Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

DEIF AGC-4 Mk II Generator Controller Depth Configuration Guide

F: | Au:FANS | DA:2026-07-07 | 12 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Setting prompt: Taking reverse power as an example, the typical setting is -5%~-15%, with a delay of 5-10 seconds, and the fault level is set to "trip+stop"; The overcurrent reversal time limit can be set with 6 inflection points (such as 110%/5s to 200%/0.5s) to achieve selectivity. Voltage protection should consider measurement accuracy (Class 1), and it is recommended to set the value offset by 1-2% to avoid misoperation.

PID regulator and speed/pressure control

The AGC-4 Mk II is equipped with an independent PID controller for speed regulation (GOV) and voltage regulation (AVR), which respectively manage frequency, power, active power distribution, voltage, reactive power, and reactive power distribution. The parameters of each controller (Kp, Ti, Td) can be adjusted from menu 2500 to 2690.

Proportion (Kp): determines the response speed, excessive will cause oscillation. It is recommended to fully utilize the output range (such as 0-20mA) to avoid large output changes caused by small deviations.

Integral (Ti): Eliminating steady-state errors, the smaller the Ti, the stronger the integral effect, but if it is too small, it is prone to oscillation. When Ti=0, the integral is turned off.

Differential (Td): improves dynamic stability and is beneficial for rapid disturbances (such as static synchronization). It is usually set to 0 or very small, and the differential is turned off when Td=0.

The load distribution controller (parallel mode) adjusts the power regulation intensity through the power weight factor (PWEIGHT, 2544). 100% indicates full effort to eliminate power deviation, while lower values prioritize ensuring frequency stability. If there is a large fluctuation in power during parallel operation, the PWEIGHT can be reduced or the Kp of the frequency PID can be reduced.

Relay output regulation: If relay pulse output is used, the "ON time" (minimum pulse width) and "Period time" (period) need to be set. The regulator automatically adjusts the duty cycle according to the deviation. When the deviation is large, the pulse is long or continuous, and when the deviation is small, the pulse is short. After entering the dead zone, it stops.

Droop mode: When connected in parallel with existing droop units, frequency droop (2514) and voltage droop (2644) can be enabled, with a droop amount of 0-10%, activated through M-Logic, suitable for old units that cannot provide constant speed regulation.


Synchronization principle and parameter settings

The AGC-4 Mk II supports dynamic synchronization (default) and static synchronization (menu 2000 selection).

Dynamic synchronization: Grid connected units catch up with the bus phase at a certain slip frequency (usually positive, slightly faster than the bus). Key parameters: Sync dfMAX/dfMIN (2021/2022) allows maximum positive/negative slip, typically ± 0.3Hz; Sync dUMAX (2023) allows maximum voltage difference, typically 5%; The inherent closing time of Sync tGB/tMB (2025/226) circuit breaker is used to issue closing pulses in advance. The dynamic synchronization speed is fast and suitable for load switching, but it is necessary to ensure that the slip is positive to avoid reverse power tripping after closing.

Static synchronization: First, adjust the frequency to almost the same frequency as the bus (deviation<50mHz), and then fine tune the phase angle by the phase controller (2070). When the phase angle enters the "closing window" (2033, ± 0.1~20 °), issue a closing command. Small impact but slow adjustment, suitable for applications sensitive to impact.

Pre closing excitation (CBE): allows the unit to close without excitation and then re excite after closing, significantly reducing grid connection time and suitable for black start or emergency scenarios. MPU or EIC speed signal needs to be configured, and parameters such as closing speed threshold (2251) and excitation start delay need to be set. When CBE fails, a 2270 alarm is generated, and the fault level can be configured separately. In addition, CBE supports the "rerun" function. During the cooling period, if a new start request is received, the CBE sequence can be directly re executed without stopping the machine. The excitation state during the cooling period can be controlled through parameter 2266 (ExcCtrl cooldown) (following the bus/normally open/normally closed).

Individual synchronous relay: The closing and synchronization signals can be separated through digital input and additional relays to achieve two-step closing and prevent accidental closing.


PMS Lite Lightweight Power Management

PMS Lite is a simplified power management system designed specifically for off grid power stations, supporting up to 127 generators and allowing for quick configuration through a display screen without the need for PC software. Each controller automatically detects and assigns an ID through the CAN bus (options H12.2/H12.8), supporting load dependent start/stop, priority setting, running hour balancing, minimum operating quantity, and multi start strategy.

Load dependent start stop: Parameters 8501 (start threshold, default 90%) and 8503 (stop threshold, default 70%) determine when to request the start/stop of the next priority unit. Stop logic to consider the remaining unit load and avoid overload.

  • Basler KR7FFX Static Regulator 840V
  • Basler EL200-7 Voltage Regulator 90-660VAC 7A
  • Basler PRP210-1 Reverse Power Relay 9056300102
  • Basler SSR 63-12 Static Regulator 600VAC
  • Basler 9289901106 Digital Board
  • Basler DECS100 Voltage Regulator DECS100A01
  • Basler Electric CEM-2020 Contact Expansion Module
  • Basler Electric BE3-25-1 C1 N4 Synchronizing Check Relay
  • Basler Electric ACA2000-50GM GigE Camera 2MP 50fps
  • Basler Electric ACA2240-20GMSYM GigE Camera Sony IMX264
  • Basler BE1-50G Ground Overcurrent Relay
  • Basler PRS250 Veri-Sync Relay
  • Basler MOC2199 Output Module
  • Basler UFOV 260A Underfrequency Overvoltage Module
  • Basler BE-15482-001 Control Module
  • Basler LSP4-7 Protective Relay
  • Basler SCP 250-G-60 VAR Power Factor Controller
  • Basler BE146N Negative Sequence Overcurrent Relay
  • Basler APR63-5 Automatic Voltage Regulator
  • Basler 9507900107 SR8A Retrofit Voltage Regulator
  • Basler BE1-320 Directional Power Relay
  • Basler KR7F Voltage Regulator 9116200100
  • Basler UFOV 260A Overvoltage Protective Module
  • Basler AEC63-7 Analog Excitation Controller
  • Basler 9992D90G01 Control Module
  • Basler 6966D22G01 Control Board
  • Basler 6965D40G01 Control Board
  • Basler BE1-50/51M-104 Overcurrent Relay
  • Basler BE1-BPR Programmable Breaker Relay
  • BASLER Electric SSR 125-9 1256 00 102 Static Voltage Regulator
  • Basler Electric MVC 112 Manual Voltage Control
  • Basler Electric 9321000102 Control Module
  • Basler Electric RA-70-MDCT7 Rectifier Assembly
  • Basler Electric ACA1300-60GM GigE Camera
  • Basler Electric 6427C85G01 Interface Board
  • Basler Electric 6965D05G01 Control Board
  • Basler Electric ACA2500-14UC Current Transducer
  • Basler Electric 9170206111 Protective Relay
  • Basler Electric BE1-11-G6D1M1J1P0E000 Protection Relay
  • Basler Electric BE1-50/51B-107 Overcurrent Relay
  • Basler 9121000106 Voltage Controller
  • Basler B3E-E1P-A0N0F Solid State Protective Relay
  • Basler 9121000106 Manual Voltage Control
  • Basler PRP320 Motor Pull-out Relay
  • Basler SSE-N 250-9KW Shunt Exciter Regulator
  • Basler BE1-50-51B-107 Overcurrent Relay
  • BASLER ELECTRIC MVC 108 MANUAL VOLTAGE CONTROL MODULE 9 0370 00 102
  • Basler BE1-59N-A7E-D1J-D0N0F Ground Overvoltage Relay
  • Basler BE1-46N-G1E-B8P-B0N0F Negative Sequence Overcurrent Relay
  • Basler BE1-951 Overcurrent Protection System
  • Basler Electric MOC2199 Motor Operated Potentiometer
  • Basler Electric BE1-60 Voltage Balance Solid State Relay B1FA1C1M1F
  • Basler Electric BE1-67N Directional Overcurrent Relay
  • Basler Electric PIA2400-17GM Interface Module
  • Basler Electric V6RAB Rectifier Module
  • Basler Electric BE1-32R Reverse Power Relay B2E E1R A0N1F
  • Basler Electric IFM-150 Firing Circuit Chassis 120V AC
  • Basler Electric IFM-102 Firing Circuit Chassis 120V AC
  • Basler Electric 9170206111 NSNP Control Module
  • Basler Electric SSR 63-12 Static Voltage Regulator
  • Basler UFOV 260A Overvoltage Protective Module
  • Basler SCA1300-32GM CCD Camera Lens Enclosure
  • Basler BA1-27 Under Voltage Relay
  • Basler 149D866G06 Control Board
  • Basler 9072300130 Power Supply Module
  • Basler CBS 305 Current Boost System
  • Basler BE1-60 Voltage Balance Relay
  • Basler Electric CBS 212 Current Boost System Sensing 120/240VAC 50/60Hz 10VA
  • Basler MVC-300 Manual Voltage Control Unit
  • Basler SSR125-12 Static Voltage Regulator 918500102
  • Basler SR32A2B05B3E Static Voltage Regulator
  • Basler Electric BE1-59N Ground Fault Overvoltage Relay
  • Basler Electric 9110000113 Excitation Module
  • Basler Electric 90-72300-114 Control Accessory
  • Basler Electric PRS-250 Protection Relay System
  • Basler Electric BE1-50/51M-109 Overcurrent Relay
  • Basler Electric SR4A1B10B3E Static Voltage Regulator
  • Basler Electric CBS 212 Current Boost System
  • Basler Electric SR32A2B05B3E Static Voltage Regulator
  • Basler Electric MOC2207 Motor Operated Potentiometer
  • Basler Electric SR4A1B05A3E Static Voltage Regulator
  • Basler Electric BE1-32R Power Relay B2EE1PA0N1F
  • Basler BEI-81 Underfrequency Relay
  • Basler CBS 212A Current Boost System
  • Basler SSR 63-12 Static Voltage Regulator
  • Basler DGC-2020 Digital Genset Controller
  • Basler BE1-32 Reverse Power Relay
  • Basler BE1-50/51B-207 Overcurrent Relay
  • Basler BE1-951 Overcurrent Protection System
  • Basler 9073800-103 Power Supply
  • Basler SCA1300-32FC CCD Camera
  • Basler 9073800-103 Power Supply
  • Basler SCA1300-32FC CCD Camera
  • Basler L304KC Protective Relay
  • Basler BE3-25-1S1N4 Time Overcurrent Relay
  • Basler 9032300113 Excitation Support System
  • Basler BE1-59N Ground Overvoltage Relay
  • Basler MVC-300 Manual Voltage Control Unit
  • Basler MOC2102 Potentiometer
  • Basler BE1-87G Generator Differential Relay
  • Basler Electric DECS-200 Digital Excitation Control System
  • Basler Electric DECS 125-15-B2C5 Digital Excitation System
  • Basler Electric PLA2400-12GM Power Supply
  • Basler Electric BE1-50/51B-235 Overcurrent Relay
  • Basler Electric BE1-27/59 Undervoltage Overvoltage Relay
  • Basler Electric CEM-2020 Contact Expansion Module
  • Basler Electric BE1-32R Solid State Power Relay
  • Basler Electric BE1-700 Digital Generator Management Relay
  • Basler Electric BE1-59N Ground Fault Overvoltage Relay
  • Basler Electric BE10493002 Protection Module
  • Basler Electric BEI-79A1AA5CA3M1F Digital Annunciator
  • Basler Electric SSR 32-12 Static Voltage Regulator
  • Basler Electric BE1-CDS240 Current Differential System
  • Basler Electric BE1-67 Directional Overcurrent Relay
  • Basler Electric 9121000106 DECS-100 Voltage Controller
  • Basler Electric BEI-871 Interface Module
  • Basler Electric 8650C72 Exciter Control Module
  • Basler Electric RDP-110-S1 Generator Annunciator
  • Basler Electric BE1-32O/U Directional Power Relay
  • Basler Electric BE2000E AVR Voltage Regulator
  • BASLER ELECTRIC BE1-50F2EA1PA0N0F Instantaneous Overcurrent Relay
  • BASLER ELECTRIC BE1-81T1EE1WA0N1F Underfrequency Relay
  • Basler BE1-67 Directional Overcurrent Relay
  • Basler BE1-25/79TR Reclosing Relay
  • Basler CEM-2020 Contact Expansion Module
  • Basler BE1-11 Overcurrent Protection Relay
  • Basler BE1-GPS Generator Protective Relay
  • BASLER ELECTRIC MVC-300 MANUAL VOLTAGE CONTROL UNIT 9121000106