The device supports IRIG-B time synchronization and can accept modulated or demodulated signals for precise timing. The internal clock can also be manually set without IRIG-B, but it is recommended to stop the clock during long-term shutdown to extend battery life.

Key points of tuning and configuration
System parameter settings are the foundation of tuning. It is necessary to correctly input the rated voltage (50-140V), rated current (0.5-6A), CT and VT ratio, VT wiring method (line voltage/phase voltage/line voltage to phase voltage), phase sequence (ABC/ACB), etc. It is particularly important to note that when the VT wiring is line ground and the secondary voltage is 69V, the "line ground to line conversion" method should be selected. At this time, the device will automatically calculate the line voltage for voltage sensitive functions.
The fixed value configuration file supports four groups and can be switched through HMI, communication, programmable logic, or control/status input. The protection function will be interrupted for about 1 second during switching, which needs to be considered during system operation. The function of copying activity configuration files can quickly create new fixed value groups and reduce duplicate inputs.
IPSlow provides 6 sets of logic schemes that can be programmed using IPSgom software. The logical input sources include output contacts, function start/trip, control/status inputs, and communication triggers. Logic gates can be selected as AND, OR, NAND, or NOR. The output can be used for export tripping, switching constant value groups, or as input for other functions. Each fixed value group can be configured with 6 sets of logic, and up to 24 logic schemes can be implemented in four fixed value groups.
The circuit breaker monitoring (BM) function estimates the wear of circuit breaker contacts by integrating current (IT) or current squared (I ² T). The cumulative value is calculated separately by phase, and an alarm can be triggered when it exceeds the set threshold. The preset accumulator function allows for continued accumulation from the current wear value after replacing the circuit breaker.
Trip circuit monitoring (TC) determines circuit integrity by monitoring the continuity of the trip coil circuit. When the output contact is disconnected, if a small current flows through the TC input, it indicates that the circuit is intact; If there is still no current in the TC input after the output contact is closed, it indicates that the contact is not closed. It should be noted that the TC input voltage level can be selected through jumper wires (24/48/125/250V dc) and must match the actual tripping coil voltage.
Debugging and testing methods
The device has been precisely calibrated at the factory and generally does not require recalibration after on-site installation. But for the 64F Field Ground function, it is recommended to perform system calibration to compensate for cable capacitance effects when the cable length exceeds 100 feet. Automatic calibration can be initiated through HMI or IPScom, simply enter the reference voltage and current according to the prompts.
Functional testing should be carried out item by item according to the steps in the device manual. Before testing, it is necessary to confirm that all tested functions have been activated, and other functions are temporarily disabled to avoid misoperation. During testing, use a three-phase voltage source and a current source, and connect them according to the testing configuration diagram for each function. The phase angle relationship between voltage and current needs special attention, usually with the lead angle being positive and the lag angle being negative.
The commissioning inspection includes: checking the polarity of CT and VT, checking the phase sequence, confirming that the differential current is close to zero, checking the power direction, and verifying the displayed values of various analog quantities. By examining the waveform of the recorded wave, it is possible to visually determine whether the polarity of CT and VT is correct. If excessive negative or zero sequence components are found, the phase sequence and polarity should be checked.
The self check and diagnostic functions can be entered into diagnostic mode through HMI to test output relays, input contacts LED、 Button, display, and communication ports. Diagnostic mode will temporarily disable all protection functions, so it is strictly prohibited to enter while the protection device is running.
Typical application scenarios
M-3425A is suitable for various types of generator protection. For directly connected generators, 87 differential protection is used as the main protection, and 87GD is used as the grounding backup. For generators connected through a Δ - Y transformer, the device can compensate for a 30 ° phase shift through internal calculations without the need for auxiliary VT. For high impedance grounding systems, the 59N+27TN combination provides 100% stator grounding protection. For low impedance grounding systems, 87GD provides high sensitivity grounding differential protection. For pumped storage units, the forward/reverse power lockout function of 27TN can prevent misoperation during the start-up process.