HONEYWELL INTELLIKNIGHT®MODEL 5700 Addressable Fire Alarm Control Panel

来源: | 作者:FAN | 发布时间 :2026-03-23 | 250 次浏览: | 🔊 Click to read aloud ❚❚ | Share:

For UL 864 certified installations, the following programming restrictions must be followed:

Low AC report delay: must be set to 1-3 hours (central station/remote signal application)

Alarm verification time: must be set to 1-60 seconds

Automatically display earliest events: must be enabled


Key points for installation and wiring

1. Cabinet installation

The dimensions of the 5700 cabinet are 12.75 inches wide by 15.125 inches high by 3.375 inches deep. Attention should be paid during installation:

Avoid installing in locations that may be damp

Concrete walls should be installed with 3/4 inch plywood before fixing the cabinets

The conduit should enter from the side or bottom, and entering from the top can easily cause water vapor to enter

2. Wiring specifications

High voltage (AC power) and low voltage (SLC, SBUS, telephone lines) must be wired separately

Separate conduits should be used for different functional wires to avoid electromagnetic interference

Notification circuits, relay circuits, SLC loops, etc. should be routed along the inner edge of the cabinet to avoid crossing the circuit board

3. Battery connection

The batteries are connected in series to form a 24 VDC power supply. The battery cable (red positive black negative) needs to be connected correctly, as incorrect polarity can damage the panel. The RBB battery cabinet can be used to store larger capacity batteries, and the distance between the battery cabinet and the main cabinet should not exceed 18 inches.

Programming and Configuration

The 5700 control panel can be programmed through the front panel menu or the Silent Knight software suite (SKSS).

1. JumpStart automatic programming

JumpStart is the recommended programming method for initial system installation. After running JumpStart, the system will:

Scan SLC loop to identify all detector and module types

Create Zone 1 and assign all input points to Zone 1

Create an output group and assign the notification circuit to Group 1

Map Zone 1 to Group 1 (alarm events use constant light mode)

Assign relay 1 to Group 124 (for monitoring events)

Assign relay 2 to Group 125 (for alarm events)

Important note: JumpStart should only run once after the system is powered on for the first time and the SLC device completes address settings. After running, all manual configurations will be reset, so it cannot be repeated after the system has been configured.

2. Manual programming

The system supports up to 125 input zones and 125 output groups. Programming options include:

Input point configuration:

Equipment types: photoelectric detector, ion detector, thermal detector, manual pull station, water flow switch, monitoring switch, etc

Regional allocation: Each input point can be assigned to a region

Locked/unlocked: The locked point needs to be manually reset, while the unlocked point automatically recovers

Muteable/Unmute: determines whether the point can be suppressed by pressing the mute button

Output group configuration:

Output modes: constant light, continuous, ANSI 3.41, UL encoding, etc

Muteable/Unmute: determines whether the output of the group can be muted

Locked/unlocked: determines whether the output will automatically reset after the condition is restored

Reverse polarity: used for remote station applications

Regional event mapping:

Each region can map 11 types of events (manual pull station alarm, water flow alarm, detector alarm, pre alarm, monitoring, fault, CO alarm, etc.), and each event can activate up to 8 output groups or output group templates.

3. User access code

The system supports up to 20 user profiles:

Configuration File 1 (Firefighter Key): Read only permission, can perform specific functions (such as fire drills)

Configuration file 2 (installer code): highest authority, factory default 123456

User Profile 3-20: Customizable Name, Code, and Function Permissions (System Reset, Mute, Confirm, Point Function, Programming, etc.)


Operation mode and system behavior

The 5700 control panel can operate in multiple modes during operation:

Mode triggering condition system behavior

Normal, no alarms, no faults, no monitoring. The green power LED is always on and displays a custom banner

Alarm detector alarm, manual pull station activation DACT dialing, continuous local buzzer sound, red alarm LED flashing, notification circuit activation

Monitoring switch activation (such as water flow pressure monitoring) DACT dialing, buzzer pulse sound (1 second on/1 second off), yellow monitoring LED flashing

System malfunction (battery, SLC open circuit, AC power failure, etc.) DACT dialing, buzzer pulse sound (1 second on/9 seconds off), yellow fault LED flashing

Pre alarm 2-Count: A single detector in the area will sound the local buzzer, and the output group can be programmed to activate without reporting to the central station

Silent alarm or fault has been muted but the condition has not been restored. The system mute LED is on, indicating that the circuit is silent and the LED remains lit

After pressing the reset button, all LEDs briefly light up, and the system resets the detector to restore normal operation or re-enter the alarm state


Releasing Operations

The 5700 control panel supports single interlock and double interlock release systems, suitable for applications such as pre action fire extinguishing systems and rain shower systems. The release function must be equipped with a 5496 intelligent power module.

  • ABB 3BUS208720-001 Industrial Power Signal Interconnection Module
  • TMEIC KPAD-3122A LCD Display Keypad
  • Siemens 6SN1145-1BA02-0CA1 PLC
  • LAM 2004365 TURBO BYPASS PLC ASM
  • Omron CJ1W-CORT21 PLC Module
  • Euchner MGB-L2B-PNA-L-121853 Safety Switch
  • XPSMC32ZP Safety Controller
  • Schneider 9070T3000D33 PLC
  • Omron C200H-MAD01 AD DA Module
  • Omron NJ501-1320 CPU Controller
  • Honeywell C36TR1UA1000 Thermostat
  • Honeywell TC-RPDXX1 Power Supply Module
  • Fuji NW0E32-3 PLC Programmable Controller
  • ASM 2004219 Turbo Bypass ASM 107864 Module
  • Future IHDW-BLA4S-IM CNC MPG Handwheel
  • Wieland R1.180.0080.0 SA-OR-S1-4RK-A Safety Module
  • Reliance Electric 57C493 AutoMax Power Supply 376W
  • Siemens 3VT8563-2AA03-2KA2 MCCB 3VT8
  • B&R X20IF1072 CAN Bus Interface Module
  • Mitsubishi OSE253S2 Rotary Encoder
  • Mitsubishi NV630-SW 4P 500A Earth Leakage Breaker
  • Euchner MGB-L1B-PNA-R-121857 Safety Switch
  • Honeywell 900A01-0102 Analog Input Module
  • OMRON C500-ID219 Input Unit
  • Westinghouse EL3030R Current Limiter
  • CLA-2 3L Electric Lubrication Pump
  • Proface GP2501-TC41-24V HMI
  • Omron KM-N1-FLK Small Power Monitor
  • HPM 1D703-0040 Command 9000 Console Card
  • Siemens 3RW5074-6AB14 SIRIUS Soft Starter
  • Genie 75032 Limit Switch
  • OMRON C200H-SP001 Space Module
  • OMRON C200H-PS211 Power Supply Unit
  • OMRON C200H-OC222 Relay Output Unit
  • Keyence KV-8000SO 4221 CPU Module
  • Cincinnati Milacron 3-542-1079A Circuit Board
  • Beckhoff EL3124 Analog Input EtherCAT Terminal
  • KRONES BWU1703 0900853537 ASi PROFIBUS Gateway
  • Radio Energie RE0444 R1S 0.06 CA Tachogenerator
  • Mitsubishi GT1685M-STBA GOT1000 HMI
  • Siemens 6GK7342-5DA03-0XE0 CP 342-5 PROFIBUS
  • Allen Bradley 8520-PX-ASM3-EXEC2-63M Servo Module
  • Delta AH10PM-5A Programmable Controller
  • Siemens 3TK2805-0BB4 Safety Contactor Combination
  • EUCHNER HBA-079827 Pendant Station
  • CLC-2 4L PLC Lubrication Pump
  • KEYENCE GS-51P5 Safety Switch
  • AB 442G-MABH-R Safety Switch
  • GE Fanuc VersaMax PLC Module Set
  • Siemens 6ES7214-1HF40-0XB0 CPU 1214FC
  • Microchip DSPIC30F4011-30I/P DSC
  • FANUC A20B-2102-0081 I/O Link Module
  • Endress Hauser CLS15-B1M2A Conductivity Sensor
  • B&R 3AM050.6 Analog I/O Module
  • Fanuc A16B-2201-0320 MAIN-B CPU Board
  • Pilz 475650 PNOZ 1 Safety Gate Relay
  • Omron NSH5-AL001 Handheld HMI Terminal
  • Allen-Bradley 1756-OF8 Analog Output 8 Ch
  • Siemens 6SL3210-1SE31-0AA0 45kW Power Module
  • PMA TB45-110-00000-000 Temperature Limiter
  • PSR-SCP-24DC-ESD-5x1-1x2-300 Safety Relay
  • Pilz 774140 PZE 9 24V AC Safety Relay
  • Telemecanique TSXRKN82F 8 Slot Rack
  • Mitsubishi R16CPU iQ-R PLC CPU
  • Mitsubishi A2ACPU-R21-S1 PLC CPU
  • Omron NX-AD4208 Analog Input Unit
  • Schneider LMC802CAA10000 PacDrive 3 Controller
  • Reliance Electric 0-51874 Static Sequence Card
  • Pilz 787310 PNOZ X3P C Safety Relay
  • B&R X20CP1684 CPU Module
  • Siemens 6SN1145-1BB00-0FA1 Power Module
  • Beckhoff EL3174 Analog Input EtherCAT Terminal
  • CLC-2P 4L PLC Lubrication Pump System
  • Omron CJ1W-DA08C Analog Output Unit
  • Metso Automation D201776 ACN PO DC PLC Control Server Computer
  • GE AT868 AquaTrans Ultrasonic Flow Transmitter
  • ABB PFSA107-Z42 DTU Stressometer Digital Transmission Unit
  • ABB PFSA240 3BSE073476R1 Roll DC Supply Unit
  • Fanuc A16B-2201-0320 CPU MAIN Board
  • Pilz 475650 PNOZ 1 Safety Gate Relay
  • Omron NSH5-AL001 HMI Interface Unit
  • Allen-Bradley 1756-OF8 Analog Output Module
  • Siemens 6SL3210-1SE31-0AA0 Power Module 45kW
  • PMA TB45-110-00000-000 Temperature Limiter
  • PSR-SCP-24DC-ESD-5x1-1x2-300 Safety Relay
  • Pilz 774140 PZE 9 Safety Relay
  • Telemecanique TSXRKN82F PLC Rack Chassis
  • Mitsubishi R16CPU PLC CPU Module
  • OMRON C500-PS223-E Power Supply Module
  • Siemens 3VL4731-1DC36-0AA0 Circuit Breaker
  • Siemens 7ML5201-0EA0 Ultrasonic Level Transmitter
  • OMRON NQ3 NQ5 Touch Panel HMI
  • OMRON CJ1W-AD081-V1 Analog Input Module
  • OMRON NJ301-1100 Machine Automation Controller
  • B&R X20BC00G3 EtherCAT Bus Controller
  • Schneider ATV212HD22N4S Variable Speed Drive
  • B&R 8B0C0320HW00.002-1 Power Supply Module
  • Mitsubishi OSA105S2A Incremental Rotary Encoder
  • Pilz 777514 PNOZ XV3P Safety Relay
  • Gould AS-884A-111 Modicon 884 Controller
  • Siemens 6SC6130-0FE00 SIMODRIVE Control Card
  • Omron CV500-PS221 PLC Power Supply Module
  • ABB CM577-ETH AC500 PLC Ethernet Module
  • Omron NX-SIH400 Safety Input Unit NX Series
  • Omron NJ501-1300 Machine Automation Controller
  • Siemens 3VT8563-2AA03-2KA2 Molded Case Breaker
  • Pilz PNOZ m1p ETH 773103 Safety Controller
  • Omron CJ1H-CPU66H-R CJ1 Series CPU Module
  • ASI ASI533-S00 PLC Module S1
  • Mitsubishi AJ71C21-S1 Serial Module
  • Keyence IX-1000 Laser Sensor Amplifier
  • Siemens 6SN1145-1AA01-0AA1 Power Module
  • Siemens 3VA2340-5HL32-0AA0 MCCB 400A
  • Mitsubishi OSA104S Absolute Encoder
  • Siemens 6ES7350-1AH03-0AE0 FM 350-1 Counter
  • Siemens 6SE7038-6EK84-1JC2 IGD8 Gate Driver
  • Eaton EASY819-AC-RC Programmable Relay
  • Omron CPM1A-40CDT-D PLC 24V DC
  • Omron NA5-12W101B-V1 12-inch Programmable Terminal
  • Siemens 6ES7331-7KF02-0AB0 Analog Input SM 331
  • Moxa PTC-101-S-SC-HV Photoelectric Converter
  • Fanuc A20B-3300-0031 CNC Control Circuit Board
  • OMRON NA5-7W001B-V1 Programmable Terminal HMI
  • Parker AH385851U002 590C DC Drive Power Board
  • ABB 3BSE040662R1 AI830A Analog Input Module
  • DOLD BF9250.01/001 Solid State Relay
  • Siemens 6ES7331-7KF02-0AB0 SIMATIC S7-300 SM 331
  • ABB 07AC91 I6 GJR5252300R3101 Advant Controller 31