2-speed non commutation (for 2 separate windings)
Used for multi tap windings
Can achieve multi-level speed control
Typical model:
T0X-3-8451/EZ (3-pole multi speed switch)
T3X-4-8440/12 (4-pole multi speed switch)
5.6 Step switch
Function: Used for gradually switching circuits, such as heater grading control.
Features:
Multi position step control
Connect different numbers of contacts at each position
Suitable for temperature control, power regulation, etc
Typical model:
T0X-1-15401/11 (1-pole stepper switch)
T0X-2-15403/IVS (2-pole stepper switch)
5.7 Control switch
Function: Used to control various operations of the circuit, including on-off, switching, manual automatic switching, etc.
Type:
On-off switch: simple ON/OFF control
Conversion switch: I-0-II or I-II conversion
Manual/Automatic Switch: Switch between manual and automatic modes
Turn on switch: jog operation
Typical model:
T0X-1-15321/11 (Turn on switch)
T0X-2-8177/11 (control switch)
5.8 General control switch
Function: Multi functional control switch, can be configured with multiple contact combinations.
Features:
Self locking 3-digit switch
Connect 3 contacts at positions 0 and 1
Connect 3 contacts at positions 0 and 2
Connect 3 contacts at positions 1 and 2
Spring reset function is optional
Typical model:
T0X-3-15391/11 (3-digit universal control switch)
5.9 Instrument selection switch
Function: Used to select different measuring instruments or measuring points.
Features:
Multiple options, such as V1-V2-V3
Suitable for switching between voltmeters and ammeters
Ensure safe isolation of the measurement circuit
Typical model:
T0X-1-15113/E (instrument selection switch)
Chapter 6 Attachments and Extended Functions
6.1 N-pole module and auxiliary contact module
N-pole module (N-P1X/N-P3X)
Function: N-pole contact for early closure and delayed disconnection
Installation position: can be installed on the left or right side
Breaking capacity: the same as the main contact
Order number: N-P1XE (for P1X flat installation), N-P1XZ (for P1X rear installation)
Auxiliary contact module (H11-P1X/P3)
Contact configuration: 1 normally open+1 normally closed
Function: Delay breaking, delay closing, N/O contacts are usually used for load shedding
Installation position: can be installed on the left or right side
Order number: H11-P1X/P3E (for flush installation), H11-P1X/P3Z (for rear installation)
6.2 Installation Accessories
Central installation accessories (EZ-T0X)
Used for single hole installation with a diameter of 22.3mm
Equipped with a buckle system for quick installation
Suitable for T0X/T3X flush mounted switches
Installation accessories for distribution cabinet (IVS-TOX)
Including crimping shaft, used for installation and renovation of distribution cabinets
Use the basic switch front panel
Connectors (DE-TOX/DE-P3X)
Used to convert flat installation to rear installation
Suitable for T0X/T3X/P1X/P3X
6.3 Interlocking mechanism and extension rod
Interlocking mechanism (UV-TOX/UV-P3X)
Connected with PE and neutral wire
When installed flush, it is installed at the rear of the switch
Installed at the front of the switch during rear installation
Implement door interlocking function
Interlocking extension device (ZW-TOX/ZW-P3X)
Up to 4 units can be plugged in
Each 25mm, totaling 100mm
Used to extend interlocking distance
Extension rod (ZAV-TOX/ZAV-P3X)
Up to 4 units can be installed
Each 25mm, totaling 100mm
Suitable for rear mounted switches
6.4 Shield and Key
Shield (H3-TOX/H1-T5X/H2-T5X)
Used for flush mounted switches
H3-TOX: Up to 8 contacts, cable entry holes 2 × 20mm+2 × 15mm
H1-T5X: Basic Shield
H2-T5X: Expansion shield for 6-16 contacts
Lock buckle (HZ-T5X)
Each contact requires one
Suitable for input and/or output wiring
Key (VR-TOX)
Used for changing the engagement position of key extraction in the later stage
Suitable for all switch angles
6.5 Emblem and Front Panel
Standard Emblem (FS908)
Size: 88 × 88mm
88 × 88 framework suitable for P3X, T5X, T5XB
Order number: FS908GE-P3X
Blank engraved emblem
FS-ALU980-TOX: Aluminum, used for T0X
FS (*) - TOX: Plastic, used for T0X
BS84X24-P3X: Insertion Emblem
Card holder (ZF5X-TOX)
Black, detachable
Used for inserting signage
Insert signboard (BS45X14-TOX)
Size: 45 × 14mm
Engravable text
6.6 Insulated distribution box
IP65 insulated distribution box (CI-K1-TOX)
1-2 contact modules: CI-K1-TOX-2
3-4 contact modules: CI-K1-TOX-4
With diaphragm and cable port
1 contact module=2 contacts

Chapter 7 Dimensions and Installation Points
7.1 Flat Installation (.../E)
T0X/T3X flush installation
Door opening size: depends on the number of contact modules
Installation depth: increases with the number of contacts
Can be equipped with H3-TOX protective cover
T5X (B) flat installation
Door opening size: 88 × 88mm
Installation depth: depends on the number of contacts (c2 size)
Flat installation type main switch with SVB: adding padlock function
7.2 Rear Installation (.../Z)
feature
Installation hole with a diameter of 22.3
Can be extended with interlocking long poles, up to a maximum of 4 × 25=100mm
Can be extended with an extension rod, up to 4 × 25=100mm
Size Table (T0X)
Model, number of contacts, installation depth (c20), maximum depth (≤ 4 ZAV)
T0X-1 2 41 mm 86~102 mm