Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Allen Bradley Guardmaster 440R Safety Relay Troubleshooting and Configuration Guide

F: | Au:FANS | DA:2026-06-05 | 36 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Allen Bradley Guardmaster 440R Safety Relay Troubleshooting and Configuration Guide

Introduction: On site challenges of modular safety relays

In modern factory automation systems, safety relays are the core safety logic components that connect input devices such as emergency stop buttons, safety door switches, light curtains, safety carpets, and output actuators such as contactors and drivers. Guardmaster of Rockwell Automation ®  Safety Relay (GSR) series (including 440) R‑S13R2 CI、440R‑D22R2 DI、440R‑D22S2 DIS、440R‑EM4R2 EM、440R‑EM4R2D EMD  The 440R-S12R2 SI adopts a 22.5mm ultra-thin design, supporting single wire secure (SWS) communication, configurable logic (AND/OR), and pulse test diagnosis. For on-site maintenance engineers, quickly identifying LED flashing patterns, checking input/output wiring, and understanding timing functions are key to restoring safety circuits and reducing downtime.

This article combines the official user manual to provide an executable technical guide from six dimensions: hardware selection, wiring specifications, configuration process, LED diagnosis, common troubleshooting, and safety level requirements.


Model Overview and Selection Basis

The GSR series includes multiple models, and their input/output and main functions are compared as follows:

Model Catalog Number Safety Input Safety Output Auxiliary Output SWS Delay/Function

CI 440R-S13R2 1 channel dual channel 3 N.O. electromechanical 1 N.C. electromechanical only outputs none

SI 440R-S12R2 1 channel dual channel 2 N.O. electromechanical 1 PNP output only none

DI 440R-D22R2 2-channel dual channel 2 N.O. electromechanical 1 PNP input+output logic AND/OR

DIS 440R-D22S2 2-channel dual channel 4 PNP OSSD 1 PNP input+output logic AND/OR, high-capacity load output

EM 440R-EM4R2 only has SWS input 4 N.O. electromechanical 1 PNP input+output (direct) none

EMD 440R-EM4R2D SWS Input+B1/B2 4 N.O. Delay Electromechanical 1 PNP Input+Output Close Delay, Open Delay, Jogging

Selection Tips:

When expanding the number of output contacts, use EM or EMD as the slave station (connected to the host through SWS).

If delayed output (such as pressure relief behind a safety door) or jog function is required, EMD must be selected.

For capacitive loads such as the Safe Torque Off input of PowerFlex drives, it is recommended to use DIS 34/44 terminals (capable of withstanding 9 μ F capacitors).

CI/SI can directly replace the old MSR127/MSR126 models.

Installation and wiring points

3.1 Mechanical Installation

DIN rail: 35mm (EN 50022), directly clamped. Use a screwdriver to pry down the bottom latch during disassembly.

Spacing: Reserve at least 50.8mm ventilation distance above and below.

Shell protection: IP40 (NEMA 1), to be installed in control cabinets with IP54 or higher.

3.2 Terminal Wiring

All terminals are compatible with 0.2... 2.5 mm ² (24... 14 AWG) copper wire, with a torque of 0.4 N · m (4 lb · in). The terminal block is pluggable, and a small screwdriver can be inserted into the top slot to pry and remove it (refer to Figure 4 in the manual). Key terminal functions:

Terminal function

A1 24V DC power supply (+10%/-15%)

A2 24V common terminal

S11, S21 pulse test output (for mechanical contacts)

S12, S22 secure input channel 1/2 (first channel)

S32, S42 secure input channel 1/2 (second channel, only DI/DIS)

634 Reset/Monitor Input

L11 Single Wire Safety (SWS) Output

L12 Single Wire Safety (SWS) Input

Y32/X32 auxiliary output (PNP, conducting when safety output is disconnected)

13/14, 23/24... Safe output (N.O. or OSSD)

B1, B2 only EMD: jog input or can be triggered again to close delay input

3.3 Grounding Requirements

A 24V power supply certified by PELV or SELV must be used.

The 24V common terminal (A2) must be single point grounded to the protective ground (PE), otherwise it may cause false faults due to common mode noise (refer to Figure 61 in the manual).

If SELV is used and cannot be grounded, floating ground can be retained (but NFPA79 does not allow it).


Configuration Process (Five Step Method)

The GSR safety relay sets the logic, reset type, and delay through the front panel rotary switch. Before configuration, the input circuit must be closed (if the emergency stop button is not pressed).

Turn off the power and set the switch to position 0 (DI/DIS logic switch to 0); Set the CI/SI reset switch to 0; Set the Range and Time of EMD to 0, 1, or 10 respectively.

Power on: The PWR/Fault LED flashes red at 1Hz (indicating that the old configuration has been cleared and waiting for a new configuration).

Turn the switch to the desired position (refer to the table below).

Confirm configuration: The corresponding status LED will indicate the current switch position by the number of flashes (for example, if the LOGIC IN LED of EMD flashes 4 times, it indicates Time=4).

Power off and then power on: The new configuration is stored in EEPROM, and the device enters normal operation.

4.1 DI/DIS logic switch (10 levels, only used 1-8)

Position reset type logical expression

1. Manual monitoring (IN1 OR IN2) OR L12

2 Monitoring Manual (IN1 AND IN2) OR L12

3 Monitoring Manual (IN1 or IN2) AND L12

4 Monitoring Manual (IN1 AND IN2) AND L12

5 Automatic/Manual (IN1 OR IN2) OR L12

6 Automatic/Manual (IN1 AND IN2) OR L12

7 Automatic/Manual (IN1 or IN2) AND L12

8 Automatic/Manual (IN1 AND IN2) AND L12

Example: If two safety doors are connected in series and need to be closed simultaneously to reset, select position 4 or 8 (AND logic). If one of them is closed, choose OR logic.

4.2 CI/SI Reset Switch (3rd gear)

Location function

MM monitoring manual reset (requires rising edge+falling edge, pulse width 0.25... 3 seconds)

AM automatic/manual (when connected to 24V, it automatically resets; when connected to a button, it resets with a rising edge)

4.3 EMD Delay/Jogging Configuration (Range × Time)

Range switch: Select the function type (turn off delay, turn on delay, jog) and range (in conjunction with Time switch).

Time switch: If set to 1 at the beginning of the configuration, use a short range (such as 0.1... 10 seconds); If set to 10, use a long range (10... 3000 seconds).

Actual delay=Range reference value x (Time switch value x 10%).

For example: Range=3 (turn off delay, baseline 30 seconds), Time=5 → 30 × 50%=15 seconds.

Jogging function: It needs to be triggered when B1 is connected to 24V and L12 is ON. The ON time is the set value, and the OFF time is fixed at 500 ms.

Configuration precautions:

To make the shutdown delay retrievable, B1 and B2 must be short circuited before configuration.

If delay is required, B1 must be suspended.

After configuration is completed, the device must be powered off and saved within 5 minutes, otherwise it will permanently malfunction.

LED status diagnosis (quick reference)

5.1 Normal operation of LED

Meaning of LED color/status

PWR/Fault green is always on and normal

IN/IN1 green first input channel closed

IN2 green second input channel closed (DI/DIS)

LOGIC IN green SWS input L12 is ON

OUT green constant light safety output has been closed

OUT green flashing (1Hz) safety input closed, waiting for reset signal

B1 (EMD) green B1 input closed

LOGIC IN (EMD) flashing (1Hz) timing in progress (shutdown delay not yet expired)

LOGIC IN (EMD) fast flashing (8Hz) jog OFF time

5.2 Fault LED code (PWR/Fault indicator light)

Display status, fault types, possible causes, and solutions

The red light is constantly on and cannot be restored. The input or output is short circuited to 24V/0V, and there is an internal hardware error. Power off, restart, and reconfigure.

Red flashing (1Hz) configuration mode is normal, waiting for the switch to be set.

Red flashing twice (intermittent) configuration conflict. After power on, the switch position is inconsistent with the EEPROM. Reconfigure or check the switch.

Red flashes three times, B1-B2 connection error. After configuring EMD, B2 was short circuited to B1. Remove the short circuit and the fault will be automatically cleared.

Red flashing 4 times can trigger the input error EMD to non triggered mode, but L12 is turned on again during the shutdown delay period. Wait for the delay to end or reconfigure to trigger again.

Red flashing 5 times SWS fault L11/L12 signal abnormality, check wiring, shielding, and cable length (<30m).

The fault can be recovered by keeping the green light on and flashing the red light 4 times. If L12 flips more than once during the shutdown delay, it will automatically recover after the delay is over.


Common troubleshooting process (step-by-step)

Step 1: Check the PWR/Fault indicator light

Extinguish: No power supply. Check the A1/A2 voltage (should be 24V DC ± 15%).

Red flashing twice: The switch position does not match the stored value → Repeat the five step configuration.

Red flashing 4 times (under constant green background): see the table above.

Step 2: Check the power supply and grounding

Measure the voltage of A1-A2.

Confirm that the 24V common terminal is connected to the protective ground (only required for PELV). If the on-site grounding is poor and causes irregular faults, the grounding test can be temporarily disconnected (note: it is only for troubleshooting and must ultimately meet the standards).

Step 3: Check the security input

Measure the voltage between S11 and S21 and A2 using a multimeter. When the mechanical contact is disconnected, the S11/S21 of CI is about 19V; DI/DIS/SI is about 14V/18V (due to different pulse test waveforms).

After closing the contacts, the voltage of S12 and S22 should be close to the voltage of S11/S21. If the difference is greater than 2V, check the resistance or capacitance effect of the circuit.

Capacitive effect: Long line to ground capacitance will slow down the pulse front, but it can still work (for example, 1 μ F to ground can still operate).

Resistance effect: The total circuit resistance should be less than 900 Ω, and the round-trip of 22AWG wire within 200m is only about 21 Ω, which is rarely a problem.

OSSD device: Connect OSSD1/2 directly to S12/S22 and must share the same 24V reference. GSR cannot detect OSSD output short circuit, and upstream equipment needs to self diagnose.

Step 4: Check the SWS (Single Wire Safety) circuit

L11 output waveform: Send a set of pulses every 4ms (1ms+0.5ms), with a valid reading of 8-9V on the digital multimeter.

L12 input: LED LOGIC IN should light up. If it is not lit and L12 is not used, set the DI/DIS logic switch to 1, 2, 5, 6 (OR logic) to ignore L12.

SWS cable length ≤ 30m, it is recommended to use shielded wire. One L11 can drive up to 10 L12s.

Step 5: Check the reset circuit (S34)

If the OUT LED is flashing (waiting for reset), measure the voltage of A2 in connection with S3.

Automatic reset: S34 must be connected to 24V (constant high), and the safety output will immediately turn on after the input is closed.

Monitoring manual reset: S34 requires a pulse from 0V → 24V → 0V, and the low-level time must last for 0.25... 3 seconds. When using the button, the release time should be within this range.

External contact monitoring: The auxiliary contacts of the contactor can be connected in series in the S34 circuit. If the contacts are not closed, they cannot be reset.

Step 6: Check the safety output

Mechanical and Electrical Output (CI/DI/EM/EMD/SI): The output terminal is connected in series with the load. Confirm that the voltage of 13 or 23 is the same as the power supply, and the voltage of 14 or 24 is the same (when the output is ON). If the voltage is normal but the contactor does not engage, measure the contactor coil.

OSSD output (DIS): 14/24 terminal maximum load 1.5A, capacitance 1.6 μ F; The maximum load of terminal 34/44 is 0.5A, with a capacitance of 9 μ F. When the output is ON, the terminal voltage should be close to 24V. If connecting the PowerFlex driver S1/S2 input, it must be grounded together (the COM of the driver is connected to A2).

Auxiliary output: Y32 (DI/DIS/SI) and X32 (EM/EMD) conduct when the safety output is OFF (PNP output). If the safety output is OFF but the auxiliary output does not have 24V, it may be due to internal safety relay adhesion or internal failure, and the module needs to be replaced.

Step 7: EMD Special Input B1/B2

Jogging function: B1 is connected to 24V and L12 is ON → output ON for a set time and then OFF for 500ms.

Can trigger shutdown delay again: Short circuit B1-B2 before configuration. If L12 is turned on again during the shutdown delay period, the timer will be reset.

If the B1 LED lights up but has no waveform, it may be an internal fault.


Security level and maintenance recommendations

7.1 SIL/PL parameters

All GSR models meet the following requirements:

PFH: 1.5E-09~4.5E-09 (applicable to high demand mode)

SIL 3(IEC 61508 / IEC 62061)

Cat 4 / PLe(ISO 13849‑1)

MTTFd: ≥ 252 years

DCavg:98.8%

7.2 Service life and replacement

Electrical lifespan: 10 times of operation (electromechanical output).

After 20 years of use, replacement should be evaluated.

Online replacement: The GSR module supports hot swapping (can be replaced with power on, but must ensure that the safety circuit is disconnected).

7.3 Suggestions for spare parts

Common models: CI (440R-S13R2), DI (440R-D22R2), EM (440R-EM4R2).

Backup wiring terminal (pluggable, module can be replaced without disconnecting).

If using SWS, ensure that the cable length is ≤ 30m and prepare shielded cables.

  • Honeywell 30751044-008 ROM Card
  • Honeywell 5SE1-12 Micro Switch Specifications
  • Schneider AS-BDAU-204 Analog Output Module
  • K93712 Expansion Kit Industrial Module
  • MGE DCHEN 3400116300 Circuit Board
  • Siemens 6SE7036-1EE85-1HA0 Rectifier Board
  • Renesas UPD70F3624GBA1 Microcontroller
  • Omron E5AC-CX4A5M-014 Temperature Controller Parameters
  • GE IS200TBCIH1BCE Contact Input Board
  • Fanuc A05B-2255-C101#EAW Teach Pendant Data
  • Rieter RMC186C RMC RIO-1 PLC Controller
  • Siemens PXC24.2-EF32.A Building Automation Controller
  • Fanuc A16B-1200-0220 PC Memory Board F3
  • Omron CJ2M-CPU33 PLC CPU Module
  • Beckhoff EL1918 Safety Input Terminal EtherCAT
  • Fanuc A16B-1212-0871 CNC PCB Board
  • GE Fanuc IC697BEM713J PLC Module
  • Mitsubishi A2ACPU-R21 PLC CPU Module
  • Programmable Relay 230V AC 16 Inputs 8 Outputs T2UK
  • Schneider F3SP71-4S Safety PLC Module
  • NEED-24DC- T2UK Programmable Relay 24V 16in 8out
  • Siemens 3RT1075-6SP36 SIRIUS Power Contactor 200kW
  • GE 1C31170G02 Printed Circuit Board Module 94V-0
  • BPT 67200020 Multifunction Touch Terminal 50Hz
  • Fanuc A16B-2200-0931 Option Board with Daughter Cards
  • Honeywell FC-SDOL-0424 I/O Module Board
  • Lenze EMF2179IB DeviceNet Communication Module
  • Yaskawa CIMR-JC4A0007BAA J1000 VFD 0.4kW
  • Yokogawa PSBCMNBN Bus Continuation Module ProSafe-PLC
  • Phoenix Contact PLC-BPT-24DC/1/SEN Solid-State Relay
  • Allen-Bradley 193-EC2AB E3 Plus Overload Relay
  • GE DS200TCTGG1AFF Turbine Control Board
  • Westinghouse 1C31170G02 Ovation Module
  • Mitsubishi A2ACPU21 Programmable Controller Review
  • 710-95045-AD PLC I/O Operation Console Cable
  • Allen-Bradley 1785-L11B PLC-5 Processor Specifications
  • BEMAC UST-202-D 1307D V08B2 Circuit Board
  • Pilz 312070 PSSu H PLC1 FS Safety Module
  • Keyence QS-MB1 Safety Network Module Overview
  • GE Fanuc IC693CPU372 CPU Module 90-30 Series
  • Mitsubishi RJ71EIP91 EtherNet/IP Module
  • Schneider LXM62DD27D21000 Lexium 62 Servo Drive
  • Mitsubishi Q13UDEHCPU Universal PLC CPU Module
  • B&R X20CP3585 Programmable Controller X20 CPU
  • Siemens 6FC5203-0AF02-0AA0 Sinumerik Operator Panel
  • IWKA PG02 VKR TEL-Z Self-Sufficient Measuring System
  • Schneider BMXCPS2010 PLC Power Supply Modicon M340
  • Mitsubishi A171SCPU Motion Servo CPU Specifications
  • PLC Board with Finder 44.52 Relay Module 6A 250V
  • Honeywell DOP 09436601 Measurex Module Data
  • Fanuc A20B-8101-0320 CNC Circuit Board
  • KUAX 680I V.24 PLC Module 68142304
  • Allen Bradley 1785-L30B PLC 5/30 Processor
  • Phoenix ILC 191 ETH 2TX 2700976 Ethernet Controller
  • Siemens 6SY7000-0AC80 PLC Power Supply Module
  • Reliance Electric MACS 804.46.20 CWW PLC Drive
  • Omron CP1E-N60DR-D PLC CPU 36 Input 24 Output
  • Mitsubishi Melsec PLC System A2ACPU A63P AY13E AX82
  • Square D PAF361600DC1680 2000A Circuit Breaker
  • MERLIN GERIN STR 58U 5000A Electronic Trip Unit
  • Omron CJ1W-SCU21-V1 Serial Communication Unit
  • SICK S30A-6011EA S3000 Safety Laser Scanner
  • Mitsubishi Q00JCPU-S8 Universal Programmable Controller
  • Allen-Bradley 20AB9P6C3AYNANC0 PowerFlex 70 AC Drive
  • SYSMELEC Handheld Robot Automation Controller
  • LG Display LB315WRM-SVA1 32 Inch 4K LCD Panel
  • Mitsubishi Kakoki E Series PLC I/O Modules
  • Allen-Bradley 1440-VST02-01RA Dynamic Measurement Module
  • Beckhoff EL5042 EtherCAT Encoder Terminal
  • Beckhoff CX5010-0112 Embedded PC Controller
  • Guardmaster 440R-D22R2 Safety Relay Specifications
  • NL12880BC20-10ND Industrial Display Panel Data
  • LFI 12X5326-S1 Slide-in Control Board Technical Data
  • Modicon AS-9370-001 Programmable Controller Data
  • Mitsubishi Kakoki E-01B-4130 PLC Module Overview
  • Guardmaster 440R-D22S2 Dual Input Safety Relay Data
  • NL10276AC30-48D Industrial LCD Display Panel Data
  • GE ICMFA000000-ABAC Field Control Module Specification
  • Siemens 6SN1123-1AB00-0BA1 SIMODRIVE Module Review
  • Siemens 6SL3210-1SE23-2AA0 Power Module Technical Data
  • Schmersal T.250-11z-t Limit Switch
  • Schmersal T.250-11z-t Limit Switch
  • Honeywell 900H32-0102 ControlEdge 900 PLC
  • Siemens 6FX1132-1BA01 PCB B84141-A-A40
  • BEMAC UST-202-D 1307D PLC Circuit Board
  • Mitsubishi HS-MF23-S2A Servo Motor
  • B&R 3AI775.6 Analog Input Module
  • Omnipure 69003 Rev 11 3-Phase Gate Board PCB
  • Pilz 751134 PNOZ s4 C Safety Relay
  • Proface PFXGM4301TAD HMI Graphic Panel
  • Keyence KV-RC8BXR Programmable Controller
  • Siemens 6GK7243-1BX30-0XE0 CP 1243-1 Ethernet Module
  • Mitsubishi GT2310-VTBA GT2310-VTBD HMI 10.4 Inch
  • Schmersal SRB-NA-R-C.21-24V Safety Relay Module
  • Emotron 01-2520-40 M20 Shaft Power Monitor 3x380-500V
  • Omron CQM1 SYSMAC PLC System PA203 ID211 OC221
  • ABB CI830 3BSE013252R1 Profibus DP V1 Module
  • B&R 4PP035.0300-01 Power Panel PLC Module
  • SICK S30A-6111CL S3000 PROFINET Safety Laser Scanner
  • Siemens 6ES7215-1HG40-0XB0 CPU 1215C AC/DC/RLY
  • Automation Direct H2-ECOM100 Ethernet Module Details
  • Siemens 6GK1143-0TB01 CP 1430 TF Module Review
  • Siemens Simatic 505 10 Slot PLC Rack Technical Review
  • Automation Direct EZ-SP Message Display Unit
  • Mitsubishi A1SJ71QE71N-B5T Ethernet Interface Unit
  • Modicon AS-P810-000 Modbus Plus Processor Unit
  • Honeywell 51309241-175 TK-PPD011 PWA Specifications
  • Omron S8AS-24006N Smart Power Supply Specifications
  • Beckhoff EL3218-0018 EtherCAT Terminal Specifications
  • Omron CJ1W-PRT21 PROFIBUS-DP Interface Unit
  • Inovance AC810-0122-U0R0 PLC Controller
  • Cypress CY7C1021CV33-10ZXCT 1Mb SRAM IC
  • GE Fanuc IC695CPU315-CD PLC CPU Module RX3i
  • Drager 8312088 PCB Safety Module PAC 5500
  • Weltronic H70-T02A S430-V1.2 Weld Timer PLC
  • B&R 3AM051.6 PLC Analog Input Module
  • Schneider BMENOC0301 Communication Module M580
  • Mitsubishi FX3UC-32MT-LT PLC Controller
  • Omron TZ-1G TZ-1GV TZ-1GV2 TZ-1GV22 Motion Switch
  • Mitsubishi AJ71C21-B1-S2 PLC Controller 424749
  • Beckhoff EL5042 EtherCAT Encoder Terminal BiSS C
  • Eaton easyE4 Programmable Relay 12 Inputs 8 Outputs
  • Carel PCO5 P+ 500BAA000L0 Programmable Controller
  • Siemens 6ES7223-1PL22-0XA0 EM223 I/O Module 16DI 16DO
  • Lenze EMF2179IB DeviceNet Communication Module
  • Mitsubishi Q173DCPU Motion CPU Module
  • B&R X20AT2222 Temperature Input Module Pt100
  • Siemens SITOP UPS1100 Battery Module 7Ah 6EP4134-0GB00-0AY0