T0X-3 6 60 mm 105~121 mm
T0X-6 12 88 mm 134~150 mm
T0X-8 16 107 mm 153~169 mm
7.3 Surface Installation (.../11,.../12)
T0X surface installation
Base opening size: varies with model
Total depth: including handle and wiring
T3X surface installation (model c25 size)
T3X-1.../2:80 mm
T3X-3.../2:100 mm
T3X-5.../2:145 mm
7.4 Size of PX load isolation switch
P1X/P3X flat installation
Width: P1X 49mm, P3X 72mm
Depth: P1X 86mm, P3X 102mm
P5X flat installation
Front frame size: 112 × 112 mm
Installation depth: ≥ 130 mm
Wiring capacity: 50-70mm ² cable or copper strip
Chapter 8 Technical Data and Selection Table
8.1 Selection Table for Main/Maintenance Switches
Model Pole Power (kW) AC-23A 400V Rated Continuous Current Order Number (with padlock)
T0X-1-8200/11/SVB 1 6.5 20 A CPD05900
T3X-1-8200/12/SVB 1 13 32 A CPD06465
P1X-25/12/SVB 1 7.5 25 A CPD05650
P1X-32/12/SVB 1 13 32 A CPD05694
P3X-63/14/SVB 1 22 63 A CPD06886
8.2 Main switch with N pole
Model Description Order Number
P1X-25/12/SVB/N 25A main switch with N-pole CPD05652
P1X-32/12/SVB/N 32A main switch with N-pole CPD05696
P3X-63/14/SVB/N 63A main switch with N-pole CPD06888
8.3 Main switch with emergency stop function
Model Description Order Number
T0X-1-8200/11-RT T0X 1 pole, red handle emergency stop CPD05902
P1X-25/12-RT P1X 25A, Red handle emergency stop CPD05658
P1X-32/12-RT P1X 32A, Red handle emergency stop CPD05702
8.4 Conversion Switch Selection Table
Model, Number, Description, Order Number
T0X-1-8210/E 1 conversion switch I-0-II CPD05910
T3X-1-8210/12 1 Transfer Switch I-0-II CPD06472
T0X-2-8211/E 2 conversion switch I-0-II CPD06058
T3X-2-8211/12 2 Conversion Switch I-0-II CPD06486
T0X-3-8212/E 3 conversion switch I-0-II CPD06209
T3X-3-8212/12 3 Transfer Switch I-0-II CPD06525
8.5 Steering Switch Selection Table
Model, Number, Description, Order Number
T0X-2-8400/EZ 2 reversing switch -0- reverse CPD06101
T3X-2-8400/12 2 Reversing Switch Positive 0 Reverse CPD06495
T0X-3-8401/EZ 3 reversing switch positive 0 reverse CPD06268
T3X-3-8401/12 3 Reversing Switch Positive 0 Reverse CPD06548
8.6 Multi speed Switch Selection Table
Model, Number, Description, Order Number
T0X-3-8451/EZ 3 2-speed non reversing CPD06274
T3X-3-8451/12 3-speed non reversing CPD06552
T0X-4-8440/EZ 4 multi tap winding CPD06353
T3X-4-8440/12 4 multi tap winding CPD06596
Chapter 9 Application Precautions
9.1 Service life and load selection
There are significant differences in the service life of contacts based on the breaking current and usage category:
AC-21A (non inductive or slightly inductive load): longest service life
AC-23A (motor load): medium service life
AC-4 (inching, reverse braking): extreme load, shortest service life
To ensure a reasonable service life under AC-4 application, the static current of the motor should not exceed the rated operating current of the switch under AC-21A.
9.2 Installation environment requirements
Ambient temperature
Open installation: -25 ° C to+50 ° C
Closed installation: -25 ° C to+40 ° C (P5X: -25 ° C to+40 ° C)
Climate protection: Complies with IEC 60068-2-78 (Constant Damp Heat) and IEC 60068-2-30 (Alternating Damp Heat)
Installation location: Any
Mechanical impact resistance strength: 15g (half sine wave impact)
9.3 Safety isolation characteristics
Compliant with standard: IEC/EN 60947-3 (requirements for isolating switches)
Main switch characteristics: compliant with IEC/EN 60204
Definitely disconnect the contact: the operating element is rigidly fixed to the spindle
Safe insulation: compliant with EN 61140 and VDE 0106 Part 101
Switching angle between auxiliary contact and main circuit: 90 °