Installation Steps: First, make sure the installation surface is flat and meets the requirements. Then, use the provided fasteners to fix the CP450.
The installation depth is 51.6 mm, and the opening size is 286.0 x 211.0 mm.
Grounding: The operator terminal should be grounded with a cable of at least 2 mm² (AWG 14),
and the grounding resistance must be less than 100 Ω (Class 3).
Note that the grounding cable cannot be connected to the same grounding point as the power circuit.
Power Supply and Wiring: The CP450 is powered by 24V DC ± 15%.
The power connector on the back of the operator terminal should be properly grounded. When connecting the power supply, make sure the ground is good. Communication cables must be separated from the power cables of the operating circuit and only shielded cables should be used.
Product Specifications
Dimensions: The front panel is 297.0 x 222.0 x 9.0 mm in size, and the net weight is 1.9 kg.
Communication Ports: COM1 is a 9 - pin female connector for RS232/RS485, COM2 is a 25 - pin female connector for RS232/RS422/RS485,
and COM3 is a 9 - pin female connector for RS422/RS485. It also has an Ethernet port, 2 USB host ports, and 1 USB device port.
Memory: It has 8 MB of flash memory, 16 MB of RAM, a 32 - bit RISC CPU, 512 KB of battery - powered memory for data/recipes, and a CF card port.
Display: It features a color TFT liquid - crystal display with 64K colors, a resolution of 640 x 480 pixels, and a CCFT backlight with a lifespan of approximately 50,000 hours at 25 °C.
Operation
Self - Test: The CP450 can perform a self - test to check the hardware status.
System Menu: The system menu provides various functions, such as setting communication parameters, calibrating the touch screen, and downloading/uploading applications.
Keyboard: There are 8 keys on the CP450, including a menu key and 7 function keys (F1 - F7).
The function keys can be defined in CP400Soft as "shortcut keys" for operations such as setting ON/OFF values and changing screens.
Bench and Function Tests: By setting dip switches SW3 and SW4 to OFF, the bench and function tests of the CP450 can be run.
Communication Parameter Settings: Communication parameters can be set either on the operator terminal or in CP400Soft.
On the operator terminal, select F2 - Config in the system menu to set parameters.
Touch - Screen Calibration: Use the system menu command F4 - Set to calibrate the touch screen.
Touch the upper - left and lower - right corners of the screen as prompted, and then touch the square in the center of the screen to complete the calibration.