3.3 Parallel/Independent Switch (43P)
This switch selects the control mode:
P (Parallel): Enable the circulation compensation function, and the controller adjusts the tap according to the circulation signal.
I (Independent): Disable circulating current compensation, and each transformer is independently regulated (suitable for disconnection operation or maintenance).
Important warning: When the transformer is in parallel and under automatic control, it is absolutely forbidden to turn the switch from "P" to "I", as this will cause the controller to lose its ability to correct circulating current, which may result in the two transformer taps adjusting in opposite directions, causing a sharp increase in circulating current and damaging the equipment. The correct switching sequence is to first set all transformer controls to manual or release parallel connection, and then switch modes.
Key points of wiring and system integration
4.1 Basic wiring scheme
The terminal block (TB1) of M-0115A mainly includes:
Current input (K1, K2 or ACT): used to connect the circulating current CT signal (0.2A).
Calibration signal output: sent to the circulating current input terminals of each voltage regulator controller.
The typical wiring is as follows:
The CT secondary of each transformer (converted by auxiliary CT) is connected to its corresponding load CT input terminal of the voltage regulator controller, and the CT signal is also connected in series or parallel to the circulating current detection winding of M-0115A.
The correction signal output by M-0115A (usually in the form of voltage or current) is then sent in parallel to the circulating current input terminals of all voltage regulating controllers.
4.2 Coordination with different controllers
M-0067E: This controller has an independent circulating current input (0.2A), but it should be noted that its line voltage drop compensation and circulating current compensation share the CT input channel and need to be switched through internal jumpers or external switches. The output of M-0115A can be injected into this input, either as a substitute or in addition to the load current.
M-2001C/D: The new digital controller has dedicated circulating current input terminals and phase angle correction settings, supports direct connection to the output of M-0115A, and can adjust phase shift through software to simplify wiring.
4.3 Effects of auxiliary contacts on circuit breakers
If there are line circuit breakers (52) or contact circuit breakers (24) in the system, their auxiliary contacts should be connected to the logic circuit of M-0115A to ensure that the corresponding transformer is automatically switched to independent mode when the circuit breaker is opened. In the wiring diagram, auxiliary contacts are usually in a closed state (parallel mode) when the circuit breaker is closed, and when disconnected, the parallel circuit is disconnected. If there is no such circuit breaker on site (such as using only one common load switch), it should be handled according to the principle of "normally closed contacts connected to the circuit, normally open contacts not connected".
4.4 Precautions for manual operation
When manually operating the load switch, each voltage regulator controller must be placed in the "MANUAL" position, and the 43P switch of M-0115A must be placed in "I" (independent) before operating the switch. Otherwise, there is a possibility of misadjustment due to sudden changes in circulation during the operation process.

On site debugging and troubleshooting
5.1 Pre operation inspection
CT polarity: Ensure that all CT polarities are consistent, otherwise the circulation detection will reverse, resulting in incorrect correction signals.
Auxiliary CT ratio: Confirm that the 5A: 0.2A ratio is accurate, with an error within ± 1%.
Initial sensitivity setting: Set to the middle gear and fine tune after the system stabilizes.
Switch position: Confirm that 43P is in the "P" position and each controller is in "AUTO" or "REMOTE".
5.2 Debugging steps
Close the power supply of each transformer and confirm that there are no abnormal loads.
Adjust one of the transformers to the rated tap and observe whether the tap of the other transformers follow the adjustment (if the voltage deviation is large, the controller will prioritize voltage adjustment first).
After the voltage stabilizes, observe the circulating current (using a clamp meter to measure CT twice, converted to once). If the circulation is greater than 5% of the rated value, gradually adjust the sensitivity and observe the changes in circulation.
If the circulation continues to be large, check the CT polarity and wiring, and if necessary, exchange the S1/S2 terminals of a certain CT.
Conduct a load mutation test to observe whether the controller response is stable and without oscillation.
5.3 Common faults and their solutions
Possible causes and solutions for the fault phenomenon
Excessive circulation, inconsistent tapping, low sensitivity setting, increase sensitivity (reduce gear)
The tap frequently operates, and the system oscillation sensitivity is set too high to reduce sensitivity (increase the gear position)