In the field of process control, the capacity and performance of the controller directly determine the system's responsiveness, scalability, and operational reliability. The C300 controller in Honeywell's Expert Process Knowledge System (PKS) platform, as a high-performance control engine for the process industry, is widely used in automation control systems in industries such as petrochemicals, power, and pharmaceuticals due to its powerful processing capabilities, flexible I/O support, and excellent communication performance. This article will provide a comprehensive and in-depth professional interpretation of the system architecture, control network capacity, redundancy mechanism, communication performance, processing and memory models, engineering tool performance specifications, and I/O capacity of the C300 controller.
Overview of System Positioning and Architecture
The C300 controller is one of the core controllers based on the Control Execution Environment (CEE) in the Expert PKS platform. It shares a unified infrastructure and engineering tools with controllers such as C200, C200E, UOC, etc., providing users with comprehensive control capabilities from simple logic control to complex process regulation.
The C300 controller communicates with the upper system through Fault Tolerant Ethernet (FTE), supports connection with Control Firewall (CF9), and then connects to the L1 FTE control network. The system architecture is highly scalable and can flexibly configure servers, workstations, controllers, and I/O subsystems according to application requirements.
Control network capacity
The FTE control network where the C300 controller is located follows the following capacity limitations:
Parameter capacity
1 redundant network per Expert server (served by 1 or more redundant/non redundant servers)
330 FTE nodes per FTE community (standard); If there is FTEB or C300-20ms or deployment of EtherNet/IP ™, Then it is 200
200 Ethernet (non FTE) connections
The maximum number of controllers per server is 60 (redundant or non redundant)
Transmission rate of 100 Mbit/s (FTEB is 10 Mbit/s)
Key explanation:
When there are any FTEB, C300-20ms, or C300 deployments of EtherNet/IP in the FTE community ™ At that time, the upper limit of FTE nodes was reduced to 200.
PLCs connected to SCADA are not included in the "controller" quantity limit.
60 controllers can include any combination of CEE controllers (C200, C200E, C300, UOC, vUOC) and CDA controllers (up to 20 Safety Managers, up to 25 PMD Field Controllers, EHPM, etc.).
C300 configuration options
The C300 controller provides two types of CEE execution cycle configurations:
Configuration item 50 ms CEE 20 ms CEE
The supported control network FTE is only FTE
Supported C300 models CC-PCNT01/CC-PCNT02 CC-PCNT01/CC-PCNT02
Device index range 1-510 1-510
I/O links 2 2
I/O link rate 375 Kbaud (PMIO)/750 Kbaud (Series C) 750 Kbaud (Series C only)
Basic execution cycle 50 ms 20 ms
Redundancy support is
Remote I/O support supports PM I/O or Series A I/O, only Series C I/O is supported
I/O module execution cycle 50 ms 20 ms
Time source SNTP/PTPv2 SNTP/PTPv2
Important note:
C300 20ms CEE is only used for Honeywell Turbine Control Solutions (TMCS) in R410.1.
Extended features such as EIM and Profit Controller are only supported for CC-PCNT02 model.

C300 redundancy feature
C300 supports redundant configuration and achieves high availability through paired primary and backup controllers. Redundancy refers to the use of consecutive device indices (odd as primary, even as backup), connected via Ethernet STP cables.
Redundant specification 50 ms CEE 20 ms CEE
Function block redundancy configuration "module redundancy" optional "module redundancy" optional
Redundant IOTA quantity 2 2
Redundant cable lengths 36, 48, 60, 84 inches 36, 48, 60, 84 inches
Control processing switch interrupt time 1.25 seconds 200 ms
Initial synchronization time 240 seconds 240 seconds
OPM control freezing time 20 seconds 20 seconds
Attention: When configuring Direct or Through EIM-C300 EtherNet/IP ™ When switching, the interruption time may increase to 2.5 seconds.
Communication performance specifications
The communication performance of C300 controller is one of its core capabilities, and the following are key indicators:
1. Overall data access performance
Indicator 50 ms CEE 20 ms CEE
Maximum total parameter access response rate 32500 PPS 700 PPS
Maximum subscription parameters 34000 4000
Request/Response Parameter Access Rate 3000 PPM Read/1500 PPM Write 750 PPM Read/375 PPM Write
2. Point to point communication performance
Indicator 50 ms CEE 20 ms CEE
Maximum initiator Pull/Get subscription rate (inbound) 1000 PPS 250 PPS
Maximum target release rate (outbound) 1000 PPS 250 PPS
Peer to peer subscription capacity (by update rate) 100 @ 100ms / 200 @ 200ms / 500 @ 500ms / 1000 @ 1s 25 @ 100ms / 50 @ 200ms / 125 @ 500ms / 250 @ 1s
Point to Point Connection Unit (PCU) 30 5
3. Push/Store performance
Indicator 50 ms CEE 20 ms CEE
Maximum concurrent Push/Store requests 800 800
Maximum Push/Store Request Rate 250 PPS 12 PPS