Introduction: Core components of industrial electrical control
In industrial electrical control systems, cam switches and load isolation switches serve as manually operated control and isolation components, responsible for key functions such as circuit on/off, equipment switching, and safety isolation. As a global leader in power management, Eaton's TX series cam switches and PX series load isolation switches are widely used in mechanical manufacturing, building electrical, industrial automation, and other fields due to their excellent performance, reliable quality, and flexible combination methods.
This article is based on Eaton's official Chinese product catalog, providing a comprehensive analysis of the technical characteristics, model composition, installation methods, accessory selection, and application points of TX cam switches and PX load isolation switches. It provides a professional and detailed technical reference for electrical engineers, system integrators, and equipment maintenance personnel.
Chapter 1 Overview of Product Series
1.1 Product positioning and certification
The TX cam switch and PX load isolation switch are electrical control products designed by Eaton specifically for industrial, handicraft, and building service management. Both series share the following common characteristics:
Front panel protection level: IP65, suitable for harsh environments such as high dust and humidity
International certifications: CCC (China Compulsory Certification), CE (European Union Safety Certification)
Modular design: Flexible combination of contact modules and installation accessories according to requirements
Environmentally friendly materials: free of PCB, CFC, asbestos, and silicon, and the contacts do not contain cadmium
1.2 Product Series Comparison
Series Type Power Range Current Range Main Applications
TX cam switch to 55kW to 100A control circuit, instrument selection, stepper control
PX load isolation switch to 55kW to 175A main switch, maintenance switch, safety isolation
1.3 Basic switch types
Two series offer a total of ten basic switch types, covering the vast majority of application scenarios:
Main switch/maintenance switch/forced manual control switch
on-off switch
changeover switch
turn signal switch
Multi speed switch
Step switch
Control switch (on/off/switch/manual automatic/on)
General control switch
Instrument selection switch
Safety switch with interlock function
Chapter 2 Detailed Analysis of TX Cam Switch
2.1 Overview of Technical Specifications
The TX series cam switch is divided into multiple sub series based on current capacity:
Model Rated continuous current (Iu) Maximum number of contact modules Single contact depth Mechanical life (10000 cycles)
T0X 20 A up to 11 pieces 9.5 mm 40
T3X 32 A up to 11 11.5 mm 40
T5XB 63 A up to 10 16.5 mm 40
T5X 100 A up to 10 16.5 mm 40
2.2 Electrical Performance Parameters
T0X cam switch
Rated connection capacity (cos φ=0.35): 130 A
Rated breaking capacity (motor load):
230 V:100 A
400 V:110 A
500 V:80 A
690 V:60 A
Motor power (AC-23A load):
230 V:4 kW
400/415 V:6.5 kW
500 V:6.5 kW
690 V:4 kW
T3X cam switch
Rated connection capacity (cos φ=0.35): 320 A
Rated breaking capacity (motor load):
230 V:400 A
400 V:500 A
500 V:450 A
690 V:250 A
Motor power (AC-23A load):
230 V:7.5 kW
400/415 V:13 kW
500 V:13 kW
690 V:11 kW
T5XB/T5X cam switch
Rated connection capacity (cos φ=0.35):
T5XB:800 A
T5X:950 A
Motor power (AC-23A load, 400/415 V):
T5XB:22 kW
T5X:30 kW
2.3 DC application parameters
For DC-23A load (L/R=15ms):
T0X cam switch
24 V: 6 A (1 contact module)
48 V: 4 A (2 contact modules in series)
60 V: 3 A (3 contact modules in series)
120 V: 2 A (3 contact modules in series)
240 V: 1 A (5 contact modules in series)
T3X cam switch
24 V: 16 A (1 contact module)
48 V: 10A (2 contact modules in series)
60 V: 8 A (3 contact modules in series)
120 V: 4 A (4 contact modules in series)
240 V: 2 A (6 contact modules in series)
Chapter 3 Detailed Analysis of PX Load Isolation Switch
3.1 Overview of Technical Specifications
The PX series load isolation switch is divided into multiple sub series based on current capacity:
Model Rated continuous current (Iu) Maximum power (AC-23A, 400V) Mechanical life (10000 cycles)
P1X-25 25 A 7.5 kW 10
P1X-32 32 A 13 kW 10
P3X-63 63 A 22 kW 3
P3X-100 100 A 30 kW 3
P5X-125 125 A 45 kW 3
P5X-175 175 A 55 kW 3
3.2 Electrical Performance Parameters
P1X series (25A/32A)
Rated working voltage: 690 VAC
Rated impulse withstand voltage: 6000 VAC
Overvoltage category/pollution level: III/3
Short circuit rating (fuse):
P1X-25:25 A gG/gL
P1X-32:50 A gG/gL
Rated short-time withstand current (1 second): 640 A rms
Wiring capacity: 1 × (1.5-6) mm ² or 2 × (1.5-6) mm ²
Tightening torque of wiring screw: 1.6 Nm
P3X series (63A/100A)
Rated working voltage: 690 VAC
Rated impulse withstand voltage: 6000 VAC
Short circuit rating (fuse):
P3X-63:80 A gG/gL
P3X-100:100 A gG/gL
Rated short-time withstand current (1 second): 1300 A rms
Wiring capacity: 2 × (1.5-6) mm ²
P5X series (125A/175A)
Rated working voltage: 690 VAC
Rated impulse withstand voltage: 8000 VAC
Short circuit rating (fuse):
P5X-125:125 A gG/gL