Direction power (32) action direction error voltage or current phase reversal; Check the ABC/ACB settings for phase rotation errors and verify the voltage current angle using a phase meter; If using line voltage and phase current (Type B), pay attention to the inherent phase shift of 30 °
VT fuse detection (60FL) mistakenly detects PT secondary circuit disconnection or single-phase voltage loss. Check PT fuse and wiring; Confirm whether the negative sequence voltage/current criterion is met; External fuse input lockout can be enabled
The frequency (81) is set close to the system frequency due to misoperation after grid connection, or the circuit breaker auxiliary contact (56a) is not used to lock the circuit breaker position to prevent low-frequency misoperation during shutdown; Increase delay (≥ 5 cycles) to avoid transients
The sensitivity of the rotor grounding (64F) is insufficient, and the rotor capacitance is too large or the injection frequency is not suitable. Adjust the injection frequency (0.1~1.0Hz) to match the capacitance, and refer to Table 2-5 in the manual for typical values; Ensure correct wiring of M-3921 coupling module
Precautions for replacing old relays
When replacing electromechanical or early solid-state relays with M-3425A:
Voltage input: Confirm that the PT secondary voltage is within the rated range (50-140V). If it is a 69V phase voltage, set the VT configuration to "LG to LL" and input the line voltage value correctly.
Current input: Confirm that the CT rating is 1A or 5A, and select the corresponding version when ordering.
Output contacts: Electromechanical contacts usually have a larger capacity (such as 5A DC), while M-3425A output contacts have a smaller arc breaking ability (0.3A inductive). When driving the trip coil, an external intermediate relay is required.
Time characteristics: Digital relays have more flexible inverse time curves (IEC, IEEE, BECO), which can be more accurately matched with fuses and low-voltage protection, without worrying about aging drift.
Power requirement: M-3425A supports a wide range of AC/DC power supply (such as 125VDC or 120VAC), without the need to replace the original power circuit.
Maintenance and Storage
Regular verification: It is recommended to verify the accuracy of the main protection functions according to the manual testing program every 1-2 years, and record the data for archiving.
Clock Battery: The internal clock module contains lithium batteries. When stored for a long time (>5 years), it needs to be powered on once a year or the clock should be stopped before storage (through the diagnostic menu) to prevent the battery from running out.
Cleaning: Keep the chassis ventilated, regularly remove dust, and check the terminal tightening torque (7.5~9.0 in lbs).
Firmware upgrade: Contact the manufacturer to obtain the latest firmware, which can be upgraded through RS-232 or Ethernet.