P5X-175:160 A gG/gL
Rated short-time withstand current (1 second): 1125 A rms
Wiring capability: 50-70 mm ² solid wire, or copper strip connection (6 × 9 × 0.8 mm)
3.3 Breaking ability
P5X-125
AC-21A load switch, 440V: 125 A
Motor power (AC-3 load):
230 V:22 kW
400 V:37 kW
690 V:30 kW
Motor power (AC-23A load):
230 V:30 kW
400 V:45 kW
690 V:37 kW
P5X-175
AC-21A load switch, 440V: 160 A
Motor power (AC-3 load):
230 V:30 kW
400 V:45 kW
690 V:37 kW
Motor power (AC-23A load):
230 V:30 kW
400 V:55 kW
690 V:37 kW
3.4 DC application parameters
P5X series (DC-23A load, L/R=15ms)
125A model:
24 V: 125 A (3 contact modules in series)
48 V: 125 A (3 contact modules in series)
60 V: 125 A (3 contact modules in series)
120 V: 40 A (3 contact modules in series)
Model 175A:
24 V: 160 A (3 contact modules in series)
48 V: 160 A (3 contact modules in series)
60 V: 160 A (3 contact modules in series)
120 V: 50 A (3 contact modules in series)

Chapter 4 System Composition and Selection Guide
4.1 Modular System
The TX cam switch and PX load isolation switch adopt modular design, consisting of the following basic components:
Joystick: Provides multiple colors and function options
Switch unit: core on-off component
Contact module: Each module contains 1 or 2 contacts
Install attachments: Implement different installation methods
Emblem: Identify the position and function of the switch
4.2 Installation method
According to application requirements, the following installation methods can be selected:
Characteristics of installation method code
Flat installation.../E front IP65, rear installation and wiring
Center installation.../EZ front IP65, single hole diameter 22.3 installation, card fixed
Rear installation.../Z front IP65, installed from the rear
Surface mount.../11,.../12 front IP65, connected from the front
Installation of distribution cabinet.../IVS installed on the distribution cabinet, depth 45mm
Control screen installation.../VS installed on the control screen
4.3 Flat installation type main switch
Special design for main switch, maintenance switch, and safety isolation:
Model code: ../EA/SVB (flat installation),.../V/SVB (rear installation)
Emblem: Standard FS908 with 0-position padlock function
Handle color:
Red/Yellow: with emergency stop function, compliant with IEC/EN 60204-1
Black/Black: No emergency stop function
Padlock function: Up to 3 padlocks can be added to 0 positions
4.4 Contact module configuration
The contact number of the switch is defined by the standard configuration table and can be selected as needed:
T0X: Up to 11 contact modules (22 contacts), with a single module depth of 9.5mm
T3X: Up to 11 contact modules (22 contacts), with a single module depth of 11.5mm
T5X (B): Up to 10 contact modules (20 contacts), with a single module depth of 16.5mm
P1X/P3X: up to 3 poles+N poles
4.5 Customization of non-standard switches
For applications where standard contact sequences cannot be met, Eaton provides customized non-standard switch services:
Initial customization: The "Cam Switch Customization Model Initial Order Customization Form" (F02 Form) needs to be filled out
Reorder: simply specify the contact number and country identifier (e.g. 4711D)
Customized models: T0X/T3X/T5XB/T5X all have corresponding customized models, and the order number is marked with "- SONG *"
Chapter 5 Detailed Explanation of Main Function Types
5.1 Main switch, maintenance switch/forced manual control switch
Function: As the main power switch of the device, it is used for safety isolation and emergency disconnection.
Features:
Compliant with IEC/EN 60204 and IEC/EN 60947-3 standards
Definitely disconnect the contact, the operating element is rigidly fixed to the spindle
Optional red/yellow handle with emergency stop function
0-position can be equipped with a padlock, which meets the safety requirements of Lock/Tag Out (LOTO)
Typical model:
T0X-1-8200/11/SVB (1-pole, with padlock)
P1X-25/12/SVB (25A, with padlock)
P3X-63/14/SVB (63A, with padlock)
5.2 on-off switch
Function: Used for circuit connection and disconnection, can serve as a main switch or control switch.
Features:
Multiple configurations including 2-pole, 3-pole, 4-pole, etc
Optional with 0 bits or direct on/off
Suitable for load types such as AC-21A and AC-23A
Typical model:
T0X-3-8342/11 (3-pole on-off switch)
T3X-3-8342/12 (3-pole on-off switch)
5.3 Conversion switch
Function: Implement power or load switching, such as switching between primary and backup power sources, star delta startup, etc.
Features:
Switch with 0-position (I-0-II)
Switch without 0 position (I-II)
Can be configured for manual automatic conversion
Typical model:
T0X-1-8210/E (1-pole toggle switch)
T3X-2-8211/12 (2-pole conversion switch)
T0X-3-8212/E (3-pole conversion switch)
5.4 Steering switch
Function: Used for forward and reverse control of electric motors.
Features:
Reversing switch with 0 position (positive 0 reverse)
Directly control the direction of the electric motor
Suitable for lifting, conveying and other equipment
Typical model:
T0X-2-8400/EZ (2-pole reversing switch)
T3X-3-8401/12 (3-pole reversing switch)
5.5 Multi speed switch
Function: Used for speed switching of multi speed motors.
Features: