In the power system, when two or more on load tap changers (LTC) operate in parallel, if the tap positions are not consistent, circulating current will be generated between the transformers, causing winding overheating, increased losses, and even endangering equipment safety. Therefore, a dedicated parallel balancing module must be used to achieve coordinated control of each transformer tap through the circulating current method. The M-0115A parallel balancing module launched by Beckwith Electric is the core component designed for this scenario, which can be combined with voltage regulators such as M-0067E or M-2001C/D to form a complete and stable parallel voltage regulation system. This article is based on product technical specifications and provides an in-depth analysis of the working principle, parameter settings, wiring points, and common on-site problem handling of M-0115A, providing authoritative reference for power engineers.
Product positioning and functional overview
M-0115A is an independent parallel balancing module that integrates all the additional components required for the parallel operation of on load tap changers. It uses the Circulating Current Method to automatically balance the tap positions of each transformer. This scheme complies with the requirements of ANSI C57.12.10-1988 Section 10.2 and has been adopted by numerous transformer manufacturers.
The core functions include:
Circulating current detection: Using a 0.2A rated CT input, detect the amplitude and phase of circulating current between transformers.
Sensitivity adjustment: 9-level sensitivity selection (from 2 times normal to 0.5 times normal) to prevent system oscillation (over sensitivity) or excessive tap deviation (under sensitivity).
Parallel/Independent Mode Switching: The panel switch allows the controller to operate in parallel or independent mode.
Transient protection: meets the requirements of ANSI/IEEE C37.90.1-1989 for oscillation wave and fast transient immunity, with input and output isolated from ground and withstand voltage of 1500Vac.
This module is designed to be compatible with voltage regulators with 0.2A load/circulating current input (such as Beckwith M-0067E, M-2001C/D) and can be installed on new transformers or retrofitted to existing equipment.
Working principle: Parallel control using circulation method
The basic principle of the circulating current method is that when the tap voltages of two parallel transformers are not consistent, a circulating current will be generated on the secondary side, and its size and direction reflect the deviation of the tap position. M-0115A detects the circulating current and generates a correction signal (usually proportional to the circulating current, with a phase lag of about 90 °) to be sent to the voltage regulating controllers of each transformer, causing the controllers to adjust the tap to reduce the circulating current.
Specific process:
The load current and circulating current of each transformer are superimposed by CT and sent to the current input terminal of M-0115A.
M-0115A internal processing circuit extracts circulating current components (through load current balancing and vector synthesis).
According to the sensitivity setting, output the corresponding amplitude DC or AC correction signal to the circulating current input port of the voltage regulator controller.
The voltage regulator controller combines the correction signal with the local voltage deviation to determine the boost or buck command.
The ultimate goal is to make the tap positions of each transformer the same and minimize the circulating current, which can usually be controlled within 5% of the rated current.

Key parameters and setting methods
3.1 Rated current input value
Rated current: 0.2A (continuous), corresponding to 1PU (per unit).
Short term overload capacity: 0.4A continuous; 2.9A lasts for 5 seconds; 3.3A lasts for 4 seconds; 4.0A lasts for 3 seconds; 5.0A lasts for 2 seconds.
The turns ratio design ensures that the iron core is not saturated under a 12VA load.
If the CT secondary is 5A on site, auxiliary CT (such as Beckwith M-0169A, variable ratio 5A: 0.2A) conversion must be used. If using phase to phase voltage (such as some wiring of M-0067E), it is important to note that it should be led out from terminal 5 of M-0169A instead of terminal 1 (only applicable to non-M-2001C/D controllers, as the latter have phase angle correction function).
3.2 Sensitivity switch (43S)
There are 9 levels of sensitivity adjustment, with level 1 being the highest sensitivity (2 times normal) and level 9 being the lowest (0.5 times normal). Proper setup is crucial:
Excessive sensitivity: The system reacts excessively to the circulation, causing frequent movements of the tap and resulting in hunting.
Low sensitivity: The circulating current cannot be effectively suppressed, and the tap deviation may reach several levels, increasing winding stress.
It is recommended to set the initial setting to the middle gear (about 5 or 6), and adjust it to the minimum circulation and smooth operation by observing the circulation (CT secondary can be measured with a clamp gauge) and tap action frequency on site.
3.3 Parallel/Independent Switch (43P)
This switch selects the control mode:
P (Parallel): Enable the circulation compensation function, and the controller adjusts the tap according to the circulation signal.
I (Independent): Disable circulating current compensation, and each transformer is independently regulated (suitable for disconnection operation or maintenance).
Important warning: When the transformer is in parallel and under automatic control, it is absolutely forbidden to turn the switch from "P" to "I", as this will cause the controller to lose its ability to correct circulating current, which may result in the two transformer taps adjusting in opposite directions, causing a sharp increase in circulating current and damaging the equipment. The correct switching sequence is to first set all transformer controls to manual or release parallel connection, and then switch modes.
Key points of wiring and system integration
4.1 Basic wiring scheme
The terminal block (TB1) of M-0115A mainly includes:
Current input (K1, K2 or ACT): used to connect the circulating current CT signal (0.2A).
Calibration signal output: sent to the circulating current input terminals of each voltage regulator controller.
The typical wiring is as follows:
The CT secondary of each transformer (converted by auxiliary CT) is connected to its corresponding load CT input terminal of the voltage regulator controller, and the CT signal is also connected in series or parallel to the circulating current detection winding of M-0115A.
The correction signal output by M-0115A (usually in the form of voltage or current) is then sent in parallel to the circulating current input terminals of all voltage regulating controllers.
4.2 Coordination with different controllers
M-0067E: This controller has an independent circulating current input (0.2A), but it should be noted that its line voltage drop compensation and circulating current compensation share the CT input channel and need to be switched through internal jumpers or external switches. The output of M-0115A can be injected into this input, either as a substitute or in addition to the load current.
M-2001C/D: The new digital controller has dedicated circulating current input terminals and phase angle correction settings, supports direct connection to the output of M-0115A, and can adjust phase shift through software to simplify wiring.
4.3 Effects of auxiliary contacts on circuit breakers
If there are line circuit breakers (52) or contact circuit breakers (24) in the system, their auxiliary contacts should be connected to the logic circuit of M-0115A to ensure that the corresponding transformer is automatically switched to independent mode when the circuit breaker is opened. In the wiring diagram, auxiliary contacts are usually in a closed state (parallel mode) when the circuit breaker is closed, and when disconnected, the parallel circuit is disconnected. If there is no such circuit breaker on site (such as using only one common load switch), it should be handled according to the principle of "normally closed contacts connected to the circuit, normally open contacts not connected".
4.4 Precautions for manual operation
When manually operating the load switch, each voltage regulator controller must be placed in the "MANUAL" position, and the 43P switch of M-0115A must be placed in "I" (independent) before operating the switch. Otherwise, there is a possibility of misadjustment due to sudden changes in circulation during the operation process.

On site debugging and troubleshooting
5.1 Pre operation inspection
CT polarity: Ensure that all CT polarities are consistent, otherwise the circulation detection will reverse, resulting in incorrect correction signals.
Auxiliary CT ratio: Confirm that the 5A: 0.2A ratio is accurate, with an error within ± 1%.
Initial sensitivity setting: Set to the middle gear and fine tune after the system stabilizes.
Switch position: Confirm that 43P is in the "P" position and each controller is in "AUTO" or "REMOTE".
5.2 Debugging steps
Close the power supply of each transformer and confirm that there are no abnormal loads.
Adjust one of the transformers to the rated tap and observe whether the tap of the other transformers follow the adjustment (if the voltage deviation is large, the controller will prioritize voltage adjustment first).
After the voltage stabilizes, observe the circulating current (using a clamp meter to measure CT twice, converted to once). If the circulation is greater than 5% of the rated value, gradually adjust the sensitivity and observe the changes in circulation.
If the circulation continues to be large, check the CT polarity and wiring, and if necessary, exchange the S1/S2 terminals of a certain CT.
Conduct a load mutation test to observe whether the controller response is stable and without oscillation.
5.3 Common faults and their solutions
Possible causes and solutions for the fault phenomenon
Excessive circulation, inconsistent tapping, low sensitivity setting, increase sensitivity (reduce gear)
The tap frequently operates, and the system oscillation sensitivity is set too high to reduce sensitivity (increase the gear position)
Correction signal without output 43P in "I" position, CT disconnection or polarity error check switch position, CT wiring and fuse
A certain controller does not respond. The correction circulating current input terminal is not connected or the controller configuration is incorrect. Check the circulating current input channel settings of the controller
After switching the circuit breaker, if the parallel connection fails, the auxiliary contact wiring logic is incorrect. Check the wiring diagram to ensure that the contact status is correct
Installation and physical specifications
Panel opening: 8.5 "x 6.125" (width x height), with dimensions of 10 "height x 6.375" width x 4.47 "depth.
Surface mount: M-0124 surface mount adapter can be used to increase the depth to 4.56 inches.
Weight: Approximately 6 pounds, shipping weight 7.5 pounds.
Environmental tolerance: -40 ℃ to+80 ℃, 95% humidity without condensation, PCB triple proof coating.
Terminal torque: 4.8 inch pounds, wire specification 22-16 AWG.
Upgrade and renovation suggestions
For existing systems that use 5A CT, if the original voltage regulator controller does not have a 0.2A input, the controller needs to be replaced (recommended M-2001C/D) and an M-0169A auxiliary CT needs to be installed. M-0115A can be directly installed in the original panel space (using an adapter) without the need for large-scale wiring changes. If the old Westinghouse SVC/SVR controllers are used, they can be replaced as a whole with the M-0067E+M-0115A combination to achieve digital upgrading.
