Basler BE1-87B busbar differential setting test

F: | Au:FANS | DA:2026-06-24 | 423 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Complete guide for setting calculation and on-site testing of Basler BE1-87B high impedance bus differential relay

In power plants and substations, the busbar is the core confluence node of the power system. Once a fault occurs, if it cannot be quickly cut off, it will lead to widespread power outages and equipment damage. Bus differential protection is the main protection for bus faults, and its action speed, sensitivity, and reliability are directly related to system safety. The BE1-87B from Basler Electric is a high impedance, solid-state relay designed specifically for bus differential protection, featuring outstanding features such as fast action speed (up to<5.5ms), flexible setting, and built-in CT circuit monitoring. Starting from engineering practice, this article systematically analyzes the protection principle, selection points, installation and wiring, parameter setting calculation (including maximum voltage for external faults and minimum sensitivity for internal faults), and on-site testing methods of the relay, providing a technical reference for relay protection engineers that can be directly grounded.


1. Principle of high impedance differential protection and action logic of BE1-87B

BE1-87B belongs to the high impedance differential relay, and its core idea is to achieve selectivity by utilizing the difference in current and voltage flowing through the relay when faults occur inside and outside the busbar area. When there is a normal or out of zone fault, the secondary currents of each CT are basically cancelled out in the differential circuit, and the voltage at both ends of the relay is extremely low; When there is a fault in the area, all CTs supply current to the fault point, and a high voltage is generated at both ends of the relay, triggering the internal SCR to conduct and output a trip.

The relay adopts a dual criterion of voltage and current internally:

Voltage component: detects the effective value of the power frequency voltage at both ends of the differential circuit (set range 50~400V, step size 50V). When the instantaneous peak voltage reaches 2.83 times the set value (corresponding to the full offset waveform), the SCR is triggered to conduct.

Current element: After the SCR is turned on, the current flowing through the interior of the relay must be greater than the set current threshold (0.25~2.5A, step size 0.25A) in order to finally output the trip signal.

This "voltage start+current hold" design effectively prevents misoperation caused by CT saturation during external faults, while improving the reliability of internal faults.


2. Interpretation of Model Code and Key Selection Points

The model code of BE1-87B defines options such as primary/secondary rating, phase number, timing characteristics, power supply, chassis, etc. Taking S5AA1YNONOF as an example:

S: Single phase current detection (also available in three-phase M-type).

5: 5A current input range (standard CT secondary 5A).

A: The front panel has a CT test button channel.

A1: Equipped with a 20ms delay (for use with high-speed fuses), and A2 (2ms delay for lightning protection interference).

Y: Control power supply 48/125Vdc or 110Vac (wide range), and also Z (125/250Vdc or 110/230Vac).

The N series indicates no special options.

F: Semi embedded S1 chassis (single-phase); Three phase is M1 or 19 inch rack.

Selection precautions:

Busbar protection usually requires three phases, so choose a three-phase model (starting with M).

If there are feeders (such as capacitor banks) protected by high-speed fuses in the busbar branch, A1 delay (20ms) should be selected to avoid relay misoperation when the fuse cuts off the fault.

If there is often transient interference such as lightning strikes near the busbar, A2 (2ms delay) can be selected to improve anti-interference performance.

The power supply selection needs to match the DC/AC voltage inside the station, with Y-shaped coverage of the most common 48/125Vdc and 110Vac.

3. Installation wiring and grounding specifications

BE1-87B adopts S1 (single-phase) or M1 (three-phase) drawer type chassis, supporting semi embedded, protruding, and 19 inch rack installation. Please refer to the manual for installation dimensions and hole drawings.

Key wiring points:

Current circuit: All CT secondary windings are connected in parallel to the differential junction point at the same end, and each phase is connected to the corresponding input terminal of the relay (single-phase: terminals 5 and 7; three-phase: A phase 5 and 7, B phase 3 and 7, C phase 1 and 7). The CT circuit must use shielded twisted pair or twisted cable to reduce induced interference.

Locking contact (86): After tripping, the relay input should be short circuited (terminals 5-6, 3-4, 1-2) through the normally open contact of the external locking relay (86) to protect the internal SCR from long-term high current impact. The action time of the latch relay should be less than 1 cycle (16ms).

CT test source: If a CT diagnostic test source (P/N 9282300014) is selected, its output is connected to terminals 7 (common) and 10 (test) for regular testing of CT circuit integrity.

  • Basler DECS-250-CGCM-LN2SA1C Digital Excitation Control System
  • Valmet Automation PLC Module A413171
  • Valmet Automation 542852-3A Rack-Mount Cross Connect Panel
  • Valmet Marine Damatic M851565 Main Keyboard
  • Valmet TIU 6 Printed Circuit Board A413110
  • Metso Valmet U4440253V1.1 RMI CPU 300
  • Metso Valmet A413016 Ver.12 NCU2
  • Valmet M851565 Damatic Keyboard
  • Valmet ATB16-4 16 Channel Relay Card
  • Valmet Metso A413331 SPU Power Supply
  • Valmet PUD 10B Automation Control Rack
  • Valmet MT917 ABMB DMU PCB I/O Module
  • Valmet M851565 Damatic Keyboard Mkb2
  • Valmet EDS-518A-MM-SC Ethernet Gateway
  • Valmet 542836-6A PCB Card
  • Valmet ATB16-4/2 Terminal Board 9144047
  • Valmet ATB16-4 Controller Board 0-50°C 4-20mA Analog Output
  • Valmet 542852-3A Slot Rack Chassis Module
  • Valmet A413026 Ver.M1 FBC Board
  • Valmet IQ Basis Weight SH Sending Assembly A418081
  • Valmet PMB 2R Monolithic Backplane 8-Slot PCB 542821-5A and -5B
  • Valmet ATB16-4 16-Channel Relay Card Controller Board 22195028
  • Valmet Diff-EL SL6NK227SF0 Pressure Transmitter 0-380 mBar
  • Valmet A413110 TIU6 Board Ver.M1
  • Neles Automation A413278 Control Module
  • Valmet BCUTB Terminal Module 10101006 11091002
  • Valmet Senso 160 Measuring Station Display 160.2
  • Valmet AIU 1A Analog Input Unit M851245
  • Valmet IQ Web Caliper Sensor A420734
  • Valmet M851040/M8510401 Memory Board
  • Valmet AN35S1MC02RA Valve
  • Valmet M851121 M2 Cross Connect Panel
  • Valmet AIU-8 Simulator Board 421522-1A
  • Metso BIU 82 D200533 Binary Input Unit
  • Valmet M851121 M2 Module Rack
  • Valmet A413383 PC Board Module
  • Valmet N0542 NO54 ABMB PCB - 545200-3A Board
  • Valmet Metso IOP304 Input Module 181503
  • Valmet PDP601 Distributed Processing Unit 181585
  • Valmet A413084 CPU Board - Processor Module for Automation Systems
  • Valmet AIU 16T Analog Input Module M8512081 M1
  • Valmet AIU 16 Analog Input Module 545100-3A and 545100-3B
  • Metso Valmet BIU4 A413146 Binary Input Unit
  • Valmet AIU-8 Simulateur Board 421522-1a Analog Simulator
  • Valmet BIU8A Binary Input Unit 542803-3B M851222 M1
  • Valmet IQ Web Color DH Photoelectric Sensor A418182 2.04
  • Valmet A413200 AIU-8 Simulator Board 191151 421522-1A
  • Valmet Automation SCU M851006 System Control Unit Module
  • Valmet 857565/851565 Damatic Keyboard IP40 5V Operator Interface
  • Valmet A413077 FBC2 Module Rev 06 Field Bus Controller
  • Valmet DMU 2 PCB Module 545142-3A DM Data Management Unit
  • Valmet AIU16T PCB Card M851208 Analog Input Module
  • Valmet A413181 PLU Board
  • Valmet m851006 SCU Module
  • Valmet Metso 181226 Digital Input Module
  • Valmet AIU16T Analog Input Module - 16-Channel 65421466-2B MT924 V1.3
  • Valmet WIN3136875 Slide Clutch
  • Metso Valmet TIU61 A413111 Temperature Input Unit
  • Valmet MC12S Slitter Motor
  • Valmet A413139 AOH4 Board - Analog Output High Module
  • Valmet A409001 BIU85 Board
  • Valmet A413063 DMU Board
  • Valmet A413325 IPU I/O Power Unit
  • Valmet M851004 M2 CPU Module
  • Valmet IOP345 Digital Input Module
  • Metso Valmet A413215 Communication Board
  • Valmet DIFF-EL 80 M1 Transmitter
  • Valmet A413001 CPU Module
  • Valmet M899520 TDC-2 Module
  • Valmet A409001 BIU85 Board
  • Metso Valmet A413005 CPU Module
  • VALMET PUD 10 B Process Automation Rack with CPU SCU Module
  • Valmet A413091 GDU1 Board
  • VALMET M851006 M2 SCU Module
  • Lyngso Valmet Marine 990.896.000 Position Loop Card
  • Valmet Cooking Liquor Measurement 3417H
  • VALMET ABMB MT831 PCB Card
  • Valmet Automation A413325 IPU I/O Power Unit
  • Valmet Metso Consistency Transmitter Smart Pulp M2
  • VALMET METSO A413274 Connection Module
  • VALMET PI33S1KSA02RSA-ELI26 Switch
  • VALMET ND9103HN-CE07-K05 Intelligent Valve Controller
  • VALMET PMB 2R 16 Slot Backplane PCB Card
  • NELES VALMET A413135 AOU 4 Output Module
  • Metso Valmet A413345 FPU Power Unit
  • VALMET A413171 PIC Module
  • VALMET A413620 Repeater Module
  • Valmet M851521 Memory Card
  • Valmet DIFF-EL 140 M1 Transmitter
  • Valmet A413064 DMU Module
  • Valmet IOP371 I/O Bus Extender Module
  • Valmet Cooking Liquor Measurement 3400 Model 3417H
  • Metso Valmet A413043 CPU Module – Industrial Processor
  • Valmet BIU4 M851221 Binary Input Module
  • Valmet PMB 1S CPU SCU Rack Module
  • Valmet A413248 Controller Module
  • Valmet PDP601 Distributed Processing Unit
  • VALMET M851004 M2 CPU Printed Circuit Board Module
  • Metso Valmet A413045 Ver.05 CPU Module
  • Valmet A413181 Ver.05 PLU1 Board
  • Lyngso Valmet ATB16 Controller Board
  • VALMET AIU 16 Analog Input Unit 545100-3A/3B
  • VALMET PUD 10 B Power Supply PCB Rack Module
  • Valmet MS-50V/120V Bearing Unit
  • Valmet PDP603 Distributed Processing Unit – DPU Module
  • Valmet A413110 TIU Board – Terminal Interface Unit
  • Valmet S420154 I/O Backplane PCB – Printed Circuit Board
  • Valmet A413173 Industrial Control Module
  • Valmet A413044 CPU Module
  • Valmet A4IU1 Analog I/O Module
  • Valmet A413325 IPU Power Unit – PLC Module
  • Valmet M851002 CPU Module – Central Processing Unit
  • Valmet PUD10B Power Supply Board
  • Valmet K00990 Master CPU Electronic Assy
  • Valmet Metso IOP345 Input Module
  • Metso Automation T545215 Board
  • Valmet Metso IOP304 Input Module
  • Valmet 542844-6A SCU Module
  • Metso A413043 Ver.11 Valmet CPU Module
  • Valmet Automation BIU 8A Input Module
  • Metso A413044 Ver05 Valmet CPU Module
  • VALMET 542821-5A Control System Rack Module
  • Metso A413005 Ver.04 Valmet CPU Module
  • Valmet M851207 AIU16 Card
  • Valmet BIU8 Binary Input Unit
  • VALMET 547070-2B CPU Printed Circuit Board Module
  • Valmet Automation A413325 Power Module
  • VALMET AUTOMATION A413135 AOU4 Module