3. Emergency use of bypass mode
In certain special circumstances (such as when it is determined that there is no explosive gas present on site), it is necessary to supply power to the interior of the system cabinet without activating the positive pressure system. At this point, the bypass function of the control unit needs to be activated: press the "BYPASS" button, enter the password "4711", and then press the "MENU" button. The flame retardant gas supply will be turned off, and "BYPASS" will flash on the screen. It should be noted that the bypass mode can only be used with the permission of the operations manager or safety officer (issuing a hot work permit, etc.) and under the supervision of a designated person. Once the normal operation is completed, the bypass must be reactivated and the password must be entered to restore gas supply, ensure that "BYPASS" is turned off, and restore normal positive pressure monitoring.
Deep maintenance and security isolation measures
The long-term reliability of positive pressure explosion-proof equipment depends on periodic professional maintenance. ABB recommends that a qualified electrical engineer conduct a comprehensive inspection at least every three years. If the system is not in continuous monitoring mode, the inspection cycle needs to be shortened.
1. The "Ten Minute" Rule for Open Cover Maintenance
When it is necessary to open the cabinet for maintenance, the power-off procedure must be strictly followed. Although the power has been cut off, there is still residual charge in the capacitors of the power module inside the cabinet. Engineers must wait for at least 10 minutes after the power is turned off, and only remove the cover plate after the capacitor is completely discharged. When conducting any live work (limited to intrinsic safety circuits), the inductance, capacitance, current, and voltage characteristics of the testing instrument must meet explosion-proof requirements, and the testing equipment itself must be checked for explosion-proof qualifications.
2. Shutdown standards and spare parts replacement
If visible physical damage, inability to turn on normally, exposure to harsh storage environments, or severe transportation stress is found during inspection, the device must be immediately shut down and locked to prevent accidental startup. When replacing components, only ABB original spare parts can be used. If components related to explosion-proof performance (such as isolation amplifiers, control boards) are replaced, they must be verified and confirmed by experts to have explosion-proof characteristics consistent with the original certificate description before being put back into operation.
3. Prediction of common hardware failures
Display and control unit protrusion: As mentioned earlier, if the keyboard area is found to be protruding, it is highly likely that the compressed air filter has failed, causing high-pressure gas to rush directly into the cabinet. At this point, it is necessary to immediately cut off the gas source and check the filter and flame retardant gas valve.
M20 cable joint sealing: During maintenance, it is necessary to check whether unused cable interfaces are sealed with original plugs and ensure that the locking nut torque reaches 2.5 Nm to prevent explosion-proof seal failure.
AO2060 analysis module bus connection: As the system bus and 24VDC cable are the core components of the positive pressure enclosure system, their length must not be reduced to less than 1 meter and must not be damaged. When disassembling and assembling metal joints, it is necessary to strictly follow the steps of flipping out the shielding layer and pushing in the plastic inserts to ensure a firm connection and good grounding.