Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Basler BE1-87B busbar differential setting test

F: | Au:FANS | DA:2026-06-24 | 424 Br: | 🔊 点击朗读正文 ❚❚ | Share:


Complete guide for setting calculation and on-site testing of Basler BE1-87B high impedance bus differential relay

In power plants and substations, the busbar is the core confluence node of the power system. Once a fault occurs, if it cannot be quickly cut off, it will lead to widespread power outages and equipment damage. Bus differential protection is the main protection for bus faults, and its action speed, sensitivity, and reliability are directly related to system safety. The BE1-87B from Basler Electric is a high impedance, solid-state relay designed specifically for bus differential protection, featuring outstanding features such as fast action speed (up to<5.5ms), flexible setting, and built-in CT circuit monitoring. Starting from engineering practice, this article systematically analyzes the protection principle, selection points, installation and wiring, parameter setting calculation (including maximum voltage for external faults and minimum sensitivity for internal faults), and on-site testing methods of the relay, providing a technical reference for relay protection engineers that can be directly grounded.


1. Principle of high impedance differential protection and action logic of BE1-87B

BE1-87B belongs to the high impedance differential relay, and its core idea is to achieve selectivity by utilizing the difference in current and voltage flowing through the relay when faults occur inside and outside the busbar area. When there is a normal or out of zone fault, the secondary currents of each CT are basically cancelled out in the differential circuit, and the voltage at both ends of the relay is extremely low; When there is a fault in the area, all CTs supply current to the fault point, and a high voltage is generated at both ends of the relay, triggering the internal SCR to conduct and output a trip.

The relay adopts a dual criterion of voltage and current internally:

Voltage component: detects the effective value of the power frequency voltage at both ends of the differential circuit (set range 50~400V, step size 50V). When the instantaneous peak voltage reaches 2.83 times the set value (corresponding to the full offset waveform), the SCR is triggered to conduct.

Current element: After the SCR is turned on, the current flowing through the interior of the relay must be greater than the set current threshold (0.25~2.5A, step size 0.25A) in order to finally output the trip signal.

This "voltage start+current hold" design effectively prevents misoperation caused by CT saturation during external faults, while improving the reliability of internal faults.


2. Interpretation of Model Code and Key Selection Points

The model code of BE1-87B defines options such as primary/secondary rating, phase number, timing characteristics, power supply, chassis, etc. Taking S5AA1YNONOF as an example:

S: Single phase current detection (also available in three-phase M-type).

5: 5A current input range (standard CT secondary 5A).

A: The front panel has a CT test button channel.

A1: Equipped with a 20ms delay (for use with high-speed fuses), and A2 (2ms delay for lightning protection interference).

Y: Control power supply 48/125Vdc or 110Vac (wide range), and also Z (125/250Vdc or 110/230Vac).

The N series indicates no special options.

F: Semi embedded S1 chassis (single-phase); Three phase is M1 or 19 inch rack.

Selection precautions:

Busbar protection usually requires three phases, so choose a three-phase model (starting with M).

If there are feeders (such as capacitor banks) protected by high-speed fuses in the busbar branch, A1 delay (20ms) should be selected to avoid relay misoperation when the fuse cuts off the fault.

If there is often transient interference such as lightning strikes near the busbar, A2 (2ms delay) can be selected to improve anti-interference performance.

The power supply selection needs to match the DC/AC voltage inside the station, with Y-shaped coverage of the most common 48/125Vdc and 110Vac.

3. Installation wiring and grounding specifications

BE1-87B adopts S1 (single-phase) or M1 (three-phase) drawer type chassis, supporting semi embedded, protruding, and 19 inch rack installation. Please refer to the manual for installation dimensions and hole drawings.

Key wiring points:

Current circuit: All CT secondary windings are connected in parallel to the differential junction point at the same end, and each phase is connected to the corresponding input terminal of the relay (single-phase: terminals 5 and 7; three-phase: A phase 5 and 7, B phase 3 and 7, C phase 1 and 7). The CT circuit must use shielded twisted pair or twisted cable to reduce induced interference.

Locking contact (86): After tripping, the relay input should be short circuited (terminals 5-6, 3-4, 1-2) through the normally open contact of the external locking relay (86) to protect the internal SCR from long-term high current impact. The action time of the latch relay should be less than 1 cycle (16ms).

CT test source: If a CT diagnostic test source (P/N 9282300014) is selected, its output is connected to terminals 7 (common) and 10 (test) for regular testing of CT circuit integrity.

Power supply: The power supply is connected to terminals 15 and 16, with no polarity.

Grounding: The casing must be separately grounded to the ground grid with a copper wire of not less than 12 AWG; It is recommended that each device has independent wiring.

Insulation test warning: Before conducting the withstand voltage test, the connecting plug must be unplugged, otherwise high voltage may damage the internal semiconductor devices.


4. Setting calculation (core steps)

The purpose of setting BE1-87B is to ensure reliable non operation in case of faults outside the zone and reliable operation in case of minimum faults within the zone. The setting is divided into three steps: voltage setting, current setting, and sensitivity verification.

4.1 Voltage setting (based on the maximum voltage of external faults)

When there is a fault outside the area, the fault line CT may saturate, causing its secondary impedance to drop to the winding resistance. The current of other non fault CTs will all flow through the fault CT circuit, generating voltage at both ends of the differential circuit. The voltage must be less than the relay voltage setting value.

Calculation formula:

VDIFF=1.25×(RS+P⋅RL)×IFNV DIFF=1.25×(R S +P⋅R L)× NI FVDIFFV 

DIFF: Minimum required voltage setting value (taking the next step greater than the calculated value, with a step size of 50V).

RSR S: Fault CT secondary winding DC resistance+lead resistance (converted based on maximum operating temperature).

RLR L: one-way cable resistance from differential junction to fault CT (also calculated based on maximum temperature).

PP: Phase number coefficient, set to 1 for three-phase short circuits and 2 for single-phase grounding (because the current passes through a two core cable circuit during single-phase).

IFI F: Maximum out of zone fault current (primary symmetrical effective value), usually taken as the maximum breaking current of the circuit breaker or the maximum short-circuit current of the system.

NN: CT ratio (e.g. 1200/5, then N=240).

1.25 is the reliability coefficient.

Simplified method (compliance): directly take the maximum breaking current of all circuit breakers as

IFI F, Take the cable resistance of the farthest CT as RLR L and set P=2. Calculate once to obtain the maximum value

VDIF FV DIFF, Then take a higher level. This method is simple and does not require recalculating with system changes.

Accurate method: Calculate the three-phase and single-phase faults at each feeder end separately, take the corresponding IFI F and RLR L, calculate them separately, take the maximum value, and then take the higher level. This method may result in lower setting values and improve sensitivity.

Example: A 1200/5 CT, RS=0.524 Ω R S=0.524 Ω, farthest CT cable one-way resistance 0.493 Ω, maximum short-circuit current 12500A, N=240. then

VDIFF=1.25×(0.524+2×0.493)×12500/240≈98.3V 

V DIFF=1.25 × (0.524+2 × 0.493) × 12500/240 ≈ 98.3V, select the next level of 100V.

4.2 Current setting

The current setting needs to consider the following factors:

Avoiding CT circuit induced noise: Due to the high impedance of the differential circuit, external faults may induce voltage, but the induced current is extremely small. To prevent misoperation, the current setting is generally not less than 0.5A.

Combined with CT testing function: When using a CT testing source, the test current under an unhealthy CT circuit (short circuit) is approximately

Vtest/100V 

Test/100 (100 Ω series resistance) is usually around 0.3A, so the current setting should be greater than this value, such as 0.5A.

If there is a lightning arrester, the current setting must be set to 2.5A (highest level) to avoid the surge current during the operation of the lightning arrester.

If high sensitivity is desired, 0.25A or 0.5A can be set when there is no lightning arrester and the system is impedance grounded.

4.3 Minimum internal fault sensitivity verification

It is necessary to ensure that the relay can reliably operate in the event of minimal internal faults on the busbar (such as single-phase grounding). Sensitivity verification requires the peak characteristics corrected by the excitation characteristic curve of CT.

Steps:

Find the inflection point voltage based on the conventional excitation curve (effective value) of CT

EsE s and inflection point current IeI e.

Calculate points on double logarithmic coordinates

V=7Es

V=7E s,I=5Ie

I=5I e, Draw a straight line with a slope of 1/2 across this point (voltage corresponds to two ten times the current for every ten times the current), and form a corrected peak curve at the intersection with the extension of the lower straight line of the original curve.

Calculate the voltage required for the operation of relay voltage components

VS=22×VDIFF

V S=22 × V DIFF (in this case, VS=2.83 × 100=283VV S=2.83 × 100=283V).

Read the excitation current Ie'E '(approximately 0.05A in this case) corresponding to the voltage from the correction curve.

The current of the relay itself at the critical point of action is IR=(2 × VDIFF)/5000 Ω=0.04AI

R=(2 × V DIFF)/5000 Ω=0.04A (internal impedance of the relay is approximately 5000 Ω).

The total operating current (secondary value) is the sum of the excitation currents of each CT plus the relay current. If there are n CTs with the same characteristics, then

Iminsec=n × Ie '+IRI min_dec=n × Ie+IR, multiplied by the transformation ratio N to obtain the minimum operating current once.

Example (5 CTs, each 0.05A):

Iminsec=5 × 0.05+0.04=0.29AI min_dec=5 × 0.05+0.04=0.29A, with a primary value of 0.29 × 240 ≈ 70A. When the current is set to 0.5A, the corresponding primary current is 0.5 × 240=120A, and the larger one is taken, so the minimum operating current is 120A once. If the minimum fault current of the system is much greater than this, then the sensitivity is satisfied.

5. On site testing and verification

After new installation or maintenance, the relay's various functions should be tested according to the following steps.

5.1 Power Status and Basic Functions

Disconnect the power supply and ensure that terminals 11-12 (normally closed power status) are conducting.

Connect the rated power supply, the Power LED lights up, and 11-12 should be disconnected (indicating that the power supply is normal).

Disconnect the power supply, 11-12 should restore conductivity (fail safe design).

5.2 Alarm Voltage (CT OV) Test

Assuming Pickup Voltage=50V and Alarm Voltage=10% (i.e. 5V).

Apply 4.5V (90% set) for 10 seconds, and the alarm should not activate (LED not on, 13-14 not closed).

Apply 5.5V (110% setting), and the alarm action should be triggered after a few seconds (LED on, 13-14 closed). After removal, the LED will turn off (with a delay of about 1 second).

Repeatedly verify other alarm levels (20%~80%).

5.3 Voltage Pick up (SCR Trigger) Test

Set Pickup Voltage to 50V and Pickup Current to 0.25A.

Connect the voltage source to the input terminal and configure it to automatically disconnect when tripped.

When the voltage is slowly increased to about 100V (2 × 50V), the SCR should conduct, the output contacts 17-18 should close, and the Trip LED should light up. Error ± 5%.

Press Reset to reset the LED.

Assuming Pickup Voltage=100V, repeat and operate at 200V ± 4%.

Three phase models need to be tested phase by phase.

5.4 Current Pick up Test

Set the Pickup Current to 0.25A and adjust the voltage setting to 50V (to avoid voltage misoperation, but actual current testing can be triggered by short circuiting the input or applying sufficient voltage).

When the current source slowly increases from 0 to 0.25A ± 5%, the output contact closes and the Trip LED lights up.

Test each gear (0.5, 0.75,..., 2.5A) in sequence and record the action values.

5.5 Delay Test (if used)

If it is A1 (20ms delay), set the current to 3 times the set value (such as 0.75A), and measure the time from current application to contact closure, which should be within about 24.4ms (actual delay+inherent time).

A2 (2ms delay) is approximately 6.4ms.

If no delay is required, place the jumper in position 1-2 (without delay), with an action time of<7ms (1.5 times) or<5.5ms (6 times).

5.6 CT Circuit Integrity Test (Using CT Test Button)

According to the previous tuning example, assuming V_DIFF=150V and Alarm=10% (15V), calculate the required test voltage (usually using 30V or 60V range).

Connect the CT diagnostic test source to terminals 7 and 10, press the CT Test button for about 1 minute. If there is no short circuit in the CT circuit, the CT OV LED should light up and the Alarm contact should close; If the circuit is short circuited, there will be no response.

Attention: The test current should be less than the current setting value to ensure that there is no false tripping during testing. For example, when setting 0.5A, the unhealthy current tested is about 0.3A, and the safety margin is sufficient.


6. CT testing source application and security considerations

The CT test source consists of an isolation transformer and a 100 Ω series resistor, which is used to detect whether there is a short circuit in the CT circuit without exiting the protection. When the CT Test button is pressed, the test voltage (30V or 60V) is applied to the differential circuit through a resistor. If the impedance of the circuit is normal (CT parallel impedance is several hundred ohms), the voltage at the relay terminal after resistor division reaches the alarm threshold, indicating that the circuit is intact; If there is a short circuit somewhere, almost all the voltage drops across the resistor, the relay terminal voltage is insufficient, and the alarm does not operate.

Safety design: The test voltage is much lower than the SCR triggering voltage (2 × V_DIFF is usually ≥ 100V), and even if SCR is accidentally triggered, the relay will not trip due to the test current being less than the current setting value (such as 0.5A), so the testing process does not affect the safety of protection.


7. Maintenance and Storage Suggestions

BE1-87B is a solid-state relay that only requires regular (recommended annual) functional testing for daily maintenance. If stored for a long time, the internal electrolytic capacitor should be powered on for 30 minutes every year to maintain its performance. When abnormalities occur, contact the manufacturer for repair and do not dismantle or repair on site.

  • Basler DECS-250-CGCM-LN2SA1C Digital Excitation Control System
  • Valmet Automation PLC Module A413171
  • Valmet Automation 542852-3A Rack-Mount Cross Connect Panel
  • Valmet Marine Damatic M851565 Main Keyboard
  • Valmet TIU 6 Printed Circuit Board A413110
  • Metso Valmet U4440253V1.1 RMI CPU 300
  • Metso Valmet A413016 Ver.12 NCU2
  • Valmet M851565 Damatic Keyboard
  • Valmet ATB16-4 16 Channel Relay Card
  • Valmet Metso A413331 SPU Power Supply
  • Valmet PUD 10B Automation Control Rack
  • Valmet MT917 ABMB DMU PCB I/O Module
  • Valmet M851565 Damatic Keyboard Mkb2
  • Valmet EDS-518A-MM-SC Ethernet Gateway
  • Valmet 542836-6A PCB Card
  • Valmet ATB16-4/2 Terminal Board 9144047
  • Valmet ATB16-4 Controller Board 0-50°C 4-20mA Analog Output
  • Valmet 542852-3A Slot Rack Chassis Module
  • Valmet A413026 Ver.M1 FBC Board
  • Valmet IQ Basis Weight SH Sending Assembly A418081
  • Valmet PMB 2R Monolithic Backplane 8-Slot PCB 542821-5A and -5B
  • Valmet ATB16-4 16-Channel Relay Card Controller Board 22195028
  • Valmet Diff-EL SL6NK227SF0 Pressure Transmitter 0-380 mBar
  • Valmet A413110 TIU6 Board Ver.M1
  • Neles Automation A413278 Control Module
  • Valmet BCUTB Terminal Module 10101006 11091002
  • Valmet Senso 160 Measuring Station Display 160.2
  • Valmet AIU 1A Analog Input Unit M851245
  • Valmet IQ Web Caliper Sensor A420734
  • Valmet M851040/M8510401 Memory Board
  • Valmet AN35S1MC02RA Valve
  • Valmet M851121 M2 Cross Connect Panel
  • Valmet AIU-8 Simulator Board 421522-1A
  • Metso BIU 82 D200533 Binary Input Unit
  • Valmet M851121 M2 Module Rack
  • Valmet A413383 PC Board Module
  • Valmet N0542 NO54 ABMB PCB - 545200-3A Board
  • Valmet Metso IOP304 Input Module 181503
  • Valmet PDP601 Distributed Processing Unit 181585
  • Valmet A413084 CPU Board - Processor Module for Automation Systems
  • Valmet AIU 16T Analog Input Module M8512081 M1
  • Valmet AIU 16 Analog Input Module 545100-3A and 545100-3B
  • Metso Valmet BIU4 A413146 Binary Input Unit
  • Valmet AIU-8 Simulateur Board 421522-1a Analog Simulator
  • Valmet BIU8A Binary Input Unit 542803-3B M851222 M1
  • Valmet IQ Web Color DH Photoelectric Sensor A418182 2.04
  • Valmet A413200 AIU-8 Simulator Board 191151 421522-1A
  • Valmet Automation SCU M851006 System Control Unit Module
  • Valmet 857565/851565 Damatic Keyboard IP40 5V Operator Interface
  • Valmet A413077 FBC2 Module Rev 06 Field Bus Controller
  • Valmet DMU 2 PCB Module 545142-3A DM Data Management Unit
  • Valmet AIU16T PCB Card M851208 Analog Input Module
  • Valmet A413181 PLU Board
  • Valmet m851006 SCU Module
  • Valmet Metso 181226 Digital Input Module
  • Valmet AIU16T Analog Input Module - 16-Channel 65421466-2B MT924 V1.3
  • Valmet WIN3136875 Slide Clutch
  • Metso Valmet TIU61 A413111 Temperature Input Unit
  • Valmet MC12S Slitter Motor
  • Valmet A413139 AOH4 Board - Analog Output High Module
  • Valmet A409001 BIU85 Board
  • Valmet A413063 DMU Board
  • Valmet A413325 IPU I/O Power Unit
  • Valmet M851004 M2 CPU Module
  • Valmet IOP345 Digital Input Module
  • Metso Valmet A413215 Communication Board
  • Valmet DIFF-EL 80 M1 Transmitter
  • Valmet A413001 CPU Module
  • Valmet M899520 TDC-2 Module
  • Valmet A409001 BIU85 Board
  • Metso Valmet A413005 CPU Module
  • VALMET PUD 10 B Process Automation Rack with CPU SCU Module
  • Valmet A413091 GDU1 Board
  • VALMET M851006 M2 SCU Module
  • Lyngso Valmet Marine 990.896.000 Position Loop Card
  • Valmet Cooking Liquor Measurement 3417H
  • VALMET ABMB MT831 PCB Card
  • Valmet Automation A413325 IPU I/O Power Unit
  • Valmet Metso Consistency Transmitter Smart Pulp M2
  • VALMET METSO A413274 Connection Module
  • VALMET PI33S1KSA02RSA-ELI26 Switch
  • VALMET ND9103HN-CE07-K05 Intelligent Valve Controller
  • VALMET PMB 2R 16 Slot Backplane PCB Card
  • NELES VALMET A413135 AOU 4 Output Module
  • Metso Valmet A413345 FPU Power Unit
  • VALMET A413171 PIC Module
  • VALMET A413620 Repeater Module
  • Valmet M851521 Memory Card
  • Valmet DIFF-EL 140 M1 Transmitter
  • Valmet A413064 DMU Module
  • Valmet IOP371 I/O Bus Extender Module
  • Valmet Cooking Liquor Measurement 3400 Model 3417H
  • Metso Valmet A413043 CPU Module – Industrial Processor
  • Valmet BIU4 M851221 Binary Input Module
  • Valmet PMB 1S CPU SCU Rack Module
  • Valmet A413248 Controller Module
  • Valmet PDP601 Distributed Processing Unit
  • VALMET M851004 M2 CPU Printed Circuit Board Module
  • Metso Valmet A413045 Ver.05 CPU Module
  • Valmet A413181 Ver.05 PLU1 Board
  • Lyngso Valmet ATB16 Controller Board
  • VALMET AIU 16 Analog Input Unit 545100-3A/3B
  • VALMET PUD 10 B Power Supply PCB Rack Module
  • Valmet MS-50V/120V Bearing Unit
  • Valmet PDP603 Distributed Processing Unit – DPU Module
  • Valmet A413110 TIU Board – Terminal Interface Unit
  • Valmet S420154 I/O Backplane PCB – Printed Circuit Board
  • Valmet A413173 Industrial Control Module
  • Valmet A413044 CPU Module
  • Valmet A4IU1 Analog I/O Module
  • Valmet A413325 IPU Power Unit – PLC Module
  • Valmet M851002 CPU Module – Central Processing Unit
  • Valmet PUD10B Power Supply Board
  • Valmet K00990 Master CPU Electronic Assy
  • Valmet Metso IOP345 Input Module
  • Metso Automation T545215 Board
  • Valmet Metso IOP304 Input Module
  • Valmet 542844-6A SCU Module
  • Metso A413043 Ver.11 Valmet CPU Module
  • Valmet Automation BIU 8A Input Module
  • Metso A413044 Ver05 Valmet CPU Module
  • VALMET 542821-5A Control System Rack Module
  • Metso A413005 Ver.04 Valmet CPU Module
  • Valmet M851207 AIU16 Card
  • Valmet BIU8 Binary Input Unit
  • VALMET 547070-2B CPU Printed Circuit Board Module
  • Valmet Automation A413325 Power Module
  • VALMET AUTOMATION A413135 AOU4 Module