HONEYWELL INTELLIKNIGHT®MODEL 5700 Addressable Fire Alarm Control Panel

F: | Au:FAN | DA:2026-03-23 | 356 Br: | 🔊 点击朗读正文 ❚❚ | Share:

For UL 864 certified installations, the following programming restrictions must be followed:

Low AC report delay: must be set to 1-3 hours (central station/remote signal application)

Alarm verification time: must be set to 1-60 seconds

Automatically display earliest events: must be enabled


Key points for installation and wiring

1. Cabinet installation

The dimensions of the 5700 cabinet are 12.75 inches wide by 15.125 inches high by 3.375 inches deep. Attention should be paid during installation:

Avoid installing in locations that may be damp

Concrete walls should be installed with 3/4 inch plywood before fixing the cabinets

The conduit should enter from the side or bottom, and entering from the top can easily cause water vapor to enter

2. Wiring specifications

High voltage (AC power) and low voltage (SLC, SBUS, telephone lines) must be wired separately

Separate conduits should be used for different functional wires to avoid electromagnetic interference

Notification circuits, relay circuits, SLC loops, etc. should be routed along the inner edge of the cabinet to avoid crossing the circuit board

3. Battery connection

The batteries are connected in series to form a 24 VDC power supply. The battery cable (red positive black negative) needs to be connected correctly, as incorrect polarity can damage the panel. The RBB battery cabinet can be used to store larger capacity batteries, and the distance between the battery cabinet and the main cabinet should not exceed 18 inches.

Programming and Configuration

The 5700 control panel can be programmed through the front panel menu or the Silent Knight software suite (SKSS).

1. JumpStart automatic programming

JumpStart is the recommended programming method for initial system installation. After running JumpStart, the system will:

Scan SLC loop to identify all detector and module types

Create Zone 1 and assign all input points to Zone 1

Create an output group and assign the notification circuit to Group 1

Map Zone 1 to Group 1 (alarm events use constant light mode)

Assign relay 1 to Group 124 (for monitoring events)

Assign relay 2 to Group 125 (for alarm events)

Important note: JumpStart should only run once after the system is powered on for the first time and the SLC device completes address settings. After running, all manual configurations will be reset, so it cannot be repeated after the system has been configured.

2. Manual programming

The system supports up to 125 input zones and 125 output groups. Programming options include:

Input point configuration:

Equipment types: photoelectric detector, ion detector, thermal detector, manual pull station, water flow switch, monitoring switch, etc

Regional allocation: Each input point can be assigned to a region

Locked/unlocked: The locked point needs to be manually reset, while the unlocked point automatically recovers

Muteable/Unmute: determines whether the point can be suppressed by pressing the mute button

Output group configuration:

Output modes: constant light, continuous, ANSI 3.41, UL encoding, etc

Muteable/Unmute: determines whether the output of the group can be muted

Locked/unlocked: determines whether the output will automatically reset after the condition is restored

Reverse polarity: used for remote station applications

Regional event mapping:

Each region can map 11 types of events (manual pull station alarm, water flow alarm, detector alarm, pre alarm, monitoring, fault, CO alarm, etc.), and each event can activate up to 8 output groups or output group templates.

3. User access code

The system supports up to 20 user profiles:

Configuration File 1 (Firefighter Key): Read only permission, can perform specific functions (such as fire drills)

Configuration file 2 (installer code): highest authority, factory default 123456

User Profile 3-20: Customizable Name, Code, and Function Permissions (System Reset, Mute, Confirm, Point Function, Programming, etc.)


Operation mode and system behavior

The 5700 control panel can operate in multiple modes during operation:

Mode triggering condition system behavior

Normal, no alarms, no faults, no monitoring. The green power LED is always on and displays a custom banner

Alarm detector alarm, manual pull station activation DACT dialing, continuous local buzzer sound, red alarm LED flashing, notification circuit activation

Monitoring switch activation (such as water flow pressure monitoring) DACT dialing, buzzer pulse sound (1 second on/1 second off), yellow monitoring LED flashing

System malfunction (battery, SLC open circuit, AC power failure, etc.) DACT dialing, buzzer pulse sound (1 second on/9 seconds off), yellow fault LED flashing

Pre alarm 2-Count: A single detector in the area will sound the local buzzer, and the output group can be programmed to activate without reporting to the central station

Silent alarm or fault has been muted but the condition has not been restored. The system mute LED is on, indicating that the circuit is silent and the LED remains lit

After pressing the reset button, all LEDs briefly light up, and the system resets the detector to restore normal operation or re-enter the alarm state


Releasing Operations

The 5700 control panel supports single interlock and double interlock release systems, suitable for applications such as pre action fire extinguishing systems and rain shower systems. The release function must be equipped with a 5496 intelligent power module.

  • Basler DECS-200-2L Digital Excitation Control
  • Basler BE1-47N Voltage Phase Sequence Relay
  • Basler AEC63-7 Analog Excitation Controller 220-277V
  • Basler BE1-50/51B-107 Overcurrent Relay
  • Basler Electric BE1‑32R BE1‑E1P‑BON0F Protective Relay
  • Basler BE1-25 Solid State Time Overcurrent Relay M1EA6PA5S1F
  • Basler MVC 232 Manual Voltage Control Module 90 37000 103 60VAC 55VDC
  • Basler RAL6144-16GM Racer GigE Line Scan Camera
  • Basler SSR 63-12 Static Voltage Regulator
  • Basler BE1-51A Overcurrent Relay
  • Basler BE1-87T Solid State Protective Relay
  • Basler SR4A2B01B3A Static Voltage Regulator
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler TRR00696 Transformer 1KVA 115V
  • Basler DECS-100-B15 AVR Replacement
  • Basler BE1-27 Under-Voltage Relay
  • Basler ACA2000-50GM Interface Module
  • Basler AEC63-7 Analog Excitation Controller
  • Basler PRS 250 Veri-Sync Relay
  • Basler SR4A-2B15B3A Static Voltage Regulator
  • Basler BE1-32R Power Relay
  • Basler SR8A-2B06B3E Static Voltage Regulator
  • Basler BE1-81 O/U Frequency Relay
  • Basler BE1-51A-K2E-W6M-B1N0F Overcurrent Relay
  • Basler BE1-851 Overcurrent Relay G3A1S1 – 48-125V AC/DC
  • Basler BEI-51 Overcurrent Relay – NSN 5945-01-293-2363
  • Basler Electric L301KC Protective Relay – L301KC
  • Basler DECS-100-B15 Automatic Voltage Regulator – Generator AVR
  • Basler SR4A-2B15B3A Static Voltage Regulator – SR4A2B15B3A
  • Basler UF 312 Under Frequency Protective Module – 9094700100
  • Basler Electric MVC 232 Manual Control Module – 60VAC 55VDC 20A
  • Basler PRS 250 Veri-Sync Relay – Generator Synchronizing Relay
  • Basler DECS-100-A05 Digital Regulator Review
  • Basler AEM-2020 Analog Expansion Module Specs
  • Basler DECS-100-B15 Digital Excitation Specs
  • Basler Electric 9125600106 Regulator Component
  • Basler BE1-51A-K1E-W6M-B1N0F Overcurrent Relay
  • Basler MVC-301 MVC 300 Excitation Controller
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler 9-2849-00-101 Control Module
  • Basler BE1-51A Overcurrent Relay
  • Basler BE1-51/27R Overcurrent Relay
  • Basler BE1-51 Overcurrent Relay
  • Basler SR8A-2B15B3A Static Voltage Regulator
  • Basler BE32965001 Transformer and Timer Board
  • Basler 9174700100 EL200-7 Excitation Limiter
  • Basler BE2000E AVR Voltage Regulator
  • Basler BE1-87G Differential Relay
  • Basler BE21834001 Generator Control Module
  • Basler DECS-100-B15 AVR
  • Basler D90 96801 100 PCB Card
  • Basler XR2002F Voltage Regulator (110 VAC, 48-480 Hz)
  • Basler SR8A-2B14B3A Regulator
  • Basler 9561500100 Module
  • Basler DECS-400 BE1-11 System
  • Basler DECS-100-B15 Excitation Control
  • Basler SCP 210 Frequency Controller
  • Basler SR4A-2B15B3A Static Voltage Regulator
  • Basler BE1-32R Power Relay
  • Basler PIA2400-17GM Power Interface Adapter
  • Basler MVC 232 Manual Voltage Control Module
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler 5MW AVR Generator Voltage Regulator
  • Basler VR63-4B Voltage Regulator
  • Basler DECS-100-A05 AVR for Engine Generator
  • Basler DECS-100-B15 Automatic Voltage Regulator
  • Basler BE1-32R Directional Power Relay
  • Basler BE1-87B Differential Relay
  • Basler UFOV 260A Protective Module
  • Basler 9-2614-02-100 PCB Rev M
  • Basler DECS-100-B15 Digital AVR
  • Basler 9284900103 PS DECS-400N
  • Basler D4N3H1U Intertie Protection
  • Basler DECS-100-B15 A15 AVR
  • Basler KR4F Voltage Regulator
  • Basler BE26434 T14 Transformer
  • Basler SR8A-2B15B3A Regulator
  • Westinghouse 774B472A12 AR Relay
  • Basler DECS-100-B15 AVR
  • Basler XR2002F Regulator 110V
  • Basler SR125-E Static Regulator
  • Basler SSR 125-12 Regulator
  • Basler MOC2599 Motor Pot
  • Basler BE1-DFPR Feeder Relay
  • Basler CBS 305 Current Boost
  • Basler BE1-25 AutoSync
  • Basler MVC 300 Voltage Control
  • Basler BE3-25A AutoSync
  • Basler KR7FF Static Regulator
  • Basler 90-49000-100 Regulator
  • Basler 880 kVA Dry Type Transformer Specs
  • Basler Electric BE1-25 Sync-Check Relay Specs
  • Basler SSR 125-12 Voltage Regulator Specs
  • Basler Electric BE1-851 Overcurrent Relay Review
  • Basler Electric 149D930G02 Control Sub-Assembly
  • Basler Electric BE1-81O/UT Frequency Relay Specs
  • Basler Electric BE1-51/27C Overcurrent Relay
  • Basler Electric 149D956G02 Industrial Component
  • Basler Electric BE1-51A Overcurrent Relay Specs
  • Basler Electric BE1-40Q Loss of Excitation Relay
  • Basler DECS-200 Excitation Control System
  • Basler DECS-200 Voltage Regulator 56-277V AC / 125V DC
  • Basler BE1-87T Transformer Differential Relay
  • Basler RDP-110-S1 Protection Relay
  • Basler BE1-700V Digital Protective Relay
  • Basler BE1-951 Overcurrent Protection System
  • Basler DECS-300 Digital Excitation Control
  • Basler DECS-200 Digital Excitation Control
  • Basler DECS-200-1C Excitation Control System
  • Basler DECS-200-1L Digital Excitation Control
  • Basler Electric BE1-GPS Generator Protection System
  • Basler Electric DECS-200-1C Digital Excitation Controller
  • Basler Electric DECS125-15 Excitation Control with Power Module
  • Basler Electric BE1-87G Differential Relay
  • Basler Electric BE1-11 Protection System I5A3M2P2N0EA00
  • Basler Electric DECS-200-1C Excitation Control System
  • Basler Electric BE1-11g Generator Protection Relay
  • Basler Electric DECS 125-15-B2C1 V2.0.9 Excitation Control
  • Basler Electric BE1-81O/UT3ED1JA7N2F Frequency Relay
  • Basler Electric BE1-81O/UT3EE1YB7N1F Frequency Relay
  • Basler Electric DECS-200-1L Digital Excitation Control System
  • Basler DECS125-15-B2C1 Excitation Control
  • Basler 9507900205 SSR Retrofit Voltage Regulator
  • Basler BE2000E Digital Voltage Regulator
  • Basler BE1-GPS Generator Protection System
  • Basler DECS-250-CN1CN1N Digital Excitation Control
  • Basler DGC-2020 Genset Controller
  • Basler BE1-81O UT3ED1LA7N0F Frequency Relay (Variant)