Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Energy conversion process of thermal power station

来源: | 作者:佚名 | 发布时间 :2023-12-01 | 699 次浏览: | Share:

Waste heat

Nuclear reactors need to be cooled, typically with water (sometimes not directly). Using water to take energy away from a heat source requires a cold source, a process called the Rankine cycle. There is a limit to how much heat can be converted into energy through the Rankine cycle. The excess heat needs to be discharged as waste heat, which requires cooling water. Rivers are the most commonly used source of cooling water and also the site of waste heat discharge. The temperature of the waste water must be limited, otherwise it will kill the fish in the river. Hot water that is warmer than normal in the biosphere is a potential long-term hazard. In most new nuclear plants, this problem is solved by cooling towers. Wastewater is a problem for all conventional power plants, including coal, oil and gas power plants, because they rely on the Rankine cycle to generate energy. The four power plants differ only in their heat sources.

The need to limit exhaust gas temperatures will also limit power generation capacity. In extremely hot weather, when electricity use is highest, a nuclear power plant's output can drop because the cooling water in the plant becomes hotter, making it less efficient. Engineers take this into account when improving the design of a nuclear power plant, because increased cooling capacity means more money to build.

Hydropower is the use of water potential and kinetic energy into electricity to generate electricity. Hydropower plants are called hydroelectric power plants, referred to as hydropower plants, also known as hydropower stations.

The drop of water forms kinetic energy under the action of gravity, and the water is diverted from the high water source such as a river or reservoir to the low place. The pressure or flow rate of water is used to impact the turbine and make it rotate, thus converting the water energy into mechanical energy, and then the turbine drives the generator to rotate and cut the magnetic field line to produce alternating current.

Favorable aspect

Clean: Water can be a renewable energy source, basically pollution-free.

Low operating cost, high efficiency;

Power supply on demand;

Inexhaustible, inexhaustible, renewable

Flood control

Provision of irrigation water

Improve river navigation

The project will also improve the transportation, power supply and economy of the area, especially the development of tourism and aquaculture. The Tennessee River Comprehensive Development Program in the United States was the first large-scale water project to drive overall economic development.

downside

Ecological damage: increased erosion of the water flow below the dam, changes in the river and the impact on flora and fauna. However, these negative effects are predictable and mitigated. Such as reservoir effect

It is necessary to build DAMS and immigrants, and the infrastructure investment is large

In areas with large variations in precipitation seasons, electricity generation is low or even stopped during the rainy season

There is less fertile alluvial soil downstream

The working principle of nuclear power plant: Nuclear power plant is the use of nuclear fission reaction released energy, energy conversion and electricity generation.

Energy conversion situation:

1, the first way: this process is the conversion of nuclear fission energy to 1, the first way: this process is the energy conversion process of nuclear fission energy into heat energy.

2, the second circuit: this process is called the energy conversion process of heat energy into mechanical energy.

A nuclear power plant is a facility that converts nuclear energy into electricity through appropriate equipment. Nuclear power plants use nuclear reactors to replace the boilers of thermal power plants, and the special form of "combustion" of nuclear fuel in the nuclear reactor generates heat, so that nuclear energy is converted into heat energy to heat water and produce steam.

The system and equipment of a nuclear power plant are usually composed of two major parts: the nuclear system and equipment, also known as the nuclear island; Conventional systems and equipment, also known as conventional island

Nuclear power plant

Systems and equipment that convert nuclear energy released by nuclear fission into electrical energy are usually called nuclear power plants or atomic power stations. Nuclear power station is a kind of power station with high energy and low material consumption. Taking a power station with a power generation of 1 million kilowatts as an example, if coal is burned, it needs to consume about 7,000 to 8,000 tons of coal every day, and it needs to consume more than 2 million tons a year. If a nuclear power plant is used, it only consumes 1.5 tons of fissile uranium or plutonium per year, and a refueling can run continuously at full power for a year. It can greatly reduce the transportation and storage problems of fuel for power stations. In addition, during the combustion of nuclear fuel in the reactor, new nuclear fuel can also be produced. Nuclear power plants have high infrastructure investment, but lower fuel costs, lower power generation costs, and reduce pollution. By the end of 1986, 397 nuclear power plants had been built in 28 countries and regions. According to the statistics of the International Atomic Energy Agency, it is expected that 58 countries and regions will build nuclear power plants in the early 21st century, and the total number of power plants will reach 1000, the installed capacity will reach 800 million kilowatts, and the nuclear power will account for 35% of the total power generation. It can be seen that in the future for a long period of time, nuclear power will become the main energy of the power industry.

  • Alstom vajh13yf1001aba - Automatic Trip Relay 220-250 V
  • ALSTOM Servo Inverter Type:ALSPA MV 1007-IT - - 3.0 kW
  • ALSTOM Cegelec Interface Modnet 1 / MB+ Fbk Mbp S1/S - Interface Module
  • Alstom Input / Output Card I/O Module SA44647.A - Module
  • Alstom Plug-in card Input/Output module SA44650.C - Module
  • ALSTOM Adjustment Module Keypad Alspa MV1000 - Keypad
  • Alstom Operating module Keypad Alspa MV1000 - Keypad
  • Alstom Plug-In Input/Output Module Sa 45629.B - Module
  • ALSTOM Adjustment Module Keyboard Alspa MV1000 - Keyboard
  • ALSTOM Control Set - 15 V 029.069642/26472/1011 - Voltage regulator
  • Alstom Input/Output Card Module SA44650.C - Module
  • Alstom Input / Output Card I/O Module - Module
  • Alsthom Alstom Plug-In Input/Output Module SA41630 B - Module
  • ALSTOM Servo Inverter Type: ALSPA MV 1007-IT - - 3.0 kW
  • Alstom Plug-In Input/Output I/O Module SA44647.A - Module
  • Alstom Plug-In Input/Output Module Sa 45629.B - Module
  • Alstom Plug-in card Input/Output module SA46623.B - Module
  • ALSTOM Control Module Keyboard Alspa MV1000 - Keyboard
  • Alstom Plug-In Input/Output Module SA46623.B - Module
  • Alstom Plug-In Input/Output Module SA44650.C - Module
  • Alstom Plug-In Input/Output Module SA43610.E - Module
  • Alstom Insertion Card Input / Output Module SA43610.E - Module
  • Alsthom Alstom Plug-In Input/Output Module SA41630 B - Module
  • Alstom Plug-In Input/Output I/O Module - Module
  • Alstom Plug-In Input/Output Module SA46623.B - Module
  • Alstom Plug-in card Input/Output I/O module SA44647.A - Module
  • Alstom Plug-in card Input/Output I/O module SA44647.A - Module
  • Alstom Plug-in card Input/Output module SA 45629.B - Module
  • ALSTOM Alspa VF Inverter Type : VF 4004b - - 1.5 Kw
  • Alstom Plug-In Input/Output Module SA46617.B - Module
  • Alstom PS 431 - Control Unit
  • Alstom Plug-In Input/Output Module Sa 46624.A - Module
  • Alstom Plug-In Input/Output Module SA44650.C - Module
  • Alstom Plug-In Input/Output Module SA43610.E - Module
  • ALSTOM Alspa MV1000 Frequency Type : Alspa MV1032 - - 15 Kw
  • Alstom Input/Output Card Module SA46617.B - Module
  • Alstom Input/Output Card Module Sa 45629.B - Module
  • Alstom Input/Output Card Module SA46623.B - Module
  • ALSTOM Servo-Converter Type : ALSPA MV 1007-IT - - 3.0 Kw
  • ALSTOM Frequency Type : ALSPA MD2000 - 43-400 (49-460)
  • ALSTOM Servo-Converter Type : ALSPA MV 1007 - - 3.0kW
  • Alstom PS 431 - Control
  • ALSTOM Alspa Cegelec Guide Value Transmitter 029.087.176/98N115099109 - Transmitter
  • Alstom Input/Output Card Module Sa 46624.A - Module
  • ALSTOM Control Set - 15 V 029.069642/26472/1011 - Voltage regulator
  • ALSTOM Alspa Module Control Set 029.111.890/27347/1018 - Module
  • ALSTOM Alspa Module Control Set 029.063.255/25443/1044 - Module
  • ALSTOM Alspa Cegelec Module Control Set 029.063.292/25943/1008 - Module
  • ALSTOM Microverter D 4-8/500/029.130.005 - Inverter
  • Alstom ISTAT M233 M233X2GUYECAL0A - Measurement unit M233X2GUYECAL0A NEW
  • ALSTOM Alspa Cegelec Guide Value Transmitter 029.087.176/98N115099109 - Transmitter
  • Alstom Input/Output Module SA 46624.A - Plug-in card
  • ALSTOM Cegelec Interface Modnet 1 / MB + Fbk - Mbp S1/S
  • ALSTOM MAE 00-11 - 8 Channel isolated analog i/o termination panel LC11-13 24118b
  • Alstom MMLG01 137945N - Test block electric panel 715209M T&D protection and control
  • ALSTOM Mae 00-11 - Channel Isolated Analog I/O Terminal Panel LC11-13 24118b Al
  • CONVERTEAM S20X4262/50 / S20X426250 - Module
  • CONVERTEAM MV530A4C1A / MV530A4C1A - Inverter
  • CONVERTEAM C100/5302 / C1005302 - Module
  • CONVERTEAM 20X4355B1L / 20X4355B1L - (new without box)
  • CONVERTEAM GM0020002 / GM0020002 - Module
  • CONVERTEAM P111-6052 / P1116052 - Module
  • Alstom PS 431 - Controller
  • ALSTOM Type : Alspa BC 32 - Brake Chopper Unit
  • ALSTOM Alspa MV500 SE23400075/MV502A4C1A - - 0.75kW Inverter
  • Alstom M30-Tx200 DIN931 - Hexagon screw stamped 8A B screw GE Alstom SW 46
  • Alstom Sa 46624.A - Plug-In Input/Output Module
  • ALSTOM Adjustment Module Keyboard Alspa MV1000 - Keyboard
  • Alstom PA20397/2186-03-H01 - Circuit Board
  • Alstom KBCH12001H12MEL 228633J - Relay Differential KBCH120
  • Alstom MMLG01 137945N - TestBlock Electric Panel 715209M T&D Protection & Control
  • Alstom KBCH12001H12MEL 228633J - Differential Relay KBCH120
  • Alstom MMLG01 137945N - Test Block Electrical Panel 715209M T&d Protection &
  • ALSTOM Mae 00-11 - 8 Channel Isolated Analog I/O Terminal Panel LC11-13 24118b
  • Alstom KBCH12001H12MEL 228633J - Differential Relay KBCH120 and extended warranty
  • Alstom MMLG01 137945N - Test Block Electrical Panel 715209M T & D Protection & De
  • Alstom DFI-110-0340F - DFI1100340F Diagnostic Flame Indicator
  • KCGG142 KCGG14201D20EEA - 287362J
  • ALSTOM MAE 00-11 - Channel isolated analog i/o termination panel LC11-13 24118b Al
  • KCGG122 KCGG12201DEED - 463055L and extended warranty
  • Alstom MMLG01 137945N - Test Block Electrical Panel T&D Protection & Control
  • Alstom 3FAFA5100A - Voltage Sensor TN7 112 003 Alstom T&D Protection & Control
  • Used ALSTOM PIB100 F 3BEB0169 - Board
  • Alstom Keypad - Alspa MV 1000
  • Alstom MMLG01 137945N - Test Block Electrical Panel 715209M T & D Protection &
  • ALSTOM PS441 - Overcurrent protection - Used
  • Alstom Power 2506305 - Circuit Board
  • ALSTOM PS431 - CONTROL UNIT
  • ALSTOM MV502S2B1A - 1 pc X Frequency Drive Alspa MV500
  • Alstom 3VAFS5500A - Voltage Sensor TN7105 002 Alstom T&D Protection & Control
  • ALSTOM MV507A2D1A - 1 pc X Frequency Drive Alspa MV500
  • KCGG KCGG12201L20EED - 655002M and extended warranty
  • ALSTOM TRVP059753000 - AGC3X-007 BLOCK ENCODER TRVP05975400
  • KCGG KCGG14202l20EEB - 654833M and extended warranty
  • Alstom 029 204 538 - cegelec Interface RS422/RS232 Alspa MV 1000
  • ALSTOM PIB100 F - 3BEB0169 Board
  • CONVERTEAM 8321-4002 / 83214002 - (new with box)
  • CONVERTEAM MVAJ14D1GA0774A / MVAJ14D1GA0774A - Relay
  • CONVERTEAM 8178-4002 / 81784002 - (new with box)
  • CONVERTEAM QTWIE2-VD4A / QTWIE2VD4A - (new with box)
  • CONVERTEAM A48DI-40DX-B7/95 / A48DI40DXB795 - Meter
  • CONVERTEAM V96LC/0-400RPM / V96LC0400RPM - Meter
  • CONVERTEAM A72DI-5-40X4/95 / A72DI540X495 - Meter
  • CONVERTEAM 8321-4002 / 83214002 - Module
  • CONVERTEAM 029.081-942 / 029081942 - Module
  • CONVERTEAM V96LC/0-600RPM / V96LC0600RPM - Meter
  • CONVERTEAM 20X4524B1L / 20X4524B1L - Module
  • CONVERTEAM EGS3C-ST11001 / EGS3CST11001 - Module
  • CONVERTEAM S8503-4001 / S85034001 - Module
  • CONVERTEAM MVAX12B1DA0752A / MVAX12B1DA0752A - Relay
  • CONVERTEAM 11P408ND8268/7 / 11P408ND82687 - (new without box)
  • CONVERTEAM MVAJ26L1BB0502A / MVAJ26L1BB0502A - Relay
  • CONVERTEAM C100/5120 / C1005120 - Module
  • CONVERTEAM D-984-0578 / D9840578 - Board
  • CONVERTEAM GDS1017-4001 / GDS10174001 - Enhancement Card
  • CONVERTEAM MBC101F1AD0761A / MBC101F1AD0761A - Module
  • CONVERTEAM GDS1006-4001 / GDS10064001 - Keypad
  • CONVERTEAM 25X8521/10 / 25X852110 - Module
  • CONVERTEAM VSELC1011A1AB / VSELC1011A1AB - (new without box)
  • CONVERTEAM RTS-13060102-R / RTS13060102R - Relay
  • CONVERTEAM LGPG-11101P55LEF / LGPG11101P55LEF - Relay
  • CONVERTEAM 203-399 / 203399 - Module
  • CONVERTEAM MV516A4C1 / MV516A4C1 - Inverter
  • CONVERTEAM SW867577-007 / SW867577007 - Module
  • CONVERTEAM MCGG22D1CD0503D / MCGG22D1CD0503D - Relay
  • CONVERTEAM MV506A4C1A / MV506A4C1A - Inverter
  • CONVERTEAM GM0025002 / GM0025002 - Module
  • CONVERTEAM MBCI01F1AD0511A / MBCI01F1AD0511A - Module