Lsi type protection
Add short delay protection (S) on the basis of Li:
Short delay protection (S): Short circuit selective protection
Isd adjustable: 1.5 to 10 x Ir (11 levels)
Tsd adjustable: 0, 100, 200, 300, 400, 500 ms
Optional I ² t=K or t=K characteristics
Lsig type protection
Add ground fault protection (G) on the basis of Lsi:
Ground fault protection (G)
Ig adjustable: 0.2 to 1 × In (9 levels) and OFF
Tg adjustable: 0.1s, 0.2s, 0.3s, 0.4s, 0.5s, 1s
2. Measurement function
LCD display screen: Real time display of parameters such as current, voltage, power, and electrical energy
Internal battery: Parameter settings can still be made even when the circuit breaker is disconnected
USB port: used for local connection and configuration
Communication interface: Supports MODBUS RS485 protocol for remote monitoring
3. Self powered and auxiliary power supply
The electronic protection unit is normally powered by an internal current transformer (CT):
When the current is greater than 12% of the maximum power (single-phase load>20% In), the protection unit operates entirely on its own power supply
The measurement and display function is enabled when the current is greater than 20% of the maximum power (single-phase load>35% In)
To ensure continuous measurement and communication, it is recommended to use an external auxiliary power supply:
External auxiliary power module (M7ALIM)
MODBUS communication interface (M7COM)
Temporary power supply for USB port (5V DC)
4. Self diagnosis and protection
The protection unit has the following self diagnostic functions:
Over temperature protection: triggered when the internal temperature exceeds 95 ° C
Watchdog self-test: detects internal faults in the microcontroller to ensure reliable protection functions
Power loss and derating usage
1. Power loss per pole
In (A) Fixed front wiring (W) Fixed rear wiring (W) Pull out front wiring (W) Pull out rear wiring (W)
500 11.6 11.5 20.0 15.0
630 18.5 18.3 31.8 23.8
800 29.8 29.4 51.2 38.4
1000 47.6 47.0 82.0 60.0
1250 74.4 73.4 128.1 93.8
1600 65.3 58.9 112.6 97.3
2. Temperature reduction
The ambient temperature has a significant impact on the current carrying capacity of circuit breakers. The following table shows the maximum continuous operating current at different temperatures:
In (A) 50°C 60°C 70°C
500 500 500 500
630 630 630 630
800 800 800 720
1000 1000 1000 900
1250 1250 1250 938
1600 1600 1600 1360
3. Altitude Capacity Reduction
When the installation altitude exceeds 2000 meters, it is necessary to reduce the capacity according to the following coefficient:
Altitude (m) ≤ 2000 3000 4000 5000
Working voltage Ue (V) 690 590 520 460
Rated current In 1 × In 0.98 × In 0.93 × In 0.9 × In
4. Environmental adaptability
Climate conditions: comply with Appendix Q, Cat. F of IEC/EN 60947-1
Electromagnetic compatibility: Complies with Appendix F of IEC/EN 60947-2
Pollution level: Level 3

Accessories and Options
The M5 series offers a wide range of electrical and mechanical accessories to meet different application needs.
1. Release device
Split release (ST)
Voltage specifications: 24V, 48V, 110-130V, 220-250V, 380-440V (AC/DC)
Voltage range: 70% to 110% Un
Action time: ≤ 50 ms
Power consumption: 300 VA/W
Undervoltage Release (UVR)
Voltage specifications: 24V AC/DC, 48V DC, 110-125V AC, 220-240V AC, 380-415V AC
Operating voltage: 35% to 70% Un
Reset voltage: 85% to 110% Un
Action time: ≤ 50 ms
Delay module: can be equipped with 800ms delay module (M7000E/024, M7000MR/230, M7000MR/400)
2. Auxiliary contacts
Model: M7X01
Contact form: 1NO/NC conversion contact
Rated current: 3A @ 250V AC
Configuration: M5 supports up to 3 auxiliary contacts, 1 fault signal contact, and 1 release
3. Rotate the handle
Type and Model Description
Direct standard M7647 black handle
Variable depth standard T7649 IP55, black
Variable depth emergency T7649E IP55, red/yellow
Lock attachment M7R17 for variable depth handle, requires universal lock cylinder
4. Electric operating mechanism
Factory assembled type
Model: M7875P/024, M7875P/048, M7875P/230
Voltage: 24V, 48V, 230V AC/DC
Installation method: Pre operation
Customer assembly type
Model: 0 261 24 (24V), 0 261 25 (48V), 0 261 26 (110V), 0 261 23 (220V)
Scope of application: In ≤ 1250A
1600A dedicated: 0 261 19 (24V), 0 261 28 (48V), 0 261 29 (110V), 0 261 27 (220V)
5. Connect attachments
Cage terminal
Standard type: M7900/2 (2 × 185mm ² flexible/2 × 240mm ² rigid)
High Capacity Type: M7900/4 (4 × 185mm ² Flexible/4 × 240mm ² Rigid)
Expansion terminal
Short terminal: M7940/2 (500-1250A, maximum 2 busbars per pole)
Long terminal: M7940/3 (1600A, maximum of 3 busbars per pole)
Rear wiring terminal
Rotating: M7960 (3P), M7961 (4P)
Flat panel: M7950 (3P), M7951 (4P)
6. Pull out attachments
Pull out base
Front wiring: M7B25 (3P), M7B26 (4P)
Rear wiring: M7B27 (3P), M7B28 (4P)
Debro lift mechanism (moving parts)
3P:M7B29
4P:M7B30
Pull out attachment
Position signal contact: MT7910N
Pull out the handle: MT7412
Auxiliary contact (12 pins): M7B21
8-pin connector: M7500
7. Electronic version specific attachments
Auxiliary power module
Model: M7ALIM
Input voltage: 24V AC/DC (± 10%)
Installation method: 2 DIN modules
Purpose: To provide external power supply for electronic protection units, ensuring continuous operation of measurement functions