BENDER RCMA475LY Residual Current Monitoring

F: | Au:FANS | DA:2026-10-14 | 59 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:


Type B characteristics and operating conditions

RCMA475LY complies with the Type B requirements of IEC 60755 Amendment 2 and is capable of responding to various waveform residual currents. According to the operating conditions, the tripping current range is as follows: 0.5... 1 × I Δ n when the AC residual current is 50 Hz; Pulse DC residual current, including positive and negative half waves, with a half wave current of 0.5... 1.4 × I Δ n; Phase controlled half wave current, current delay angle of 90 ° el... 135 ° el, 0.5... 1.4 × I Δ n; When half wave current is superimposed with 6 mA smooth DC, it is 0.5... 1.4 × I Δ n; The smooth DC residual current is 0.5... 2 × I Δ n. These features enable RCMA475LY to cover complex scenarios such as frequency converter output side, DC power supply, UPS battery circuit, charging device, etc.

In industrial sites, six pulse rectifiers, single-phase rectifiers with smoothing capacitors, inverters, battery chargers, construction site variable frequency drive equipment, etc., may all generate smooth DC or pulsed DC residual current. If an AC type monitor is used, the DC component may cause transformer saturation or measurement deviation, resulting in failure. The AC/DC sensitive design of RCMA475LY can effectively identify these waveforms and improve protection coverage. Its typical applications include grounded two, three, and four conductor systems, single conductor monitoring without charge under normal conditions, such as N and PE conductors, as well as variable speed drive and UPS systems.

Wiring, installation, and precautions

The wiring terminals of RCMA475LY include power supply A1, A2, external measuring instruments M+, M -, external TEST/RESET terminals T/R, alarm relay terminals 11, 12, 14, and pre alarm relay terminals 21, 22, 24. The power supply voltage should be selected according to the order information, and it is recommended to use a 6A fuse for line protection. External measuring instruments can be connected to 0... 100% display heads, and the measurement converter 9604-4241 in the attachment can provide 96 × 96 mm display. RK170 can also be used to convert 0... 400 μ A input to 0... 10 V or 0/4... 20 mA output.

During installation, the phase and N wires of the monitored circuit should pass through the internal measuring current transformer. Never pass PE conductors through measuring current transformers. If the PE line passes through the transformer, some of the residual current will return through the PE line, causing the measured value to cancel or misjudge. For single-phase circuits, L and N should pass through in the same direction; For three-phase circuits, L1, L2, L3, and N should all pass through. If only monitoring non electrified conductors, such as N or PE, the system structure and monitoring targets need to be confirmed. The equipment can be installed with screws, compact in size, and suitable for installation in distribution cabinets. The transparent cover can be sealed to prevent parameters from being mistakenly adjusted.


Front panel settings and DIP switches

On the left side of the front panel are the TEST/RESET button, Power ON, and Alarm LEDs. The LED bar chart in the middle displays scales such as 10%, 50%, and 100%. There are two potentiometers on the right: one is used to set the response delay within the range of 0... 10 s; the other is used to set the response value, which, in conjunction with DIP switches, achieves a magnification of x1... x10 mA. DIP switches are used to configure key parameters:

Switch 7: Action point of pre alarm contacts 21-22-24. Position A is 50% of I Δ n1, and position B is 100% of I Δ n1.

Switch 8: Pre alarm response delay. Delay at position A is 1 second, and delay at position B is 0 seconds.

Switch 9: Operation mode of alarm relay. Position A is normally open N/O, and position B is normally closed N/C.

Switch 10: Response range. The A position is 30 mA, and the B position is 50 mA.

Switch 11: Response delay multiplier. Position A is the set value x10, and position B is the set value x1.

When setting up, the required response value of the system should be determined first. For example, if a 300 mA alarm is required, the response range can be set to 30 mA or 50 mA, and the target value can be obtained by combining a potentiometer and a multiplier switch. The response delay should be adjusted according to the load start-up characteristics to avoid false alarms caused by motor start-up and power on of the frequency converter. It is recommended to set the pre alarm threshold to 50% in order to receive alerts during the early stages of insulation degradation. If there is strong interference on site, the delay time can be appropriately increased.


Typical application scenarios

RCMA475LY is suitable for various grounding systems. In a variable frequency drive system, there are high-frequency switches and DC components on the output side of the frequency converter, and ordinary residual current monitors may malfunction or refuse to operate. The 0... 700 Hz response range and Type B characteristics of RCMA475LY can cover this type of waveform. In the UPS system, the battery circuit may generate smooth DC residual current, and RCMA475LY can monitor the insulation status of the battery to ground. In battery chargers and rectifiers, DC side fault currents may persist, making AC/DC sensitive monitoring particularly important. At construction sites, construction equipment controlled by frequency conversion, temporary distribution boxes, handheld electric tools, etc. may generate complex residual currents, and RCMA475LY can provide reliable warnings.

  • LUST LTI Drives CCD34.024.W2.1.BR Servo Drive
  • Lust LTi Drives CDE32.008.W2.2.BR Positioning Controller
  • LTi DRiVES LSH-050-3-45-320/T1 Servo Motor
  • LUST LTI Drives CDA34.006.W1.5.BR Inverter
  • LUST LTI DRIVES VF1204S Frequency Inverter
  • Lust LTI Drives EMC100.1 Network Filter
  • LUST LTi DRIVES LSH-097-1-30-560/T1 Servo Motor
  • LTi Drives Lust CDA34.017.W3.0 Servo Controller
  • LUST LTI DRIVES CDE32.003 Frequency Inverter
  • LUST CDB34.003.C2.0.H15 Servo Drive Positioning Controller
  • LTi DRiVES SO84.076.S030.0001.2-W Servo Drive
  • LUST LTI Drives CDE32.003 Frequency Inverter
  • LUST LTI Drives CDA34.017.C2.CP Servo Controller
  • LTI Motion CDE32.004.C2.4 Servo Drive
  • LUST LTI DRIVES CDE34.017.W2.0.H18 Inverter
  • LUST LTI Drives BR-200.02.540.UR Braking Resistor
  • LTi DRiVES LR32.8 Line Reactor
  • Lust LTI Drives CDS44.032 Inverter
  • LUST LTI DRIVES CDB34.008 W2.4 Frequency Converter
  • LTI DRIVES SO84.012.1030.0000.2 Servo Drive
  • LTI SO84.024.1030.0011.2 Servo Drive Controller
  • LTi Drives SO84.076.S030.0001.2-W 52.5 kW Controller
  • LTi LUST SO84.012.1030.0000.2 Servo Drive Controller
  • LTI Drives SO84.008.0020.1070.1 Servo Controller
  • LTI Motion CDE32.004.C3.0 Positioning Controller 1.6 kVA
  • LUST LTi Drives CDB34.010C2.4 Servo Drive Controller
  • Lust LTi Drives CDD32.003.C2.0 Servo Controller
  • Lust LTi Drives CDB32.003C2.3 Servo Controller UM-8I40
  • LTi Drives SO CM-1.0003.110C.0 Control Module
  • LTI Drives GmbH LR34.44-UR Servo Drive Unit
  • LTI DRIVES VF1202S Frequency Inverter
  • LTi ServoOne Junior SO24.004 Servo Drive
  • Lust CDA34.003 C1.4 LTI Servo Drive
  • LUST LTi Drives CM-CAN1 Communication Module
  • LUST LTi Motion CDB22.004 CDB2000 Drive
  • LUST Lti Drives CDE32.003 Frequency Drive
  • LTI VF1406M.C9.PT1.BR1 Frequency Drive
  • LUST LTI Drives CDA34.006 W3.0 Servo Drive
  • Lust LTI Drives CDA34.017.C2.CP Servo Controller
  • LTi DRiVES LST-097-5-30-560/T1 Servo Motor
  • LTi Drives LSH-050-2-45-320/T1 Servo Motor 4500rpm
  • LUST LTI Drives VF1204S G10 FA VFD 0.75 kW 230VAC
  • LTi Drives LST-097-3-30-560/T1 1R Servo Motor
  • LTI Servo One Junior SO22.003.0082.0000.0 Controller
  • LTI Drives GmbH SO22.003.0042.0000.0 Servo Controller
  • LUST LTi CDB32.004.C2.4.SH Servo Drive 24-48V
  • LTi Drives LST-097-5-30-560/T1 1R Servo Motor
  • LUST LTI Drives CM-CAN1 3084464 Communication Module
  • LUST LTi Drives CDE32.003.C2.3 Positioning Controller 230V
  • LUST LTi Drives SO84.020.0020.0000.2 Servo One 20A
  • LTI DRiVES CDB34.003 Servo Drive
  • LTI DRiVES CDE34.010 D2.4 Frequency Inverter
  • LTi DRiVES BR-090.03.540-UR Braking Resistor
  • LTI SO84.012 Servo Drive
  • LTi Drives LSH-050 Servo Motor
  • LTi Drives SO84.004 Servo Controller
  • LTI DRiVES LSN-127 Servo Motor
  • LUST CDA34.006 W3.0 Servo Controller
  • LTi DRiVES SO84.004 Servo Drive
  • LUST LTi DRiVES LST-097-3-30-560/T1.1R Servo Motor
  • LTi Drives CDE32.003.C2.4 Software LBXR41024B014
  • LTI Motion Servo One SO84.006.0173.1100.1 Controller
  • LTi Drives LSH-074-2-30-320/T1 G6.1M Servo Motor
  • LUST CDB22.004.0111.00.0 LTi Drives Servo Controller
  • Lust So84.012.0030.1700.2 LTi Drives Servo Controller
  • LTi Drives Lust VF1204S G10 FB I6 M3 Drive Module
  • LTI Drives GmbH SO84.008.0020.0000.2 Servo Controller
  • Lust CDA34.006.C2.0 LTI Drives Servo Controller 2.2 kW
  • LTi Drives Lust CDA34.017.W3.0 Control Unit 7.5 kW
  • LTi Drives CDE34.010 Positioning Controller 10A
  • Lust LTi Drives CDA34.010 W3.0 Frequency Inverter
  • LTi SO22.003.0010.0000.0 ServoOne Junior Drive
  • LUST LTi Drives CDA32.008 Servo Drive
  • LUST LTi DRIVES LSH-074 Servo Motor
  • Lti CDB32.004.C2.4.SH AC Servo Drive
  • Lust LTi Drives VF1202S Frequency Inverter
  • Lust LTI Drives CDB32.004.C3.0.SH Servo Controller
  • LUST SO84.012.0030.1700.2 Servo Drive
  • Lust LTi CDB32.004 Servo Drive
  • LUST LTI Drives CDA34.006 Servo Drive
  • LTi DRiVES BR-090.03.540-UR Braking Resistor
  • Lust LTI Drives CDA34.017 Servo Controller
  • Lust LTi Drives CDE34.010.D2.4 Positioning Controller 10A
  • LTi Drives LSH-050-3-30-48/T1 PM Servo Motor
  • LTI CDD34.005.C2.1 Servo Drive Controller
  • LUST LTI Drives CDB32.003.C2.4 Servo Drive
  • LTI D-35633 Drive Servo Drive Controller
  • LTI Drives GmbH SO22.003.0042.0000.0 Servo Controller
  • LTi Drives SO84.006.1030.0000.2 Servo Controller
  • LUST LTi Drives CDA32.008 C1.4 HF V180.15 1.5 kW
  • LTI Drives Servo One SO84.045.0010.0001.2-W 22 kW
  • Lust LTI CDE32.003.C2.4 Servo Drive Controller
  • LUST LTI Drives CDA34.003 Servo Controller
  • LUST LTI Drives CDA32.006 Servo Controller
  • Lust LTi Drives CDE32.004 Servo Drive
  • LUST LTi Drives SO84.012 Servo Controller
  • LTI DRIVES LSH-060 Servo Motor
  • LUST LTI Drives CDE32.004 with CM-DPV1
  • LTi DRiVES SO84.016 Servo Drive
  • LTI Drive CM-DPV1 Communication Module
  • LTi DRiVES DSM4-05.4-20R82-400 Servo Motor
  • LUST LTI Drives CDA34.003 Servo Controller
  • LTI Drives Servo One SO84.045.0010.0001.2-W 22 kW
  • LUST LTI Drives CDB32.008 W2.4 BR PC1 Servo Drive
  • LTi Drives SO84.006.1030.0000.2 Servo Controller
  • LTI DRIVES CDE34.010D2.4 Servo Drive Controller
  • Hettich Rotanta 46 RSC Control Board VF1204S
  • Lust LTI Drives CDA34.017.C2.CP Servo Controller 7.5 kW
  • LUST LTI Drives CDA34.003.C3.0 Servo Controller 0.75 kW
  • Lust LTI Drives CDA34.008.C1.3 Servo Controller 3 kW
  • Lust LTi Drives CDB22.004.0111.00.0 Servo Drive
  • LTi Drives SO84.032.0030.1000.2 Servo Controller
  • LUST LTi CDA32.004 C1.4 H08 B0 Servo Controller
  • LTI DRIVES CDB34.010 C2.4 Servo Drive
  • LUST LTi Drives CDA32.008 C1.4 Servo Controller
  • LTI Motion CDE32.003.C3.0 Servo Positioning Controller
  • LTI DRIVES CDE34.010 D2.4 Servo Drive Unit
  • LUST LTi Drives CDD34.005.C2.1 Servo Drive
  • LTi Drives SO84.012.0002.0100.2 Servo Controller
  • LUST LTi Drives CDE34.010.D2.4 Servo Drive
  • LUST LTI Drives CDF30.008 Servo Drive
  • LTi Drives SO CM-P.0010.11.00.0 Power Module
  • LTi DRiVES SO84.008.0002.0100.2 Servo Controller
  • LTI MOTION Servo Drive SO22.006.0040.1000.1
  • LTi DRiVES SO24.007.0030.1000.0 ServoOne Junior
  • LTi DRiVES LUST BC1300 Braking Module
  • LUST LTI DRIVES CDE34.010 Variable Frequency Drive
  • LUST LTI DRIVES CDA32.004 Servo Drive