4. Integer group transmission performance
Indicator 50 ms CEE 20 ms CEE
Maximum integer group size 8 KB (1000 float64) 8 KB (1000 float64)
Initiator array request rate 2500 EPS 600 EPS
Target array response rate 1500 EPS 350 EPS
5. PCDI (Modbus TCP) performance
Indicator 50 ms CEE 20 ms CEE
Maximum Modbus TCP devices 8 3
Maximum number of serial Modbus devices (per gateway) 16 3
Maximum PCDI request block message rate of 250 messages per second and 30 messages per second
Processing and Memory Capacity Model
The processing capability of the C300 controller is measured in "Execution Unit" (XU) units. C300 50ms CEE provides 5500 XU for user control, I/O, and communication purposes; C300 20ms CEE provides 5000 XU, but various operations in high-speed CEE contribute additional XU weights.
1. Reference for handling resource consumption (PU)
Typical module type 50 ms C300 (PU/module execution)
Typical I/O module 0.2
Simulated data acquisition module (10 AI) 4.4
Small simulation data acquisition module (1 AI) 0.5
Adjustment control module 3.1
Auxiliary Function Module (10 Auxiliary Blocks) 5.0
Digital data acquisition module (10 DI) 1.2
Equipment Control Module 1.3
Logic Control Module (20 Logic Blocks) 1.3
2. Memory resource (MU) consumption reference
C300 provides 214852 MU (Memory Unit, 1 MU=1 KB) of user memory. The maximum configurable number of labeled blocks is 24095, and each control module (CM) can contain up to 1100 component blocks.
Typical module type 50 ms C300 (MU/module)
Typical I/O module 0.5
Simulated data acquisition module 7.2
Adjustment control module 3.8
Auxiliary Function Module 6.2
Equipment Control Module 2.3
Logic Control Module 3.6
Sequential control module A (10 steps) 21.0
Sequential control module B (20 steps) 18.8
Formula control module A 30.4

I/O Capacity and IO UNIT Definition
The I/O capacity of the C300 controller is measured in units of "IO UNIT" (IOU), and different I/O devices consume different quantities of IOUs.
IO device or module IO UNIT consumption
1 PM IOP module 1
1 Series C I/O module 2
1 serial interface module (SIM) 6 (C300)
1 pulse input module (PIM) 1.5
1 Series C FIM4 4
1 Series C FIM8 8
1 non redundant FIM2 2
1 redundant FIM2 paired with 2
1 DHRIO module 0
1 SST-PFB-CLX Profibus module 4.5
1 DeviceNet Bridge Module (DNB) 4
Capacity limit:
The maximum IOU count for C300 50ms CEE is 64 (any combination), which can be extended to 80 if using only PM IOP or Series C IOM
The maximum IOU count for C300 20ms CEE is 12
The maximum number of IOUs per I/O link is 40 (50ms)/6 (20ms)
Performance specifications of engineering tools
Control Builder is the main engineering tool for C300 controllers, with the following performance specifications:
Rule description restrictions
1. Maximum number of labeled objects that can be operated on in the database (multi client) 6100
Typical CM numbers for database operations with 2 single clients 1000
The time for performing important database operations on 100 typical CMs is ≤ 20 minutes
The time for performing important database operations on 100 mixed typical objects is ≤ 10 minutes
5 QVCS verification operations with an additional 10% time
6 supported Control Builder clients (per cluster) 12
The number of clients that can perform important database operations simultaneously is 7
10 clients can perform controller related database operations on the same controller simultaneously. 2
11. 25000 mixed typical objects that can be exported or imported in a single operation
16 typical CM numbers that can be built in batches with a single operation of 700
22 Checkpoint Rebuild operation includes 5000 labeled objects
24 tagged object names with a maximum character count of 40
The maximum number of characters supported by 25 expressions is 1024
Comparison of C300-20ms and C300-50ms functions
The C300 20ms controller has been functionally constrained to meet the requirements of turbomachinery control applications
Function C300 50ms C300 20ms
Series C I/O support (maximum IOU limit) support (maximum 12 IOM, maximum 8 IOM per link)
PM I/O support not supported
FIM4/FIM8 support not supported
PGM support not supported
SCM/RCM/UCM/PHARE support not supported
CDB support not supported
Exchange block support not supported
Series C servo valve positioner module does not support support (turbine control)
Series C speed protection module does not support support (turbine control)
Profit Controller integration is only supported by CC-PCNT02 and is not supported
Ethernet Interface Module (EIM) is only supported by CC-PCNT02 and is not supported