Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Omron NA Series HMI Connection Guide

来源: | 作者:FAN | 发布时间 :2026-04-20 | 13 次浏览: | 🔊 Click to read aloud ❚❚ | Share:

The NX series security controller communicates with HMI through its built-in EtherNet/IP port (network gateway). Note: Ports on EtherNet/IP units cannot be connected, only CPU built-in ports can be connected.

Controller settings: In Sysmac Studio, assign a fixed IP address to the network gateway and set the subnet mask and default gateway. Link speed recommendation is' automatic '.

HMI settings: basically the same as connecting to the NJ/NX/NY series. Add external devices to the device reference, select "Ethernet" for the communication driver, and enter the IP address of the security controller. Variable import supports data types such as BOOL, BYTE, WORD, WORD, SINT, INT, DINT, REAL, LREAL, STRING, as well as array and structure members.

Special precautions:

The variables of the safety controller usually have safety attributes, and the HMI can only read the status and cannot force the writing of safety outputs (this is a requirement of safety design).

If the structural variables of the safety controller are used in the project, they must be imported from the controller function and cannot be manually copied and pasted.


Connecting Programmable Multi Axis Controllers (CK3 Series): Typical Applications of Modbus/TCP

The CK3 series Programmable Multi Axis Controller is configured using PowerPMAC IDE and supports Modbus/TCP protocol. The NA series HMI communicates with Modbus/TCP clients.

Controller side settings (PowerPMAC IDE):

In "Tools" ->"Options" ->"PowerPMAC" ->"Network Settings", configure the IP address, subnet mask, and default gateway.

Enter the command Sys.ModbusServerEnable=1 in the terminal to enable the Modbus/TCP server.

HMI terminal settings:

In the HMI settings of Sysmac Studio, configure the IP address for Ethernet port 1 (to be on the same network segment as the controller).

Add external device in device reference: supplier Omron, series selection CK3 (specific model), communication driver "Modbus/TCP".

Fill in the IP address of the controller, timeout time (recommended 1-2 seconds), and communication startup waiting time (optional).

Manually add variables in the device variable table. The data type must be FLOAT (32-bit floating-point number). The address format includes I0, M0, P0, Q [0]. 0, etc. Please refer to the appendix of the manual for the scope.

Due to the fact that the Modbus/TCP protocol itself does not distinguish data types, the NA series treats all data as single precision floating-point numbers, so it is important to pay attention to numerical conversion when reading and writing.

Key points of network installation and electromagnetic compatibility

Regardless of the protocol used, the correct installation of the physical layer is the foundation of communication reliability.

Cable selection: 100BASE-TX recommends using AWG24 × 4P STP cable (such as NETSTAR-C5E SAB). It is recommended to use shielded twisted pair cables for serial port cables.

Shielding grounding: The shielding layer of Ethernet cables should be grounded at one end on the switch side to avoid ground circulation caused by grounding at both ends. The shielding layer of the serial RS-422A cable should be connected according to the principle of "ungrounded HMI side" (as shown in Figure b), and the D-SUB fixing screw of CJ1W-CIF11 must be tightened to ensure functional grounding connection.

Switch selection: For EtherNet/IP networks, it is recommended to use switches that support IGMP Snooping (multicast filtering) and L4 QoS (such as OMRON W4S1 series) to prevent multicast data from flooding and affecting real-time performance. Non managed switches do not have these functions and are only suitable for small independent networks.

Power and Grounding: The HMI power supply must use a DC24V power supply with reinforced insulation or double insulation, with a grounding resistance of less than 100 Ω. Do not ground the 24V side, as it may cause a short circuit (only applicable to non isolated NA5- □ W □□□ - V1, while NA5- □ W □□□□ - V1 is not affected for isolated types).

Environmental Protection: The NA series HMI should be installed inside the control cabinet, and the panel thickness should comply with UL Type 1 (1.6~6.0mm) or Type 4X (1.6~4.5mm, with high-pressure waterproof accessories). Avoid direct sunlight, oil mist, corrosive gases, and strong electromagnetic fields.


Common troubleshooting and precautions

7.1 Communication interruption or timeout

Check IP address: Ensure that HMI and controller are on the same subnet and there are no conflicts.

Check firewall settings: If the controller has enabled packet filtering, the IP address of the HMI must be allowed to pass through.

Security communication mismatch: If the controller enables security communication and the HMI Runtime version is lower than 1.16, the connection cannot be established. Upgrade the runtime version of the project or disable secure communication with the controller.

Serial port parameters are inconsistent: baud rate, data bits, stop bits, and parity bits must be exactly the same as the PLC.

FINS node number conflict: Within the same Ethernet segment, all FINS nodes must have unique node numbers.

  • YASKAWA SGMPH-04AAA61D-OY 200V 400W Servo Motor
  • YASKAWA SGMPH-08A1A41 750W Servo Motor with Gearbox
  • OMRON C60K-CDR-D K-Type CPU PLC
  • OMRON CS1W-AD081-V1 Analog Input Module
  • OMRON CP1H-X40DT-D Compact PLC
  • OMRON 3G3SV-BB007-E 0.75kW Inverter
  • YASKAWA SGDH-10DE-OY 1kW Servo Pack
  • OMRON C60H-C5DR-DE-V1 SYSMAC CPU PLC
  • OMRON C60H-C5DR-DE-V1 SYSMAC CPU PLC
  • OMRON 3G3MV-P10CDT3-E RS422/485 Inverter PLC Board
  • OMRON C200PC-ISA02-DRM-E SYSMAC Board PLC with Floppy & Operator Panel
  • OMRON 3G3SV-BB007-E 0.75kW Inverter
  • OMRON CP1H-X40DT-D Compact PLC
  • OMRON CS1W-AD081-V1 Analog Input Module
  • OMRON C60K-CDR-C K-Type CPU PLC
  • YASKAWA SGMPH-08A1A41 750W Servo Motor with Gearbox
  • YASKAWA SGMPH-04AAA61D-OY 200V 400W Servo Motor
  • OMRON CJ1W-DA041 Analog Output Module
  • OMRON C60H-C5DR-DE-V1 SYSMAC CPU PLC
  • OMRON 3G3MV-P10CDT3-E RS422/485 Inverter PLC Board
  • OMRON C200PC-ISA02-DRM-E SYSMAC Board PLC
  • Omron CQM1H-MAB42 Analog I/O Board
  • Omron C200PC-ISA02-DRM-E SYSMAC Board
  • Oriental Motor ARD-C CM10-1 Stepping Driver
  • EVA 915.85.003 Embedded CPU Module
  • Omron C60H-C1DR-DE-V1 PLC CPU
  • TE.CO TFX 4G10 Industrial Power Cable
  • Siemens 6SL3120-2TE15-0AA4 Motor Module
  • Emerson SolaHD SDN10-24-100P Power Supply
  • PARKER HPD2S5N/K005 Servo Drive
  • Danfoss VLT 3008 Variable Speed Drive
  • Saia Burgess Controls PCD4.H31 PLC CPU
  • OMRON C200HW-PRT21 Profibus DP Slave Unit
  • OMRON TJ1-ML04 Trajexia Motion Controller
  • Schneider Electric Pre-Wired PLC Control Box
  • Allen Bradley 1336-L8E AC Drive
  • Siemens 6ES7123-1GB60-0AB0 PLC Module
  • Automation Direct D3-08B-1 PLC Chassis 8 Slot
  • OMRON 3G3XV-A2007 VFD 0.75kW 220V
  • STOBER F102SG0230MO20 Gear Drive Technology
  • Saia PCD4.H32 PCD4 Series PLC
  • Omron NSJ12-TS01B-G5D NSJ Terminal
  • Biticino MA250 T7314A Megatiker Circuit Breaker
  • Omron ZX-LDA41 ZX-LD300L Laser Sensor
  • Siemens 6ES7511-1AK02-0AB0 CPU 1511-1 PN
  • Saia Burgess Controls SBC PCD PLC Module
  • Siemens 6ES5 244-3AA21 S5 Temperature Module
  • Omron NSJ5-SQ01-DRM NSJ Controller
  • Omron NT15S-SF121B-E Programmable Terminal
  • Yaskawa CIMR-F7Z4045 45kW VFD AC Drive
  • AB 1494U-D100 Smart Motor Controller
  • Omron NA5-7W001B-V1 Touch Screen HMI
  • Fanuc A16B-1000-0400/01A CNC Control Board
  • Omron CV2000-CPU01-EV1 PLC CPU Unit
  • Eaton XV-102-B4-35TQRF-10-PLC Touch Panel
  • Siemens 6FX1121-3BB01 SINUMERIK Board
  • SCE M68-2000 2 Axis CNC Servo Controller
  • Omron R88M-K20030T-BS2 AC Servo Motor
  • Omron G3NH-4150B Solid State Relay
  • BITICINO MA250 T7313A Megatiker PLC Disconnector
  • IFM 2MSTR AS-i PROFIBUS DP Gateway
  • Danfoss VLT 3022 175H1238 Variable Speed Drive
  • PASABAN MTC-3052 FAST I/O Module
  • Allen Bradley 1746-A7 SLC 500 Chassis
  • Mitsubishi NF1600-SEW MCCB
  • Schneider LTMR100EBD Motor Management Controller
  • Yokogawa AIP121-S3 Analog Input Module
  • Siemens 6ES7135-4LB02-0AB0 ET200S AO Module
  • Motor Power SKA DDR 148-240 Torque Motor
  • OMRON CS1H-CPU63-EV1 PLC CPU Unit
  • ABB UFC921A101 Main Control Board
  • ABB UFC921A Main Control Unit
  • ABB UFC911B108 Drive Main Control Unit
  • ABB UFC911B106 Drive Main Control Unit
  • ABB UFC911B101 Drive Main Control Unit
  • ABB UFC765AE102 Drive Control Interface Board
  • ABB UFC762AE101 I/O and Communication Extension Board
  • ABB UFC760BE41 I/O and Communication Extension Board
  • ABB UFC760BE145 I/O and Communication Extension Module
  • ABB UFC721BE101 Fieldbus Communication Adapter Module
  • ABB UFC721AE101 3BHB002916R0101 Network Interface
  • ABB UFC718AE101 HIEE300936R0101 Communication Module
  • ABB UDC920BE01 3BHE034863R0001 Communication Module
  • GE IS420UCSCH1A-F-VO.1-A Controller Module
  • GE UCSC H1 IS420UCSCH1A Controller Station Card
  • ABB UCD240A101 3BHE022287R0101 Process Controller
  • ABB UCD224A103 Process I/O Module
  • ABB UCD224A102 Analog Input Module
  • WOODWARD 9907-838 Load Sharing Module
  • B&R X20CP1485-1 Industrial PC CPU Module
  • ELAU MC-4/11/22/400 4-Axis Servo Drive
  • ELAU C600/10/1/1/1/00 Configurable Safety Relay
  • BENTLY 60R/SIM01 Proximitor Power Supply
  • BENTLY 60R/PPM01 Protection Processing Module
  • BENTLY 60R/PNL01 Operator Control Panel
  • BENTLY 60R/PIM01 Panel Interface Module
  • BENTLY 60R/INP07 Isolated DC Input Module
  • BENTLY 60R/INP01 4-Channel Analog Input Module
  • BENTLY 60R/CMM01 Communication Multiplexer Module
  • BENTLY 60R/CHA02 System Chassis Rack Enclosure
  • BENTLY 60R/CGW01 Condition Monitoring Gateway
  • Pacific Scientific P70360-SDN Servo Motor
  • HONEYWELL 05701-A-0284 Signal Conditioner
  • YOKOGAWA NFCP501-W05 Pressure Transmitter
  • ABB CI541V1 3BSE0146666R1 Control Interface
  • ABB DSTC176 57310001-KT Terminal Base Unit
  • ABB DSDP170K02 3BSE019925R1 Analog Input Module
  • ABB DSBC173 57310001-KH Terminal Base Unit
  • ABB DSAI130K01 5730-030-UC Thermocouple Input
  • ABB DSRF182 57310255-AL Relay Output Module
  • ABB SC520 3BSE003816R1 Compact PLC
  • ABB DSDP140A 57160001-ACT Analog Input Module
  • ABB DSAI130 57120001-P Analog Input Module
  • ABB SCYC55830 3AFE58063282 MCCB
  • Fireye 95DSS3-1CEX UV Flame Scanner
  • ABB DSDP170 57160001-ADF Analog Input Module
  • ABB CI532 3BSC140120R1 Communication Interface
  • ABB DSAO120A 3BSE018293R1 Analog Output Module
  • ABB CI869K01 3BSE049110R1 Ethernet Interface
  • ABB CI522A 3BSE018460R1 PROFIBUS DP Master
  • GUTOR OP6257 Rectifier Control Unit
  • Meggitt C327845-11 Gas Shutoff Valve
  • ABB SACO64D4 4-Pole Digital Annunciator Unit
  • ABB CI522AK04 3BSE018451R1 PROFIBUS DP Module
  • ABB DSAI130DK01 3BSE020828R1 Temperature Input Module
  • ABB CI546 3BSE012610R1 PROFIBUS DP Master Module
  • ABB SC510 3BSE003832R1 Compact PLC Controller
  • ABB CI540 3BSE001077R1 PROFIBUS DP Slave Module