Basler UFOV 250A/260A underfrequency overvoltage module: full analysis of technical principles and engineering applications

Product positioning and model differentiation

The UFOV (Underfrequency Overvoltage) module is an independent protection and auxiliary regulation device installed on the input side of generator voltage regulators (such as Basler SR4A, SR4F, SR8A, SR8F, SR32A, etc.), providing two core functions:

Underfrequency voltage suppression: When the generator frequency is 4-7 Hz lower than the rated value, the output voltage reference value of the regulator is automatically reduced to proportionally decrease the generator terminal voltage, avoiding magnetic flux saturation and equipment overheating.

Overvoltage trip protection: When the generator terminal voltage exceeds the preset threshold (usually 125%~150% of the rated value), the circuit breaker connected in series with the regulator power input circuit will trip, completely cutting off the excitation power supply and achieving hardware level protection.

This series includes two models:

Model applicable frequency applicable regulator (partially listed)

UFOV 250A 50 Hz SR4A, SR4F, SR8A, SR8F, SR32A, SR32H, SR63H, SR125H, SR250H

UFOV 260A 60 Hz Same Left (Different Frequency)

Attention: The underfrequency action point of earlier versions (part number 9 0400 00 100/104) was below 10 Hz, while the current A-series version has been optimized to a threshold window of 4-7 Hz. When installing replacement, be sure to check the part number and wiring differences.


Key technical specifications and selection points

1. Input voltage adaptability

The module is equipped with a multi tap transformer that supports single-phase inputs of 120, 208, 240, 416, 480, and 600 Vac, with a factory default of 120 Vac. If the on-site voltage does not match, it can be connected to the corresponding tap through internal wiring. If the generator voltage exceeds 600 Vac, an external voltage transformer (PT) is required for voltage reduction.

2. Underfrequency action characteristics

When the frequency drops below the rated value by 4-7 Hz, the underfrequency circuit inside the module begins to intervene. Its output characteristics are shown in Figure 1-1 (Figure 1-1 in the manual), presenting a voltage frequency curve with a certain dispersion band. For example, when a 60Hz generator drops to 50Hz, the terminal voltage will decrease to 82% to 95% of the rated value (depending on temperature and component tolerances). The voltage drop rate is slightly faster than the frequency drop rate, that is, at 50% frequency, the voltage will be lower than 50%.

3. Overvoltage setting range

The overvoltage trip threshold can be continuously adjusted between 125% and 150% of the rated voltage. The factory preset value is 130%, and users can adjust it appropriately according to the transient characteristics of the system. The matching circuit breaker should be of single pole (part number 05390) or double pole (part number 05391) type, with a rated contact capacity of 50A @ 480Vac.

4. Environmental and mechanical specifications

Working temperature: -55 ° C to+70 ° C, suitable for extremely cold and high temperature environments.

Anti vibration and anti impact: Meet the requirements of 5-500Hz sweep frequency vibration and 15G impact.

The weight is about 4.5kg, and it adopts a "back panel installation" design. The external dimensions are shown in Figure 3-1 of the manual.


Working principle and engineering significance of underfrequency circuit

1. Basic principles

The underfrequency circuit continuously monitors the frequency of the input voltage. When the frequency drops to the action threshold (rated value minus 4-7 Hz), the circuit outputs a DC control signal proportional to the frequency deviation, which is applied to the voltage set point input terminal of the regulator (usually the "A" or "F0" terminal of the SR series), causing the regulator to reduce the excitation output.

2. Collaboration with Field Flashing Relay

During the initial excitation process of the generator, the excitation relay will cover the control function of the underfrequency circuit to ensure that the voltage can be established. Once the excitation is completed and the frequency is normal, the underfrequency circuit enters standby mode. If the subsequent frequency falls into the underfrequency zone, the circuit will immediately take over control. Special attention: If the generator needs to run at low speed for a long time (such as turning or debugging), it is necessary to ensure that the excitation relay is excited, otherwise the underfrequency circuit may not operate correctly.

3. Engineering considerations for curve dispersion

The shaded area in Figure 1-1 represents the inherent dispersion of the voltage frequency relationship, which is due to temperature drift and component tolerance. Engineers should reserve sufficient margin when setting protection coordination to avoid misoperation or insufficient protection caused by dispersion.

Overvoltage protection circuit and circuit breaker selection

1. Protecting Logic

The overvoltage circuit continuously monitors the generator terminal voltage (sharing the same voltage detection input with the underfrequency circuit). When the voltage exceeds the preset threshold and lasts for a certain period of time (actually instantaneous action, but needs to cross the transient peak), the internal thyristor trigger circuit will excite the circuit breaker coil, causing the circuit breaker to trip and cut off the input power supply of the regulator (i.e. PMG or auxiliary winding power supply).

  • Basler DECS-100-B15 Digital AVR
  • Basler 9284900103 PS DECS-400N
  • Basler D4N3H1U Intertie Protection
  • Basler DECS-100-B15 A15 AVR
  • Basler KR4F Voltage Regulator
  • Basler BE26434 T14 Transformer
  • Basler SR8A-2B15B3A Regulator
  • Westinghouse 774B472A12 AR Relay
  • Basler DECS-100-B15 AVR
  • Basler XR2002F Regulator 110V
  • Basler SR125-E Static Regulator
  • Basler SSR 125-12 Regulator
  • Basler MOC2599 Motor Pot
  • Basler BE1-DFPR Feeder Relay
  • Basler CBS 305 Current Boost
  • Basler BE1-25 AutoSync
  • Basler MVC 300 Voltage Control
  • Basler BE3-25A AutoSync
  • Basler KR7FF Static Regulator
  • Basler 90-49000-100 Regulator
  • Basler 880 kVA Dry Type Transformer Specs
  • Basler Electric BE1-25 Sync-Check Relay Specs
  • Basler SSR 125-12 Voltage Regulator Specs
  • Basler Electric BE1-851 Overcurrent Relay Review
  • Basler Electric 149D930G02 Control Sub-Assembly
  • Basler Electric BE1-81O/UT Frequency Relay Specs
  • Basler Electric BE1-51/27C Overcurrent Relay
  • Basler Electric 149D956G02 Industrial Component
  • Basler Electric BE1-51A Overcurrent Relay Specs
  • Basler Electric BE1-40Q Loss of Excitation Relay
  • Basler DECS-200 Excitation Control System
  • Basler DECS-200 Voltage Regulator 56-277V AC / 125V DC
  • Basler BE1-87T Transformer Differential Relay
  • Basler RDP-110-S1 Protection Relay
  • Basler BE1-700V Digital Protective Relay
  • Basler BE1-951 Overcurrent Protection System
  • Basler DECS-300 Digital Excitation Control
  • Basler DECS-200 Digital Excitation Control
  • Basler DECS-200-1C Excitation Control System
  • Basler DECS-200-1L Digital Excitation Control
  • Basler Electric BE1-GPS Generator Protection System
  • Basler Electric DECS-200-1C Digital Excitation Controller
  • Basler Electric DECS125-15 Excitation Control with Power Module
  • Basler Electric BE1-87G Differential Relay
  • Basler Electric BE1-11 Protection System I5A3M2P2N0EA00
  • Basler Electric DECS-200-1C Excitation Control System
  • Basler Electric BE1-11g Generator Protection Relay
  • Basler Electric DECS 125-15-B2C1 V2.0.9 Excitation Control
  • Basler Electric BE1-81O/UT3ED1JA7N2F Frequency Relay
  • Basler Electric BE1-81O/UT3EE1YB7N1F Frequency Relay
  • Basler Electric DECS-200-1L Digital Excitation Control System
  • Basler DECS125-15-B2C1 Excitation Control
  • Basler 9507900205 SSR Retrofit Voltage Regulator
  • Basler BE2000E Digital Voltage Regulator
  • Basler BE1-GPS Generator Protection System
  • Basler DECS-250-CN1CN1N Digital Excitation Control
  • Basler DGC-2020 Genset Controller
  • Basler BE1-81O UT3ED1LA7N0F Frequency Relay (Variant)
  • Basler BE1-81O UT3EE1YA9S0F Frequency Relay (Variant)
  • Basler BE1-81O Over/Under Frequency Relay
  • Basler DECS125-15 Digital Excitation Control
  • Basler Electric BE1-951 Overcurrent Protection System
  • Basler Electric BE1-700V Digital Protective Relay
  • Basler Electric APR63-5 Automatic Voltage Regulator
  • Basler Electric BE1-851 Overcurrent Protection System
  • Basler Electric DECS-250-LN1SN1N Excitation Control
  • Basler Electric BE1-87T Transformer Differential Relay
  • Basler Electric DECS-200-1L Excitation Control System
  • Basler Electric 9310300100 DECS-300 Excitation Control
  • Basler Electric SSE-N 125-4.5KW Shunt Exciter Regulator
  • Basler Electric DGC-2020HD-5NS1DNSBA Genset Controller
  • Basler Electric BE1-81-O/UT3EE1JB7N1F Frequency Relay
  • Basler Electric BE1-81T1EE1WA0N1F Frequency Relay
  • Basler Electric BE1-25M1EA6PN5R1F Sync-Check Relay
  • Basler Electric BE1-GPS Generator Protection System
  • Basler Electric DECS-250-LN1SN1N Excitation Control Rev V
  • Basler Electric DECS-250-CN2CN1N Excitation Control
  • Basler Electric BE1-50/51B-207 Overcurrent Relay
  • Basler Electric DECS-300-C0N0 Excitation Control System
  • Basler Electric DECS-200 Digital Excitation Control System
  • Basler Electric DECS-250-LN1CN1N Excitation Unit
  • Basler Electric DECS-250 LN2SA1D Excitation Unit Specs
  • Basler Electric BE1-87T Transformer Relay Review
  • Basler Electric BE1-11 Protection System
  • Basler Electric BE1-GPS100-E4N1H1N Protection System
  • Allen-Bradley 442G-MABH-R Safety Module
  • Beckhoff CX1030-0111 PLC Assembly Profile
  • FANUC IC693CPU364 PLC Module
  • Orange Denmark Type 200816 220 PLC Specs
  • OMRON C200H-SNT31 Sysmac PLC Module
  • Allen Bradley 20AB022A3AYNANC0 PowerFlex 70
  • OMRON C200HW-PCU01 Position Control Unit
  • ABB AO845A-eA Analog Output Module
  • OMRON CJ1M-CPU22 CPU Unit
  • Allen Bradley 100-E265ED11 Contactor
  • Honeywell 51304511-100 Interface Module
  • SOLEXY BXF3S0101N0018 Gateway Module
  • OMRON CJ2H-CPU65 CPU Unit
  • Automation Direct GS2-45P0 AC Drive
  • M68-2000 2-Axis Motion CNC Controller
  • OMRON CJ1M-CPU11 V3.0 PLC CPU Unit
  • OMRON CJ1W-NC413 4-Axis Positioning Controller
  • OMRON 3G2A3-PRO16 Programming Console HMI
  • Siemens 3VT8440-2AA04-2GA2 Molded Case Circuit Breaker
  • Siemens 3RT5045 Contactor Series
  • OMRON C200HS-CPU01-E SYSMAC PLC Controller
  • OMRON C500-NC103-E Positioning Control Unit
  • OMRON CJ1W-TC001 Temperature Control Unit
  • OMRON NJ301-1100 NJ-PA3001 PLC System EtherCAT
  • Pilz 773100 M1P Safety Relay Base Unit
  • Siemens SINUMERIK 840D SL NCU 720.3B with PLC 317-3 PN/DP
  • Siemens 6AV6618-7GD01-3AB0 HMI Panel
  • OMRON F150-C15E-3 Vision Mate Controller PLC Overview
  • Mitsubishi MELSEC A Series PLC System A63P A3ACPU A616AD A68RD3
  • M68-2000 2 Axis Motion Controller SCE SERVO CNC
  • OMRON FZ-S2M PLC Camera Vision System
  • VISOLUX SLVA-4K PLC Module from Elektronik GmbH
  • OMRON CJ1M-CPU23 V2.0 PLC CPU Unit
  • ABB AI86-16CHF PCB Card 5761751-9 B Specifications
  • Allen-Bradley 100-D140ZJ22L Contactor Overview
  • Merlin Gerin PB80 PLC Rack
  • WEIR WE203 Power Supply PLC
  • OMRON NX-TS3102 Temperature Input Unit
  • Siemens 6ES7146-6FF00-0AB0 I/O Module
  • Fanuc A16B-3300-0057 Circuit Board
  • OMRON CJ1W-IDP01 Input Module
  • Siemens 6FX2007-1AD13 Handheld Unit
  • Gems EM54 PLC Module PCB