Provide pre configured curves and up to 20 custom curves.
Analog output also supports up to 20 custom curves.
Circuit breaker control: Supports pulse, compact, and continuous circuit breakers, providing synchronous (dynamic/static), black start closing, load shedding, and circuit breaker position detection and alarm. Redundant circuit breaker feedback improves reliability.
Control mode: Supports three modes: local, remote, and distribution panel control, suitable for different operating scenarios.
Summary of Technical Specifications
Electrical safety
EN 61010‑1,CAT III,600V, Pollution level 2
IEC/EN 60255‑27,CAT III,600V, Pollution level 2
UL508,UL6200,CSA C22.2 No.14‑13,CSA C22.2 No.142 M1987
Electromagnetic Compatibility (EMC)
EN 61000-6-3 (Residential, Commercial, and Light Industrial)
EN 61000-6-2 (Industrial Environment)
IEC/EN 60255-26, IEC 60533 (Distribution Areas), IACS UR E10
IEC 60945 (Display Unit)
ISO 7637-2 pulse 5a (sudden load drop)
environment
Working temperature: Rack and module -40~70 ℃, display unit -20~70 ℃ (UL certification limit of 55 ℃)
Storage temperature: Rack and module -40~80 ℃, display unit -30~80 ℃
Humidity: 97% RH (IEC 60068-2-30)
Working altitude: 0~4000m (derating is required above 2000m, see module specification)
machine
Vibration (operation): 3~8Hz 17mm peak to peak value, 8~100Hz 4g, 100~500Hz 2g
Vibration (response): 0.15mm peak to peak at 10~58.1Hz, 1g at 58.1~150Hz
Vibration (durability): 58-150Hz 2g
Earthquake: 3~8.15Hz 15mm peak to peak, 8.15~35Hz 2g
Impact (base installation): 10g/11ms (response), 30g/11ms (durability), 50g/11ms (IEC 60068-2-27)
Collision: 20g/16ms (IEC 60255-21-2 Class 2)
Material: UL94 V0 self extinguishing
Certification
CE,UL/cUL Listed(UL508,CSA C22.2 No.142),UL/cUL Recognised(UL6200,CSA C22.2 No.14‑13)
Certification by major classification societies (latest list available at www.deif. com)
Engineering Application and Maintenance Suggestions
Rack selection: Choose a large rack (7 slots) or a small rack (4 slots) based on the number of I/O points, protection functions, and communication requirements, and reserve at least one empty slot for later expansion.
Module configuration: Generator protection comes standard with ACM3.1 and PCM3.1; If differential protection is required, add ACM3.2; If a safe shutdown function is required, use EIM3.1 and configure independent shutdown logic.
Network design: using ring network topology to achieve communication redundancy; All controllers can be accessed through a single Ethernet portal, simplifying SCADA integration.
Software backup: After debugging, backup the complete parameters and I/O configuration through PICUS and save them to a safe location.
Firmware upgrade: Upgrade the controller and display unit firmware through PICUS, and confirm compatibility before upgrading.
Permission management: Configure multi-level password protection, distinguish operator, engineer, and administrator permissions, and prevent misoperation.