Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Basler BE1-51 Time Overcurrent Relay Debugging Guide

F: | Au:FANS | DA:2026-06-23 | 14 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Basler BE1-51 Time Overcurrent Relay: A Complete Guide to Principles, Testing, and Field Applications

Equipment Overview and Functional Positioning

The BE1-51 time overcurrent relay launched by Basler Electric is a digital protection relay designed based on a microprocessor, specifically designed for overcurrent protection in 50Hz or 60Hz power systems. This relay can monitor the AC current of single-phase, two-phase with neutral wire, or three-phase with neutral wire, providing accurate time overcurrent and instantaneous overcurrent protection functions. BE1-51 adopts a pull-out chassis structure and is installed in a standard power cabinet. It supports two installation methods: semi embedded or protruding, and can be matched with a test plug (Basler Electric part number 10095) to achieve on-site testing without disconnecting wires.

Compared with traditional electromagnetic overcurrent relays, the core advantage of BE1-51 lies in its highly flexible timing characteristic selection - by selecting different timing options (Z1, Z2, Z3), users can obtain up to 69 different overcurrent characteristic curves, covering inverse time limit, I ² t, BS142 standard curve, and integrated algorithm curve, greatly expanding the adaptability of relays.


Core technical specifications

2.1 Inductive input and measurement accuracy

BE1-51 provides multiple sensing input ranges, and continuously adjustable overcurrent start value settings are achieved through panel TAP selection switches and TAP CAL calibration potentiometers

5A CT input: low range 0.5~4.0A, high range 1.5~12.0A

1A CT input: low range 0.1~0.8A, high range 0.3~2.4A

The three-phase neutral wire model can also be combined with different ranges (such as high phase current range and low neutral wire range) to adapt to diverse on-site CT configurations. The time overcurrent startup accuracy is ± 2% of the set value. When the TAP CAL potentiometer is turned clockwise to its maximum, the actual startup value is within ± 5% of the panel TAP gear value. Exit ratio is better than 92% of the startup value. The starting value of the instantaneous overcurrent component can be continuously adjusted between 1-40 times the overcurrent starting value, with an accuracy of ± 2% and an exit ratio better than 98%.

2.2 Output contacts and target indication

The rated values of the output contacts are as follows:

Resistive load: capable of connecting/disconnecting/continuous current of 7A at 120Vac; capable of connecting 30A (0.2s), continuous current of 7A, and disconnecting 0.3A at 250Vdc

Inductive load (L/R=0.04): capable of breaking 0.3A at 120Vac, 125Vdc, and 250Vdc

The target indicator can be selected as internal excitation type or current excitation type (with at least 0.2A current flowing through the output circuit). The current excitation type target has been upgraded from an electromagnetic flipping indicator to an electronic latch LED indicator in products after August 2007, with power-off memory recovery function - after the power supply is interrupted, the previously latched target state will automatically recover after the power supply is restored, greatly improving the convenience of fault tracing.

2.3 Power Supply and Electromagnetic Compatibility

BE1-51 offers five power options, covering a wide range of inputs from 12~280Vdc and 90~270Vac, suitable for DC or AC power supply conditions in different power stations around the world. The power supply adopts an electrical isolation design with no polarity requirements. In terms of electromagnetic compatibility, the relay has passed the surge withstand capability (SWC) test of ANSI/IEEE C37.90.1-1989 and meets the dielectric withstand voltage requirements of IEC 255-5 and ANSI/IEEE C37.90 (all circuits to ground 2121VDC, input to output 1500Vac or 2121VDC).

Control panel and operating components

The front panel of BE1-51 integrates all operational control and status indicator components (see manual Figure 2-1):

TAP selector (A~J, 10 bit BCD dip code): Select the reference value for starting phase overcurrent

TAP CAL potentiometer (single turn): finely adjust the startup threshold between the selected TAP gear and the next gear

TIME DIAL selector (00~99): Set the multiple for over casting

INST 1/INST 2 control (four turn potentiometer): Set the action threshold of the first/second instantaneous overcurrent component separately (1-40 times the TAP value)

Target indicator (LED): Phase/neutral line component target, timing function target, instantaneous 1/2 function target

PUSH-TO-ENERGIZE test button (recessed): Press with a non-conductive thin rod to directly drive the output relay for external circuit testing

Neutral wire related control (only for models with neutral wire): NEUTRAL TAP selector, NEUTRAL CAL potentiometer NEUTRAL TIME DIAL、NEUTRAL INST 1、 And NEUTRAL DEFEAT switch (disable neutral overcurrent protection when enabled, LED indicates status)

There is also a time overcurrent characteristic curve selection switch (limited to Z1/Z2/Z3 timing options) and a normal/test sliding switch (only for factory calibration, must be placed in the "normal" position during operation, facing towards the back of the relay) on the right internal circuit board.


Detailed explanation of overcurrent characteristic curve

The core technological value of BE1-51 lies in its rich temporal characteristic library. According to different timing options, the available characteristic curves can be divided into three categories:

4.1 Non integral timing (Z1, Z2 options)

B1~B7: Seven standard inverse time curves: short inverse time limit, long inverse time limit, definite time limit, medium inverse time limit, inverse time limit, even inverse time limit, and extreme inverse time limit

B8: I ² t curve

C1~C8: I ² t with limit range 1~8 (Z1 option only)

E2/E4/E5/E6/E7: BS142 standard curve (Z2 option only), including long inverse time, inverse time, very inverse time, and extreme inverse time

4.2 Integral timing (Z3 option)

The Z3 option uses an integral algorithm to simulate the operating characteristics of an electromagnetic overcurrent relay. Its timing curve corresponds one-to-one with the Z1/Z2 standard curve, but is implemented through time incremental accumulation - it only acts when the accumulated "energy" during the overcurrent duration reaches the preset threshold. This characteristic is closer to the thermal memory effect of traditional electromechanical relays.

4.3 Extended Timing

When selecting the 2-D or 2-E option, the standard delay is multiplied by approximately 5.7 times, which is suitable for cascading protection scenarios that require longer delay coordination.

All curves can be interpolated and selected from the 100 possible curves in each curve chart using the TIME DIAL (00~99) on the front panel. Appendix A shows the trends of each characteristic family with 14 representative curves. Users can switch between up to 16 types of curves through the 16 bit selector switch on the internal circuit board on the right.


Installation and wiring points

BE1-51 adopts the standard S1 chassis size. Attention should be paid during installation:

The grounding terminal at the rear of the chassis must be hard grounded to the ground with a copper wire of not less than 12 AWG

When unplugging the connection plug (1 10 terminal chassis, 2 20 terminal chassis), disconnect the normally open trip circuit first, short-circuit the normally closed circuit first, and then disconnect the power supply and induction circuit to ensure that the CT does not open circuit

The external trip circuit must be disconnected through the 52a contact to prevent inductive overload of the relay contacts

Wiring wire not less than 14 AWG

For equipment that is stored for a long time (as a backup) and contains long-life aluminum electrolytic capacitors, it is recommended to run the capacitor on power for 30 minutes every year to extend its lifespan.

Complete process of on-site testing and calibration

6.1 Test Preparation

Required equipment: Suitable AC/DC power supply, 50/60Hz current source, DC external power supply (for output circuit and timer input), relay protection tester capable of outputting 40A or more, timer, shunt resistor (to provide minimum load current for the target). Connect the test circuit according to the induction input type (K single-phase, G three-phase, H/V three-phase with neutral wire, I/X two-phase with neutral wire) as shown in Figure 5-1~5-4 of the manual.

6.2 Time overcurrent startup test

Set TIME DIAL to 99, INST 1/2 to maximum (clockwise), TAP CAL to maximum (clockwise)

Select A gear for TAP and slowly increase the current until the TIMING indicator light is just on (first adjust CAL counterclockwise until the light is on, then clockwise to the maximum, and then increase the current until the light is on)

Record the starting current value (should be within ± 5% of the TAP A value)

TAP selects J gear for repeated testing and records the maximum starting point (which should be within ± 5% of the J gear value)

Repeat the above steps for each phase and neutral wire model of multiphase/neutral wire

6.3 Timing output accuracy test

TAP selects B mode, TIME DIAL is set to 20

Apply an overcurrent of 5 times the precise TAP B value and start the timer

Find the intersection point between the 5-fold point on the corresponding characteristic curve and the TIME DIAL=20 curve, and read the theoretical delay

The actual timing reading should be within ± 5% of the theoretical value

Time DIAL is set to 40, 60, and 99 for repeated testing

For models with neutral wires, the test signal should be connected to the neutral wire input terminals (17, 18) and the above steps should be repeated

6.4 Transient Overcurrent Start Test

INST 1 is adjusted to the minimum (counterclockwise), corresponding to a startup value of 1 times the TAP A gear value

Slowly increase the current to the output relay of INST 1 and record the current (should be ≤ TAP A value)

INST 1 is adjusted to maximum (clockwise), corresponding to a startup value of 40 times the TAP A gear value

Slowly increase the current from 35 times to the relay action, and record the current (should be>40 times the TAP A value)

Repeat the test on neutral line INST 1 (if any) and INST 2 (if any)

6.5 On site precise calibration steps

If the target startup value falls between the TAP gears, or if the device is equipped with an instantaneous overcurrent option, it is recommended to calibrate accurately on the test bench according to the following steps:

Connect the test bench according to the induction type and use the TIMING indicator light as the start indicator (no output terminal is required)

Apply target starting current

TAP selects the gear closest to the target value and slightly higher, and TAP CAL rotates clockwise to the maximum

After applying current, slowly adjust the TAP CAL counterclockwise until the TIMING indicator light just turns on - completing the startup value calibration

Same operation for neutral wire (for models with neutral wire)


Common troubleshooting guide

Troubleshooting direction

The relay cannot be powered on to check if the voltage at the power terminal meets the nominal/range value of the selected power option (see Table 1-1); Check polarity (DC input has no polarity requirement but needs to be within the range)

TIMING indicator does not light up. Check if the induction input wiring is correct (high/low range terminals); Is TAP CAL in the correct position; Is the neutral wire DEFEAT switch mistakenly set to ON

The position of the timing accuracy out of tolerance confirmation curve selection switch is consistent with the selected curve; Does TIME DIAL correspond to the correct curve family; Test whether the current is accurate to 5 times the TAP value

Whether the momentary component does not move or moves too early, and whether the control potentiometer drifts due to vibration; Check if it is a four turn potentiometer (multiple turns are required to cover the full range)

The target does not maintain a current excitation type target and requires an output circuit of at least 0.2A; check if the target reset switch is stuck; Is the target state recovery function normal after power interruption

Communication/test plug issues: When using the Basler 10095 test plug, it is necessary to confirm that it fits well with the chassis terminals and whether the circuit switching timing is normal when the plug is unplugged


Maintenance and storage recommendations

BE1-51 does not require regular preventive maintenance, but it is recommended to conduct a functional spot check once a year, especially for the validation of start-up values and timing accuracy. For long-term stored backup equipment, due to the presence of aluminum electrolytic capacitors inside, powering on for at least 30 minutes per year can effectively extend the lifespan of the capacitors. If the device malfunctions, please contact Basler Electric technical support to arrange repairs and do not disassemble the circuit board by yourself.

  • OMRON C60H C6DR DE V1 Sysmac PLC
  • MITSUBISHI ELECTRIC A2ACPU21 S1 CPU Module
  • ABB BAILEY INNPM12 Network Process Module
  • HONEYWELL 620 0073C IPC PLC Module
  • Mitsubishi 15050 PR02B PLC Circuit Board
  • SIEMENS 6SY7000 0AC37 Drive Control Module
  • OMRON TJ2 ECT16 Traxial EtherCAT Controller
  • GE Fanuc IC698PSD300D Power Supply Module
  • Texas Instruments Series 505 16 Position Base
  • OMRON YASKAWA SGDH 10DE OY Servo Drive
  • Allen‑Bradley 440G-MT Safety Interlock Switch Specs
  • Rubycon PD27A 24V 8A Power Supply Module
  • SK-H1-GDB1-F11D PLC Gate Driver Board Kit
  • VIPA 441-4UA14 451-4UA14 PLC Module Rack
  • Mitsubishi FX5U-80MT ESS PLC Controller Specs
  • Mitsubishi Q64TCRTN Temperature PLC Module
  • GE 1C31170G Rev10 PLC Circuit Board Module
  • Schneider TWDLMDA40DTK PLC Controller Module
  • Omron FQM1-MMA22 Motion Control Module Specs
  • OMRON CJ1W-NCF71 Position Control Unit Specs
  • Schneider TSXETY4103 Ethernet Module
  • Mitsubishi Q12PHCPU Process CPU
  • Yaskawa 3G3HV-A4022-CE AC Drive
  • Cincinnati Milacron 3-533-0669G Temperature Control Board
  • Allen Bradley 20AC030A3AYNANC0 PowerFlex 70 Drive
  • Siemens 6ES7314-6BG03-0AB0 CPU 314C-2 DP
  • Carrier 17EX54007903 PLC Module
  • OMRON CS1W-V600C12 ID Controller Module
  • Honeywell 51402755-100 PCB Card
  • Heidenhain ECN 113 Rotary Encoder
  • OMRON B7AM-8B16 I/O Terminal Block
  • Fanuc A06B-6110-H026 Power Supply Module
  • Schneider TSXETG3021 Ethernet Gateway
  • OMRON CS1W-CLK21-V1 Controller Link Unit
  • NP1W6406T-Z704 PLC I/O Module
  • OMRON CJ1W-DA08C Analog Output Module
  • Yaskawa 3G3HV-A4022-CE AC Drive
  • OMRON NB7W-TW01B CP1L-EL20DR-D Power Panel
  • OMRON C500-NC103-E Position Control Unit
  • Steag Hamatech PLC DCS Servo Control System
  • Siemens 6SN1123-1AA00-0DA1 Power Supply Module
  • GE IC693CHS391H CPU & AD693CMM301A PLC Module
  • Siemens 6FC5303-0AF23-1AA1 PLC Control Panel
  • Square D CM4000T PowerLogic Circuit Monitor J1 F16
  • Siemens 6FX5002-5DG10-1BA0 MOTION-CONNECT 500 Cable
  • Schmersal SRB324ST 101195504 Safety Relay 24V
  • Mitsubishi 15050-PR02A PLC Circuit Board Module
  • OMRON CQM1-AD041 Analog Input PLC Module
  • Beckhoff EL5042 EtherCAT PLC Terminal Module
  • OMRON C200HW-MC402-E Motion Control Unit
  • C36TC0UA1100 Industrial Temperature Controller
  • NL8048BC24 12 Industrial Control LCD Module
  • OMRON R88D Servo Drive and Motor System
  • OMRON CS1W CLK21 V1 Controller Link Module
  • OMRON YASKAWA R7M A20030 S1 D Servo Motor
  • SIEMENS 6AV2128 3KB06 0AX1 Unified Comfort Panel
  • Schneider Electric METSEPM8240 PowerLogic Meter
  • Advanced AMCI 1PLC 1 31F Programmable Limit Switch
  • ABB PM582 ETH Programmable Logic Processor
  • SIEMENS 6FC5110 0CB01 0AA0 CPU Control Board
  • Schleicher P03GS13A CPU Module
  • Siemens 6SN1123-1AA00-0BA1 Power Module
  • Mitsubishi A1S61PN Power Supply Module
  • Yaskawa CPS-IONB DC Power Supply Module
  • Siemens 6ES7215-2BD00 CPU 215-2
  • Mitsubishi A2ACPU MELSEC PLC System Kit
  • ProSoft 3150-MCM Communication Module
  • Mitsubishi OSE104ET Incremental Encoder
  • OMRON CJ1W-AD081-V1 Analog Input Module
  • Broadcom BCM5464A1KRB Quad Port Ethernet IC
  • Modicon M221-24IO TM221C24 PLC 24 PNP Transistor
  • Allen-Bradley 1321-3R160-B Line Reactor 3R160B
  • Beckhoff CX1020-0012 Embedded PLC Module Specs
  • Turck BL20-PF-24VDC-D Power Feed Module Specs
  • Siemens 6SY7000-0AC37 Power Supply Module
  • Yaskawa SGDH-10DE-OY 1kW 400V Servo Drive Specs
  • Omron 3G3SV-BB015-E 1.5kW 220V VFD Specs
  • Uni-Pro CPU91-PLC J 23.020167X Processor Module
  • PASABAN MTC-3044 PLC Rack Power Supply 4835-A
  • XYCOM 3015T Operator Interface Panel BIN4.4.4
  • OMRON CJ1W-MD261 Mixed I/O Module
  • Omron NJ301-1100 PLC CPU eCat EIP Specs
  • Omron F500-C15-ETN Vision System PLC Module
  • Modicon M241-24IO TM/T2UK PLC with Ethernet
  • SIXNET YS-800-001 RTU PLC Module
  • BEMAC UST-202-D Interface Board 1307D V08B2
  • Yaskawa JANCD-MMOIC-02 Drive Circuit Board
  • ABB 3BSE005028R1 SDCS-COM-1 Comm Board
  • Omron 3G3MX2-A4110 A4150 Inverter Drives Specs
  • KEYENCE CA-E100 PLC Module
  • GE IC693ALG223-GB Analog Input Module Specs
  • ABB BAILEY IMMFP01 Multi Function Processor System
  • SIEMENS 6FC5372 0AA00 0AA1 NCU 7202 Controller
  • Modicon TM241CE4 40I O Transistor Programmable Controller
  • SIEMENS 6ES7 315 2EH13 0AB0 CPU 3152 PN DP
  • NORIS A1 91 PCB Card Rack Module System
  • SIEMENS 6ES7 313 5BE01 0AB0 Compact CPU
  • SCHNEIDER ELECTRIC S144B MICROLOGIC 60A Trip Unit
  • CNI PLC269 v3 Control Module Board Rev H
  • ABB BAILEY IIMCP02 Processor Module
  • OMRON NT20S ST121 EV3 Operator Interface Terminal
  • OMRON NS-CA001 Video Input Unit
  • GE Fanuc IC695CHS012 RX3i Backplane
  • Allen Bradley 2711E-K14C6 PanelView 1400e Terminal
  • Siemens Sinamics CCB 10000432.71 Power Cell
  • Siemens 6SL3210-1SE21-8UA0 Power Module PM340
  • Yaskawa CIMR-F7A20P4 AC Drive
  • Beckhoff EP1918-0002 EtherCAT Box I/O Module
  • OMRON CQM1-TC001 Temperature Control Module
  • GE Fanuc SGHA36AT0400 Industrial Contactor
  • OMRON NJ501-1500 PLC Machine Automation Controller
  • Mitsubishi MAZAK QX084 Power Supply MELDAS 500 CNC
  • B&R 0AC808.9 PLC Automation Module
  • OMRON CP1H-XA40DT1-D PLC Module
  • G&W Electric PLC15 5111 011 15kV Capnut Assembly
  • GE DS200SLCCG3AGH PCB Circuit Board
  • Siemens SINUMERIK 6FC3981-4FD PLC Extension
  • OMRON F300-DC I/O Image Processing Unit
  • FANUC A06B-0314-B002 AC Servo Motor
  • GC-S84 Programmable Controller Logic Module
  • PASABAN MONTELEC MTC3001-DC Drive Control PLC
  • Allen Bradley 100E460EJ11 Auxiliary Contactor
  • Bosch Rexroth 1070075337-101 Card Parameters
  • HMS Anybus AB7646-F Gateway Specifications
  • Bosch 062633-303401 CNC Servo PLC Card
  • TI 500-5023 Series PLC Power Supply
  • Siemens C98043-A7002-L1-12 Circuit Board
  • Omron E5CC-RX3A5M-000 Controller