Equipment Overview and Functional Positioning
The BE1-51 time overcurrent relay launched by Basler Electric is a digital protection relay designed based on a microprocessor, specifically designed for overcurrent protection in 50Hz or 60Hz power systems. This relay can monitor the AC current of single-phase, two-phase with neutral wire, or three-phase with neutral wire, providing accurate time overcurrent and instantaneous overcurrent protection functions. BE1-51 adopts a pull-out chassis structure and is installed in a standard power cabinet. It supports two installation methods: semi embedded or protruding, and can be matched with a test plug (Basler Electric part number 10095) to achieve on-site testing without disconnecting wires.
Compared with traditional electromagnetic overcurrent relays, the core advantage of BE1-51 lies in its highly flexible timing characteristic selection - by selecting different timing options (Z1, Z2, Z3), users can obtain up to 69 different overcurrent characteristic curves, covering inverse time limit, I ² t, BS142 standard curve, and integrated algorithm curve, greatly expanding the adaptability of relays.
Core technical specifications
2.1 Inductive input and measurement accuracy
BE1-51 provides multiple sensing input ranges, and continuously adjustable overcurrent start value settings are achieved through panel TAP selection switches and TAP CAL calibration potentiometers
5A CT input: low range 0.5~4.0A, high range 1.5~12.0A
1A CT input: low range 0.1~0.8A, high range 0.3~2.4A
The three-phase neutral wire model can also be combined with different ranges (such as high phase current range and low neutral wire range) to adapt to diverse on-site CT configurations. The time overcurrent startup accuracy is ± 2% of the set value. When the TAP CAL potentiometer is turned clockwise to its maximum, the actual startup value is within ± 5% of the panel TAP gear value. Exit ratio is better than 92% of the startup value. The starting value of the instantaneous overcurrent component can be continuously adjusted between 1-40 times the overcurrent starting value, with an accuracy of ± 2% and an exit ratio better than 98%.
2.2 Output contacts and target indication
The rated values of the output contacts are as follows:
Resistive load: capable of connecting/disconnecting/continuous current of 7A at 120Vac; capable of connecting 30A (0.2s), continuous current of 7A, and disconnecting 0.3A at 250Vdc
Inductive load (L/R=0.04): capable of breaking 0.3A at 120Vac, 125Vdc, and 250Vdc
The target indicator can be selected as internal excitation type or current excitation type (with at least 0.2A current flowing through the output circuit). The current excitation type target has been upgraded from an electromagnetic flipping indicator to an electronic latch LED indicator in products after August 2007, with power-off memory recovery function - after the power supply is interrupted, the previously latched target state will automatically recover after the power supply is restored, greatly improving the convenience of fault tracing.
2.3 Power Supply and Electromagnetic Compatibility
BE1-51 offers five power options, covering a wide range of inputs from 12~280Vdc and 90~270Vac, suitable for DC or AC power supply conditions in different power stations around the world. The power supply adopts an electrical isolation design with no polarity requirements. In terms of electromagnetic compatibility, the relay has passed the surge withstand capability (SWC) test of ANSI/IEEE C37.90.1-1989 and meets the dielectric withstand voltage requirements of IEC 255-5 and ANSI/IEEE C37.90 (all circuits to ground 2121VDC, input to output 1500Vac or 2121VDC).

Control panel and operating components
The front panel of BE1-51 integrates all operational control and status indicator components (see manual Figure 2-1):
TAP selector (A~J, 10 bit BCD dip code): Select the reference value for starting phase overcurrent
TAP CAL potentiometer (single turn): finely adjust the startup threshold between the selected TAP gear and the next gear
TIME DIAL selector (00~99): Set the multiple for over casting
INST 1/INST 2 control (four turn potentiometer): Set the action threshold of the first/second instantaneous overcurrent component separately (1-40 times the TAP value)
Target indicator (LED): Phase/neutral line component target, timing function target, instantaneous 1/2 function target
PUSH-TO-ENERGIZE test button (recessed): Press with a non-conductive thin rod to directly drive the output relay for external circuit testing
Neutral wire related control (only for models with neutral wire): NEUTRAL TAP selector, NEUTRAL CAL potentiometer NEUTRAL TIME DIAL、NEUTRAL INST 1、 And NEUTRAL DEFEAT switch (disable neutral overcurrent protection when enabled, LED indicates status)
There is also a time overcurrent characteristic curve selection switch (limited to Z1/Z2/Z3 timing options) and a normal/test sliding switch (only for factory calibration, must be placed in the "normal" position during operation, facing towards the back of the relay) on the right internal circuit board.