may also be exported to .csv files for view/manipulation in a spreadsheet and possible import to other HMI applications.

Fixed map or custom map

The type of addressing available: fixed or custom.

1.2 Modbus/TCP Interface

Introduction

ControlEdge HC900 controllers support the Modbus/TCP (also called Modbus TCP/IP or Modbus Ethernet) protocol for communications with third party HMI and SCADA software via a direct Ethernet TCP/IP connection.

The controller’s Ethernet 10/100Base-T Host port is used for the Modbus/TCP connection. Ethernet TCP allows multiple concurrent connections to hosts for data interchange. The ControlEdge HC900 (C30/C50) supports 5 concurrent host connections using Modbus/TCP protocol messaging via this port; ControlEdge HC900 (C70/C70R) supports 10.

Interface Preparation

ATTENTION

To access the controller you must have a current Process Control Designer configuration file available. Some data is referenced relative to number, such as Signal Tags and Variables.

Other principal blocks, such as PID blocks, have offsets for parameter access dependent on the order in which the blocks were placed on the Function Block Diagram.

It is strongly recommended that you upload the controller configuration using the Process Control Designer configuration tool to assure that you have a current configuration.

The Process Control Designer tool provides a series of reports for use in Modbus Address identification. The "Tag Information" report lists the variables and Signal Tags in numeric order along with their Modbus Addresses. A "Block Modbus Address" report lists the starting addresses for all principal blocks configured, identifying the offset.

Modbus/TCP Protocol

Modbus/TCP protocol, developed by Groupe Schneider’s Modicon Division, is a popular, open standard for data interchange over Ethernet TCP/IP networks using a Modbus RTU command structure.

It is simply an encapsulation of Modicon’s Modbus RTU protocol within a TCP/IP frame as shown below, which includes header information and the Modbus frame.

The Open Modbus/TCP Specification is followed with respect to the physical, data link, and network layers. The message structure within the Modbus frame uses standard Modbus RTU function codes.

The Address part of the Modbus frame is not used (set to 00) since there is no sub-addressing intended or required. The controller IP address is the identifying address, set independently at the controller.

The error checking is supported by TCP/IP network protocols and not part of the Modbus frame.

The Transaction Identifiers and Protocol Identifiers in the header are normally all 0’s (4 bytes total) while the Length field identifies the number of bytes in the Modbus frame. The controller will transmit the correct number of bytes for the remainder of the frame. However, the controller does not check this field for messages received.

The standard IEEE 32-bit floating point and 16-bit integer formats are used.

Parameter Addressing

The definition in Table 6-1 is the fixed map overview listing starting and ending addresses.

Greater detail for parameter addressing relating to a particular function class (e.g, loops, setpoint programmer, signal tags) is in referenced sub-sections. Function Codes 1, 2, 3, 4, 5, 6, 8, 16 (10h), and 17 (11h) are supported (see Table 4-1 Modbus/TCP and Modbus RTU Function Codes Definitions).

Examples for read or write access to parameters supported by the various function codes are provided in Sections 4.3 through 4.11.

ControlEdge HC900 Ethernet Communications Setup

See the ControlEdge HC900 Control (HC) Designer Users Guide, Doc. # 51-52-25-110 or respective HC Designer Help Files for setting up the following network parameters:

IP Address, Subnet Mask (optional), Default Gateway IP Address (optional)

1. Be sure the PC, HMI panel, or other Host device has a Network Interface Card (NIC) with an IP address (fixed or DHCP served) that allows access to controllers on the same or other subnet. Consult your IT department or network administrator for allocating IP addresses to the controllers as required.

2. You will need to set each controller’s IP address prior to network connection since every ControlEdge HC900 controller is shipped with the default IP address of 192.168.1.254. Placing multiple controllers on the same network before they have been given unique IP addresses will cause problems.

3. On the PC, use the Utilities Worksheet in the HC Designer software to set up the serial RS-232 connection to the controller at the desired baud rate. This will require a null modem cable.

4. Select the Set Controller’s Network Parameters button. Using the wizard (bottom radio button), select the PC COM port to be used, then set the controller’s new network parameters including IP address, Subnet Mask (if other than default, 255.255.255.0), and Default Gateway IP address (if required, otherwise leave at default 0.0.0.0). See your IT network administrator for proper entries. (Refer to the on-line help provided with the HC Designer software, Utilities Worksheet, Set Controller’s Network Parameters, for further details on this step).

Note: This setup will require the controller to be placed temporarily in the Program mode. After the new network parameters have been downloaded, the controller will conduct a Cold Start in its transition to RUN. This will cause an initialization if there is a current configuration in the controller.

The fixed IP address of each controller shall be set independently prior to placing on the network. See your IT systems administrator for allocating IP addresses, subnet masks, or default gateway IP address as necessary (network address filtering and routing may be necessary if the controller network access will not to be confined locally within the plant environment).

Ethernet 10/100Base-T Network Connections

Ethernet 10/100Base-T networks operating at 10/100MB/sec. are supported. A typical network arrangement is as shown below.

Setting Up the Modbus/TCP Double Register Format

The ControlEdge HC900 predominantly uses an IEEE floating point format for communicating data to software applications providing Modbus/TCP protocol communications drivers. A floating point value is sent as (2) consecutive 16-bit registers, each register of which consists of two 8-bit bytes. Some software packages require the registers and bytes to be sent in a certain order. The controller can be configured to deliver the data in four different byte orders.

The Process Control Designer software tool allows this order to be selected as follows:

1. Using the Utilities Worksheet in the HC Designer software, access the Set Controller Network Parameters button and make the selection to change the Modbus TCP Double Register Format (middle radio button).

2. With the Port selected for downloading this order (using a COM port or Network port), select the appropriate byte order format if the default (FP B) is not appropriate for the application. See Table 3-1, page 9.

3. Select Next and verify (by the response in the dialog box) that the change has been made in the controller. This order can be changed in the RUN mode.

The Modbus TCP double register transmission format selection, FP LB “Little Endian Byte-Swapped”, would be selected for interface to most third party software packages which use this format as standard. The default, FP B “Big Endian” is used with SpecView32 or Honeywell’s PlantScape/Experion/EBI software and follows the “Honeywell” default format of other control and recording products. It should be noted that most PC software packages offer a register (word) swap selection in their driver package anyway, so there should never be an incompatibility.

1.3 Modbus RTU RS232/RS485 Communication Ports

This implementation is designed to provide a popular data exchange format connecting the ControlEdge HC900 to both Honeywell and foreign master devices via the RS232 and RS485 communication ports. The Modbus RTU allows the instrument to be a citizen on a data link shared with other devices, which subscribe to the Modicon Modbus Protocol Reference Guide PI-MBUS-300 Rev. G specification.

These instruments DO NOT emulate any MODICON type device. The Modbus RTU specification is respected in the physical and data link layers. The message structure of the Modbus RTU function codes is employed and standard IEEE 32-bit floating point and integer formats are used. Data register mapping is unique to the ControlEdge HC900 and other Honeywell instruments. Section 6 describes the parameter mapping for the ControlEdge HC900.

Summary

The SP Programmer parameters are listed according to category related to program status and interaction, other programmer parameters and program segment mapping.

In the fixed map each SP Programmer is assigned to three non-contiguous sections of the map:

 SP Programmer parameters (Table 6-9)

 SP Programmer Additional parameters (Table 6-9, page 58)

 SPP Programmer segments (Table 6-10).

In a custom map the above parameters may be contiguous.

Function Code Support:

Read – Function Code 3

Write – Function Code 16 (10 Hex)

Considerations and Methods for Downloading. Operating, and Reading Status of SP Programs

A SP programmer interface can be developed (and recipes containing a SP profile can be created) in third party software using the parameters listed in the following table.

In creating a SP Programmer interface showing a number of segments, a graphic display might include a table referencing the maximum number of ramp/soak segments that you will be using for your process. The parameters to be referenced for each segment are listed in Table 6-10.

Procedure for Downloading Setpoint Profile

These steps are for programmer 1. For programmers 2, 3, 4, 5, 6, 7, and 8 adjust the register addresses accordingly by adding offset for starting addresses.

Table 6-7 is for downloading using Function Codes 3, 4, 6, 16.

If using a custom map, you need to know the addresses of the parameters referred to in this procedure. Use HC Designer to print a report showing the Modbus registers of the SP Programmers


  • National Instruments NI 9264 Output Module
  • National Instruments IC-3173 Controller
  • National Instruments NI 9234 Vibration Module
  • National Instruments SMB-2163 DIO Accessory
  • National Instruments PXIe-1062Q DSA System
  • National Instruments USB-6289 DAQ Device
  • National Instruments NI 9233 Vibration Module
  • National Instruments PXIe-5840 VST
  • National Instruments PXI-1033 and PXI-6132 System
  • National Instruments GPIB-USB-HS+ Controller
  • National Instruments NI 9231 Sound and Vibration Module
  • National Instruments cRIO-9074 CompactRIO Controller
  • National Instruments 782536-01 DAQ Module
  • National Instruments 779781-01 DAQ Module
  • National Instruments PXIe-8388 MXI Express Controller
  • National Instruments SCXI-1520 Strain Bridge Module
  • National Instruments PCIe-6320 Multifunction DAQ Card
  • National Instruments NI 9234 Sound and Vibration Module
  • National Instruments USB-4431 Sound and Vibration Device
  • National Instruments NI 9227 Current Input Module
  • National Instruments PXI-1033 PXI Chassis
  • National Instruments NI 9213 Thermocouple Module
  • National Instruments PXI-1042 PXI Chassis
  • National Instruments PXI-6229 DAQ Card
  • National Instruments cRIO-9075 Controller
  • National Instruments PCI-6033E DAQ Card
  • National Instruments PCIe-6363 DAQ Card
  • National Instruments cDAQ-9174 Chassis
  • National Instruments PXIe-8880 PXI Controller
  • National Instruments NI 9242 Analog Input Module
  • National Instruments USB-6221 BNC DAQ Device
  • National Instruments NI 9220 Analog Input Module
  • National Instruments cRIO-9068 CompactRIO Controller
  • National Instruments PXI-4130 Source Measure Unit
  • National Instruments USB-6251 Multifunction DAQ Device
  • National Instruments PXI-8106 Embedded Controller
  • National Instruments USB-6218 Multifunction DAQ Device
  • National Instruments PCIe-1473R Camera Link Frame Grabber
  • National Instruments PXIe-4341 DSA Module
  • National Instruments PXI-8102 Embedded Controller
  • National Instruments cDAQ-9178 Chassis
  • National Instruments USB-6210 DAQ Device
  • National Instruments USB-6212 DAQ Device
  • National Instruments NI 9485 Relay Output Module
  • National Instruments NI 9208 Current Input Module
  • National Instruments PXIe-4141 SMU
  • National Instruments PCI-6154 DAQ Card
  • National Instruments cRIO-9038 Controller
  • National Instruments PCI-6133 DAQ Card
  • National Instruments LabVIEW RIO Kit 501684G
  • National Instruments PXIe-6396 Embedded Controller
  • National Instruments USB-8502 CAN Interface Device
  • National Instruments NI 9264 Spring Terminal Output Module
  • National Instruments NI 9213 Thermocouple Input Module
  • National Instruments NI-9205 Analog Input Module
  • National Instruments NI 9264 Analog Output Module
  • National Instruments USB-6212 Multifunction I/O Module
  • National Instruments PXI-4071 FlexDMM Multimeter Module
  • National Instruments NI-9208 DSUB Current Input Module
  • National Instruments PXIe-6363 X Series I/O Module
  • National Instruments NI 6587 LVDS Digital I/O Module
  • National Instruments PCI-6225 Data Acquisition Card
  • National Instruments NI-9262 Analog Output Module
  • National Instruments NI 9235 Quarter Bridge Input Module
  • National Instruments PXIe-8301 Remote Control Module
  • National Instruments PXI-4071 FlexDMM Module
  • NI-9234 Sound and Vibration Input 779680-01
  • NI 9229 Isolated Analog Input Module
  • NI cDAQ-9178 USB CompactDAQ Chassis
  • National Instruments NI 9220 143613B-06L Analog Input Module
  • NI 9229 Analog Input Module
  • NI 9246 Analog Input Module
  • NI PXIe-1071 PXI Express Chassis
  • National Instruments 9225 780159-01 Analog Input Module
  • NI cDAQ-9171 USB CompactDAQ Chassis
  • NI PXIe-8840 Embedded PXI Controller
  • Bonfiglioli A202 UH35 FIA 39.6 Right Angle Reducer
  • Bonfiglioli BN 90 LA 4 Gearmotor 1.5kW i=14.1
  • Bonfiglioli BN71A4 Motor with C313PP71 Gearbox
  • Bonfiglioli MP 130 1 4 STD 114A CD Planetary Gear Head
  • Bonfiglioli LC155 1 10 STD Gearbox
  • Bonfiglioli Vectron ACU401-13 FA Inverter
  • Bonfiglioli AEC500-31A Solar Inverter
  • Bonfiglioli BN63B6 Geared Motor VF44P
  • Bonfiglioli Vectron ACT410-23 Inverter
  • Bonfiglioli FR FRIZ 11/90 Clutch
  • Bonfiglioli A/11.90 B3 Clutch Brake
  • Bonfiglioli 50.180.3000 Servo Motor
  • Bonfiglioli NFF 14 112 EE Clutch
  • Bonfiglioli BMD 65 Permanent Magnet Motor
  • Bonfiglioli MP 080 2 20 STD 73A1 CD Planetary Gearbox
  • Bonfiglioli VF/VF30/63 P1 1520 Gearbox
  • Bonfiglioli M3SA4 FD with X F202 H35 10.0 Gearbox
  • Bonfiglioli ACU401-19A Frequency Inverter 5.5kW
  • Lafert B6306P-02276 Servo Motor with Bonfiglioli A102
  • Bonfiglioli ACU401-09FA Frequency Inverter 1.1kW
  • ProMinent Sigma S1CBH12035 with Bonfiglioli BN56B4
  • Bonfiglioli TR 080 2 20 STD Planetary Gearbox
  • Bonfiglioli ACT400-040A Frequency Inverter 15kW
  • Bonfiglioli BE 132 MA 4 Electric Motor 7.5kW
  • Bonfiglioli W86 U30 P100 Gearbox
  • Bonfiglioli MP105 2 25 Planetary Gearbox
  • Bonfiglioli BE160L4 Motor 15 kW
  • BONFIGLIOLI TMP-105 2 25 15 19 40 70 90 Planetary Gearbox
  • Bonfiglioli Vectron ACU401-18 FA Inverter
  • BONFIGLIOLI BE80B4 Motor with A302 UH35 76.5 P80 VA Gearbox
  • Bonfiglioli Vectron VCB400-180 Inverter
  • Bonfiglioli P63B14B3 Motorization Encoder
  • Bonfiglioli Vectron ACT201-13FA Inverter
  • Bonfiglioli F202 H30 P90 Gearbox
  • Bonfiglioli BN71A4 C313 P P71 Gearmotor
  • Bonfiglioli ACT201-11FA Frequency Inverter
  • Bonfiglioli ACU410-21 3 FA Inverter 7.5kW
  • Bonfiglioli RA0 60/00 Gear Reducer i=182
  • Alpha VDS 063-MF1-10-141-BE Planetary Gear 20018280
  • Stöber FDR 71B/10 Gearmotor 0.37kW
  • Stöber DW0-2000-037-4 Gearbox 0.25kW
  • Bonfiglioli M3SA4 FD R with X F252 H35 16.6 Gearbox
  • Bonfiglioli BN90LA4 Adjustable Gear Motor 1.5kW
  • Alpha LP 090-MO1-5-111-000 Planetary Gearbox
  • Bonfiglioli 335 M3 C Planetary Gear Motor
  • Bonfiglioli TR060 2 18 STD 50C CD 14 S1 OR SB KE Gearbox
  • Bonfiglioli MP1GD3036L001 Gearbox
  • Bonfiglioli BN90LA4 Gear Motor 1.5 kW
  • Bonfiglioli A302 UH35 P90 Gearbox
  • Bonfiglioli ACU410-31A5 Inverter
  • BONFIGLIOLI BMD 118 14 4500 400 165 SS TC1 RES2 P1N S1N CUS JB00013358
  • Bonfiglioli A302 UH40 P90 Reducer