ABB REX 521 protective relay
Product positioning and hardware configuration
REX 521 is a multifunctional protective relay that supports multiple hardware versions (Basic/Medium/High/Sensor) and standard configurations (such as B01/B02/M01/H01, etc.), suitable for different voltage levels and protection requirements.
Hardware differences:
Basic: Basic type, supports basic overcurrent and ground fault protection, with fewer digital inputs/outputs.
Medium: Enhanced, extended digital input/output, supports directional protection and automatic reclosing.
High/Sensor: A high-end model that integrates advanced functions such as sensor interfaces, voltage/frequency protection, and motor start monitoring.
Key components:
Built in current/voltage transformer interface, supporting 1A/5A current and 100V voltage input.
Provide digital input/output, communication ports (RS-232/RS-485), and optional fiber optic modules, supporting protocols such as Modbus and DNP 3.0.
Core functions and protective features
1. Protection function
Overcurrent protection:
Supports three-phase overcurrent (3I>, 3I>>, 3I>>>) and ground fault (Io>, Io>>, Io>>>), including directional (67N) and non directional configurations, supporting definite time (DT) and inverse time (IDMT) characteristics.
Built in harmonic suppression and excitation inrush current detection (3I2f>) to avoid misoperation.
Voltage and frequency protection:
Overvoltage/undervoltage protection (3U>, 3U<<), residual voltage protection (Uo>), frequency anomaly protection (f1/f2), supporting voltage imbalance and phase sequence protection (U1U2<>_1).
Motor and transformer protection:
Motor start-up monitoring (Is2t n<), thermal overload protection (3Ithdev>), phase sequence reversal protection (3I()), fuse fault detection (FUSEF).
Automatic reclosing (O ->I):
Supports up to 5 reclosures, can be triggered by protection start or trip signals, and has dead time and discrimination time settings.
2. Measurement and monitoring
Electrical quantity measurement:
Real time measurement of three-phase current/voltage, power, frequency, and energy, supporting true RMS and fundamental wave analysis.
The disturbance recorder (DREC) can capture fault waveforms and supports manual or triggered recording.
Status monitoring:
Circuit breaker wear monitoring (CB wear1), trip circuit supervision (TCS1), power input supervision (MCS 3I/3U).
Power quality monitoring (PQ 3Inf/PQ 3Unf), supporting harmonic analysis and THD/TDD calculations.
3. Communication and Control
Protocol support:
Standard SPA, Modbus RTU/ASCII, DNP 3.0, optional IEC 61850 adapter (requires expansion module).
Remote control:
Support local/remote switching (I<->O POS), circuit breaker opening and closing control (I<->O CB1), and integrated interlocking logic.
3、 Standard configuration and application scenarios
1. Basic Configuration (Basic: B01/B02)
Function: Non directional overcurrent/ground fault protection, thermal overload protection, B02 supports automatic reclosing.
Application: Single busbar system for outgoing or incoming line protection, suitable for resistance grounding or solid grounded networks.
2. Intermediate configuration (Medium: M01/M02)
Function: Add directional grounding fault protection (67N), phase sequence protection, M02 supports reclosing and angle control (BACTRL).
Application: Compensate for grounding or isolated networks, requiring selective protection for outgoing scenarios.