Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Pro face GP370 Complete Guide

F: | Au:FAN | DA:2026-04-22 | 506 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Pro face GP370 series human-machine interface: a complete technical manual from installation to troubleshooting

In industrial automation sites, the Human Machine Interface (HMI) serves as a bridge for communication between operators and equipment. The Pro face GP370 series (including monochrome LCD model GP370-LG and STN color LCD model GP370-SC) is widely used in small and medium-sized control systems due to its compact design, high protection level, and strong communication compatibility. This article is based on the original factory technical manual and provides a full process operation guide for automation engineers and maintenance technicians, covering hardware installation, system initialization, communication configuration, daily operation, and fault diagnosis.


Chapter 1: Product Overview and Selection Points

The GP370 series offers two display types: GP370-LG (monochrome, black and white display) and GP370-SC (STN color, 8-color display). Both have the same external dimensions (170W × 138H × 57D mm), weigh less than 900g, and use a resolution of 320 × 240 pixels and an effective display area of 115 × 86 mm.

1.1 Core Performance Parameters

Display and Backlight: Monochrome models support white/black and reverse display; The color model supports eight colors including white, red, blue, green, yellow, magenta, cyan, and black, as well as mixed colors with flat patterns. The backlight is a cold cathode fluorescent lamp (CFL) with a lifespan of approximately 20000 hours at room temperature.

Touch panel: 16 × 12 keys/screen, supports single or two-point touch, with touch buzzer feedback (can be set to turn on/off).

Memory: Built in FLASH EPROM 1 Mbyte, can store up to 320 images when the standard screen size is about 3.2 KB.

Clock accuracy: The monthly error at room temperature is ± 40 seconds, but it may increase to+65 to -350 seconds per month with temperature rise and aging.

External interface:

Serial interface: RS-232C/RS-422, data length 7/8 bits, stop bit 1/2 bits, parity check none/odd/even, baud rate 2400-38400 bps.

Tool connector: TTL level RS-232C, used for downloading screen data, connecting barcode scanners or memory loaders.

Expansion interface: Reserved for future expansion.

1.2 Environment and Protection

Working temperature: 0~50 ℃; Storage temperature: -20~60 ℃.

Humidity: 20-85% RH (no condensation).

Protection level: The front panel is equivalent to JEM1030 IP65f and NEMA # 250 TYPE4X/12, which means it is completely dust-proof, direct water spray proof, and oil proof ("f" represents oil proof). However, it should be noted that long-term exposure to volatile oils or low viscosity cutting oils may still cause damage; The rubber gasket needs to be replaced regularly after aging to maintain its protective performance.

Anti vibration: 10-25 Hz, 30 minutes in X/Y/Z directions, acceleration 2G.

Anti interference: noise voltage of 1000 Vp-p, pulse width of 1 μ s, rise/fall time of 1 ns.

Grounding: Grounding resistance below 100 Ω.

1.3 Optional Accessories

Screen editing software: GP-PRO/PB III (DOS version) or GP-PRO/PB III for Windows 95 (CD-ROM or floppy disk), including download cable.

Communication cables: RS-232C cable (GP410-IS00-O), RS-422 cable (GP230-IS11-O), multi link cable (GP230-IS12-O), Siemens Simatic S5 programming port cable (GP000-IS11-O), Mitsubishi A-series programming port cable (GP430-IP10-O), Mitsubishi FX series programming port cable (GP430-IP11-O), Mitsubishi A-series dual port adapter (GP030-MD11-O).

Maintenance components: Backlight tube (GP370-BL00-MS, suitable for LG and SC models), mounting bracket (GP070-AT00-MS), rubber gasket (GP370-WP00-MS), screen protector film (GP370-COVER-20P, 20 sheets/set).

Tool connector attachment: Memory loader (GP070-MU01-O, used for high-speed copying of system programs and screen data, but cannot be used for system versions 1.20 and above).


Chapter 2: Hardware Installation and Wiring - The Foundation for Ensuring Reliable Operation

2.1 Mechanical installation requirements

GP370 is designed for panel embedded installation. The opening size should refer to the installation dimension diagram (Section 2.5) in the manual. Key requirements:

Panel thickness: 1.6 mm~5.0 mm, the surface should be smooth and free of burrs.

Rubber gasket: Before installation, it is necessary to confirm that the gasket is correctly attached to the back of the GP.

Installation bracket: Use the 4 metal brackets provided, hook them into the slots on both sides of the GP from the back of the panel, and tighten them with a screwdriver to a torque of 0.5-0.6 N · m.

Heat dissipation distance: To ensure natural convection cooling, GP should maintain a distance of at least 100 mm from other structural components. If installed horizontally or laterally, forced air cooling (such as a fan) is required. When installing sideways, the power terminal must face upwards.

Panel inclination: During natural cooling installation, the panel inclination should not exceed 30 °.

Avoid heat sources: Keep away from equipment that is prone to arcing, such as electromagnetic circuits and circuit breakers without fuses.

2.2 Power Wiring

Input voltage: DC 20.4~27.6 V (rated 24 VDC), power consumption less than 20 W (typical 10 W).

Terminal: The power terminal block is located on the back of the GP and uses a circular terminal (JST V2-MS3 is recommended) with a maximum cross-sectional area of 2 mm ² for the wire.

Grounding: The FG terminal must be grounded, and dedicated grounding (grounding resistance<100 Ω) should be preferred; If dedicated use is not possible, public grounding can be used. The cross-sectional area of the grounding wire should be greater than 2 mm ² and as short as possible. Attention: If the equipment works abnormally after grounding, try disconnecting the FG terminal (floating).

Wiring steps: Power off → Remove terminal cover → Loosen three screws → Insert ring terminal → Tighten screws (torque 0.5~0.6 N · m) → Replace cover.

2.3 Signal line isolation

The input/output signal line must be routed separately from the power control cable. If unavoidable, shielded cables should be used and the shielding layer should be connected to the ground of the GP rack.

2.4 Precautions for using tool connectors

Before plugging or unplugging the download cable or barcode reader, be sure to turn off the GP power.

If the barcode reader uses an independent power supply, the barcode reader power should be turned on first, and then the GP power should be turned on; When shutting down, turn off GP first, and then turn off the barcode reader.

Chapter 3: Offline Mode and System Initialization - Core Operations for First Power On

GP370 has no screen data when it leaves the factory, and for the first use, system files and screen data must be transferred through screen editing software. Off line mode is the entry point for initialization settings, self diagnosis, and image transmission.

3.1 Methods for entering offline mode

Method 1 (enter when powered on): Within 10 seconds after turning on the power, touch the top left corner of the screen.

Method 2 (Force Reset): In either running or offline mode, simultaneously press and hold the bottom right, top right, and bottom left corners of the screen to enter the Force Reset screen, and then press the "OFFLINE" button.

If a password has been set in the system settings (range 0~9999, default 0 is no password), the password needs to be entered before entering offline mode.

3.2 Main menu functions

The offline mode main menu contains four options:

Initialize: Set various parameters required for GP operation (communication, PLC, system environment, etc.).

Transfer Screen Data: Transfer screen data between PC and other devices.

SELF-DIagnoSIS: Detect GP system and interface faults.

RUN: Start normal operation and communicate with PLC.

3.3 Initialization Menu Explanation

The initialization menu is divided into 1:1 connection (one GP connected to one PLC) and n:1 multi link connection (multiple GPs sharing one PLC). The following are the key submenus:

3.3.1 System Environment Setup

Standby mode time (0-255 minutes): Screen saver function, automatically turns off display after no operation exceeds the set time. 0 indicates constant brightness.

Start time (0-255 seconds): The delay in entering the running mode after GP is powered on, used to wait for the PLC to start first.

Touch buzzer sound: on/off.

Buzzer terminal output: whether the buzzer signal is output from the AUX I/F (external buzzer).

Password setting: Prevent unauthorized access to offline mode.

Screen number data type: Select BIN (screen numbers 1~8999) or BCD (screen numbers 1~1999).

3.3.2 System Area Setup

Used to allocate a data area in PLC for GP to read and write status information (such as current screen number, error status, clock data, switching screen number, display switch, etc.). The size of the system area is automatically calculated based on the selected items. The starting address of the system area is specified by the PLC side (such as D00200), and each project is assigned an address according to a fixed offset.

3.3.3 Global Window Setup

GP can display both a global window (applicable to all screens) and two local windows simultaneously. You can set whether to use global windows, window registration numbers, and addressing methods for location (direct/indirect).

3.3.4 CHARACTER STRING DATA SETUP

The byte order of storage strings varies among different PLCs. Set according to PLC model:

Storage order of data devices (starting data storage/ending data storage)

Byte order within words (LH/HL)

Double character order (LH/HL)

For example, Omron PLCs typically choose mode 4 or 5, while Mitsubishi PLCs choose mode 1 or 2. Setting errors can result in garbled characters being displayed.

3.4 Communication parameter settings (SET UP I/O)

3.4.1 SIO Settings

Communication speed: 2400-38400 bps, must be consistent with PLC.

Data length/stop bit: 7 or 8 bits of data, 1 or 2 bits of stop bit.

Parity check: none, odd, even.

Flow control: X-CNTRL or ER-CNTRL.

Communication format: RS-232C, RS-422 4-wire, RS-422 2-wire. When using Memory Link, choose 4 wires.

3.4.2 I/O Settings

Touch operation mode: single point or two-point input.

Force reset: enable/disable. After activation, you can enter the forced reset screen by touching three points simultaneously.

Contrast adjustment: When enabled, the adjustment mode (monochrome model) can be entered through the touch screen's top right and top left corners. Color models have no contrast adjustment.

Brightness adjustment: When enabled, the adjustment mode can be entered through the bottom right and bottom left corners (color models only).

LCD Reverse (LG monochrome only): Set NORMAL or REVERSE to reverse black and white display.

3.4.3 Communication timeout and retry

Receive timeout (1-255 seconds): The maximum time GP waits for PLC response. Default 10 seconds. If it exceeds 30 seconds and the PC transmits the screen, an error may occur.

Retry count (0~255): The number of times GP resends data in case of communication error, default is 2 times.

3.5 PLC SETUP

3.5.1 1:1 Connection

Starting device/address in the system area: such as D00200.

Unit number: Consistent with PLC settings.

System area read size: Used for reading trend charts and other blocks, set to 0 if not in use to speed up communication.

3.5.2 n: 1 Multi link Connection

The starting address of the system area is set to 1:1.

Station number setting: Each GP must be assigned a unique station number (0-15).

Network information address: Assign 2 words to the connection and verification sections. The connection section records which station numbers' GPs have been registered; Verify the GP in actual communication. If both are consistent, communication is normal.

Custom settings: Communication priority can be selected - display priority (fast screen refresh, slightly slower touch response) or operation priority (fast touch response, slightly slower screen refresh). You can also set the touch exclusive function and exclusive time (0-2550 seconds).

3.6 Initialization Memory

This operation erases all screen data (but does not erase system settings, SIO protocol, and clock). Before execution, a password must be entered (either the universal password 1101 or the user's own password). Cannot be cancelled midway.

3.7 Time Setting (SET UP TIME)

Set the date and time of the internal clock. Note: The displayed time is only accurate to minutes, and the clock accuracy is affected by temperature.

3.8 Screen Settings (SET UP SCREEN)

Initial screen number: The screen number displayed after power on.

Alarm message character size: Set the alarm display font.

Online error display: Whether to display error messages in running mode.

3.9 Font Setting

Choose the character set used for running mode: ASCII, Korean, Traditional Chinese, Simplified Chinese, Japanese. If you choose Japanese, you can set the quality of Chinese characters to "high" (32 dots displayed when enlarged by 2 x 2) or "standard" (16 dots enlarged).


Chapter 4: Image Data Transmission - The Bridge from PC to GP

4.1 Hardware Connection

Use the download cable provided with the screen editing software (Dsub 25 pin male to PC serial port). Connect the cable to the tool connector on the back of the GP, and connect the other end to the RS-232C serial port of the PC (if the PC does not have a serial port, a USB to serial port adapter is required). Note: If using a serial mouse, please use a different serial port.

4.2 Transmission steps

Ensure that the GP is powered on (newly purchased GP must be powered on first).

Select 'TRANSFER SCREEN DATA' in GP offline mode.

Select "Send to GP" or "Receive from GP" in the PC software.

Starting transmission, the GP screen displays "Transferring, Please Wait".

After the transmission is completed, press the ESC key to return to the running mode.

If the initial screen number has been set during initialization, the screen will be displayed; Otherwise, return to the main menu.


Chapter 5: Operation Mode and Daily Operations

5.1 Enter operating mode

Automatic operation upon power on: After a delay in startup time, the initial screen is displayed and communication with the PLC begins.

Run from offline mode: Press "RUN" on the main menu.

5.2 Entering offline mode during operation

In operating mode, within 10 seconds, touch the top left corner of the screen (which can still be triggered if a switch is placed) to switch back to offline mode.

5.3 Forced Reset During Operation

At any time (including during operation), holding down the bottom right corner, top right corner, and bottom left corner at the same time can enter the forced reset screen, perform a reset, or switch to offline mode.

Chapter 6: Fault Diagnosis and Detailed Explanation of Error Codes

GP370 has a self diagnostic function (SELF-DIagnoSIS) that can detect display patterns, touch panels, memory checksums, frame buffers, tool connectors, and serial interfaces. The following are common running errors and solutions.

6.1 Error Message List and Handling

Solution to the meaning of error messages

SYSTEM ERROR (xx: xx) GP basic operation failure or damaged screen file records error codes, contact the dealer; If it automatically switches to offline mode during operation, it is necessary to perform memory initialization and retransmit image data.

ILLEGAL EXPRESS IN SCREEN DATA Address Overlap (such as system area and label address overlap) Check the address allocation in screen editing to ensure there is no overlap. For example, if the starting address of the system area is 100, and the starting address of a 32-bit tag is 99, it will occupy both 99 and 100, resulting in a conflict.

UNSUPPORTED TAG IN SCREEN DATA The current GP version does not support certain label modification screen editing, use the label types supported by GP.

PLC NOT CONNECTED (02: FF) communication with PLC interrupted for more than 60 seconds. Check if the PLC power is turned on; Are the communication parameters in GP initialization correct; Is the power on sequence PLC first and then GP; is the communication cable connected reliably.

PLC NOT Replying (02: FE) response timeout is the same as the above check, and ensure that the PLC side program responds normally.

Received data error (02: FD), which may be caused by noise or communication line plugging to eliminate noise sources; Restart communication; Check the wiring.

GP STATION NO. DUPLIcation (02: F9) n: In the 1:1 connection, duplicate station numbers are assigned to each GP with a unique station number (0~15).

Network Address Error (02: F8) n: 1 Check for inconsistent SIO address settings in all GP connections (usually RS-422 4-wire).

The PLC COM. ERROR tag address exceeds the range of the PLC device. After checking the error code, refer to the PLC manual. For example: FC (data format error), FB (address out of range), FA (address range error), 53 (too many labels), 51 (address does not exist). For the Allen Bradley PLC-5/SLC500, the error code displayed by GP needs to be subtracted by D0h before checking the manual.

Screen Memory Data IS CORDUPT Screen Data Checksum Mismatch Delete damaged screen files, remake or restore backups.

CLOCK SETUP ERROR: If the internal clock backup battery is depleted, please contact the dealer to replace the battery (users cannot replace it themselves as there is a risk of explosion). Battery life: below 40 ℃>10 years, 40-50 ℃>4.1 years, 50-60 ℃>1.5 years.

SCREEN TRANSFER ERROR Picture transmission error retransmission.

Reduce the number of tags if the number of SCREEN TAG LIMITED EXCEEDED tags exceeds 256; Invalid tags will be disabled starting from the end.

The PLC type set in OBJ.PLC HAS NOT BEEN SETUP software does not match the actual one. Select the correct PLC type based on the hexadecimal number following the error code (e.g. 0: OMRON SYSMAC C); 1: Mitsubishi MELSEC AnN; 2: Siemens S5, etc.

6.2 Troubleshooting process for non display faults

If there is no display on the screen or a black screen during operation after power on, troubleshoot in the following order:

Check if the power supply voltage is 24VDC and if the polarity is correct.

Check if the backlight is damaged (observe for weak images at a tilted angle). If the backlight is damaged, replace the lamp tube.

Enter offline mode to check contrast/brightness settings.

Run "PLAY PATTERN" and "FRAME BUFFER" in self diagnosis.

If the diagnosis shows abnormalities, it may require repair.

6.3 Communication fault troubleshooting process

Confirm that the communication parameters (baud rate, data bits, stop bits, parity) between GP and PLC are completely consistent.

Confirm that the cable wiring is correct (see section 2.3 of the manual for pin definitions of RS-232C or RS-422).

Use the "SIO CHECK" in self diagnosis to test the serial hardware with a loopback cable.

Check if the system area address on the PLC side is valid and does not overlap with other programs.

For n: 1 connections, set the checkpoint number and network information address.

6.4 Touch screen does not respond or responds slowly

Check if the touch buzzer is enabled. If there is a beep sound, it indicates that the touch detection is normal.

Run the "TOUCH PANEL" self diagnosis, press each touch unit one by one, and confirm the highlighted display.

If there is no response in certain areas, it may be due to damage to the touch panel.

If the overall response is slow, check if the operation priority is set in initialization (if it is set to display priority, touch response will slow down).


Chapter 7: Maintenance and upkeep

7.1 Daily Cleaning

Dip a soft cloth in neutral detergent and wring it out before wiping the display screen and borders.

It is strictly prohibited to use diluents, organic solvents, or strong acid compounds.

Do not press the touch screen with hard or sharp objects (such as automatic pencils).

7.2 Rubber gasket replacement

After prolonged use, the sealing gasket may scratch, become dirty, or lose elasticity, resulting in a decrease in waterproof and oil resistant performance. Should be replaced regularly (GP370-WP00-MS). When replacing, it is necessary to reinstall GP and ensure that the sealing gasket is properly attached.

7.3 Backlight tube replacement (important safety operation)

The lifespan of the backlight tube is about 20000 hours, and the brightness decreases by half. Replacement steps:

Power off: Turn off the GP power and unplug the power cord.

Disassembly: Use a screwdriver to unscrew the top two screws, hold down the front of the GP with one hand, and press the top center unlock buckle with the thumb of the other hand to open the chassis shaft.

Disconnect the connector: Be careful not to remove the internal metal protective plate.

Remove the old lamp tube: Move the hook to the right and pull out the lamp tube.

Insert new lamp tube: The model must match (GP370-BL00-MS for LG and SC), and plug back the connector.

Close the lid: First insert the bottom buckle into the hole, close the back cover, and tighten the screws. Be careful not to clamp the connector cable between the front and rear covers.

Warning: When replacing the lamp tube, protective gloves must be worn to prevent cuts or burns. Do not replace the internal lithium battery by yourself (explosion hazard). If the battery runs out, please contact the dealer.

7.4 Regular Inspection Items

Is the environmental temperature (0-50 ℃) and humidity (20-85% RH) compliant.

Is there any corrosive gas present.

Is the input voltage between 20.4 and 27.6V.

Is the cable connection loose.

Is the installation bracket secure.

Is there any obvious damage to the sealing gasket.


Chapter 8: Advanced Techniques and Precautions

8.1 System version differences

System versions 1.20 and above do not support Memory Loader and uploading screen data from GP.

The Device Monitor function is only available for GP-PRO/PBIII for Windows 95.

8.2 Screen Data Backup

Due to unforeseeable circumstances such as power fluctuations and static interference, it is recommended to regularly backup the image files through PC software, which may cause damage to the image data.

8.3 LCD Screen Characteristics Notice

There are fine grid points on the surface of the LCD.

Long term display of the same static image may result in afterimages (burn-in). It is recommended to enable standby mode (screen saver) or switch screens periodically.

Color changes or shadows may occur at certain angles, which is a normal phenomenon of LCD and not a malfunction.

8.4 Special Environmental Requirements

Although the front panel protection level of GP370 is IP65f, additional protective measures are still required if it is exposed to oil mist or low viscosity cutting oil for a long time. Non specified oil products may cause deformation or corrosion of the front panel plastic.

When installed in explosion-proof areas (Class I, Division 2), relevant electrical regulations must be followed: the equipment must not be disconnected when live, and replacing components may damage the explosion-proof applicability.

  • Atlas Copco PF3000-C-HW Tensor S4 S7 RBU Controller
  • Atlas Copco PPBE0613 24VAC Control Panel
  • Atlas Copco PF3000-C-HW Tensor S4 S7 Controller
  • Atlas Copco Neos ARC-D130-S+ Inverter Drive
  • Atlas Copco Power Focus SL PF4002-G-HW Controller
  • Atlas Copco 8436 6770 00 ILT Base Station
  • Atlas Copco 1900520400 Air Compressor Control Panel
  • Atlas Copco 1900-0711-51 Display Keypad Unit
  • Atlas Copco 1900-0710-52 Communication Control Board
  • Atlas Copco 1900-0701-04 Control Interface Module
  • Atlas Copco 8092 1143 40 SRTT Transducer 180Nm
  • Atlas Copco MT Focus 6000 Controller with Pump and Screwdriver
  • Atlas Copco Elektronikon GraphicPlus Controller PPBE0622 PPBE0633
  • Atlas Copco PF3109-G-DN-HW Tensor 8-9 Power Focus Nutrunner Control
  • Atlas Copco Elektronikon P1900520440 Touch Controller
  • Atlas Copco Power Focus 8 Controller 8436280002
  • Atlas Copco 8436 1500 03 FlexCarrier 3-Slot Torque System Component
  • Atlas Copco Power Focus 6000 PF6000 Industrial Controller
  • Atlas Copco TC-4000-P-PB-ES Power Macs Controller
  • Atlas Copco 8433-0015-20 8433001520 Cable Assembly
  • Atlas Copco 49X10301AB Pressure Transducer Sensor
  • Atlas Copco 8436180002 Replacement Filter Element
  • Atlas Copco C4700A01V216 Compressor Control Module
  • Alcatel-Lucent 3HE01019AAAA01 High-Speed Interface Module
  • Alcatel-Lucent 111381 Power Distribution Module
  • Alcatel TN 2523 1:1 CDN III Module – MRPQAE3
  • Alcatel-Lucent 3he06151aaac01 8-Port Interface Module – IPUIBKB3AA
  • Alcatel-Lucent LNW46 DMX Metro OC12 Interface Module – 108694878
  • Alcatel-Lucent 41A12C FT-2000 Optical Transponder Unit – 108188053
  • Alcatel-Lucent 8DG02607AA POW100 DC-DC Converter Module
  • Alcatel-Lucent LambdaXtreme WWBQ21 40G Optical Transponder
  • Alcatel-Lucent TN1891 5ESS Protocol Handler PHV5 Commcode 108747064
  • Alcatel-Lucent 300-0303-900 T1D3PDL1AE Digital Matrix Card
  • Alcatel-Lucent G-821M-A Module
  • Alcatel Lucent MPT-GC Eth 1G+ARM TX 81-86GHz 3DB80005AAAAO1
  • Nokia 3KC48990AB 1830PSS 16FAN2 Fan Unit
  • Alcatel 3EC17041AA PSPC-G4 PCB CP011200552
  • Alcatel 300-0437-906 Rev F DEXCS DMC T1D1L0S Module
  • Alcatel-Lucent 3DW03697ABBA01 TFD64A Module
  • Alcatel-Lucent AWR12 S1-1 UN Interface T3PQAC3AAA
  • ALCATEL LUCENT 9500-MPR ODU RADIO MPT-HC V2 9558HC 3DB20914BAAA03 6GHZ
  • Alcatel-Lucent 9500-MPR ODU 300 11GHz Microwave Radio MPT 3DB23035AEAA01
  • Alcatel 2C7-1005-000 Teflon Bell Jar Holder Ring – 146111
  • Alcatel-Lucent BNJ118 S1:4 Circuit Board – Interface Module
  • Alcatel-Lucent 9500-MPR ODU 300 6GHz Microwave Radio MPT 3DB23215AFAA01
  • Alcatel 3EM04001AA Signal Processing Unit with Accessory Cards
  • Alcatel VAUCAL5KAB AA1418FE2BG 3FE67437AAD02 Interface Card
  • Alcatel-Lucent 1642 Edge Multiplexer N1217P YF – Access Node
  • Alcatel-Lucent 3HE07158BA 7750 SR-12 12-Port 10GIGE MultiCore IMM IPUCA741AA
  • Alcatel 101200429000 Power Divider 746-776 MHz with Heatsinks
  • Alcatel-Lucent 9500-MPR ODU 300 MPT 6GHz 3DB23215ADAA01 High Power Radio
  • Alcatel-Lucent 9500-MPR MPT-HC 23GHz 2/2P ODU Radio 3DB20474BA
  • Alcatel-Lucent 9500-MPR ODU 300 MPT 6GHz 3DB23215AAAA01 Low Power Radio
  • Alcatel 3BA52126ABAA OmniPCX 4400 Compact Cabinet
  • Alcatel-Lucent 3HE12300AA 7750 SR-1 Subrack with Licenses
  • Alcatel 300-1368-903 Rev C DEXCS SPA-1 T1PQAC1 Line Card
  • Alcatel-Lucent 408977981 WOWUAB6HAA 10G XPR OTU2 XPonder Card
  • Alcatel-Lucent-Nokia 3HE08423AARC01 7750 SR Control Processor Module IPUCBGZ1AA
  • Alcatel-Lucent 9500-MPR ODU 300 MPT 6GHz 3DB23215ABAA01 Low Power Radio
  • Alcatel-Lucent CPU7-2 3BA23259ABJE 05 Control Processor Module
  • Alcatel WTM11AD 3DW03915DABA01 Optical Transponder Module
  • Alcatel-Lucent 1340FMPK Card Chip BA5IVY6BAA – Processor Module
  • Alcatel-Lucent 3HE06151ACAC01 Control Fabric Module
  • Alcatel-Lucent 9500-MPR 18GHz 1P-1 Protection ODU Radio 3DB20433BA AA04
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 18GHz Radio 3DB20433BAAA04
  • Alcatel-Lucent SM269 LMPQ04KAXX Circuit Pack – Interface Module
  • Alcatel OME25HP Filter Cartridge – 107494
  • Alcatel-Lucent ALU-BZ74 99BC-4 –48V Battery Cabinet
  • Alcatel-Lucent WWAA37 Optical Amplifier WMAPZNZAAB – CP Series
  • ALCATEL LUCENT 9500-MPR ODU RADIO MPT-HC V2 9558HC MPT-XP 3DB20476BAAA04 23GHZ
  • Alcatel Tyco Yukon ES760A Rectifier
  • Alcatel-Lucent 9500-MPR ODU 300 MPT 23GHz 3DB23045HMAA02 Microwave Radio
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 11GHz 3DB20548ACAA01 Microwave Radio
  • Alcatel Lucent 3DH03173AKAA Module
  • Alcatel-Lucent 76-0300-02 CSM-V2 PCB
  • Alcatel 9400 UX ODU Module 3CC06729ABAA
  • Alcatel-Lucent 408981363 Jigsaw A Band Block 24/-48V KS24624L58
  • Alcatel 3BA53095 PCB Card
  • Alcatel 2C7-1005-000 Bell Jar Holder Ring Teflon PC7-1005-000
  • Alcatel-Lucent ES640 PWDQAGKUAA 5ESS 48V DC Alarm Control Unit
  • Alcatel-Lucent 9500-MPR ODU 300 23GHz Microwave Radio MPT 3DB23045HM
  • Alcatel-Lucent KFA720 WMOTCMVLAB Optical System Interface Carrier
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 15GHz Microwave Radio 3DB20373BAAB04
  • Alcatel-Lucent AKM70 S1-7 SMUX1 Sub-Multiplexer – T3PQWAEAAH
  • Alcatel-Lucent 107486490 DDM-2000 SONET DS3 Circuit Pack – BBG4B
  • Alcatel-Lucent SBEVM BNJ82 1:12 Module – AV950-01168
  • Alcatel-Lucent 938A Optical Loss Set – Test & Measurement Kit
  • Alcatel-Lucent MS1025-25O16-ED Fiber Optic Unit – 48VDC
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 23GHz 1/1P Microwave Radio 3DB20473BA AA04
  • Alcatel-Lucent bCEM-U Control Module – 3BK28676ABAC01
  • Alcatel ASI20 Detector Control Module
  • Alcatel Lucent 130B S-1 PWPQ08B Power Unit
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 9558HC 6GHz 3DB20441BBAA02
  • Alcatel-Lucent 9500-MPR ODU MPT-MC 15GHz 3DB20824AAAA02 Microwave Radio
  • Alcatel-Lucent 9500-MPR ODU MPT-MC 15GHz 3DB20822AAAB02 Microwave Radio
  • Alcatel-Lucent 3AL92111AA 1P10GSO Interface Module
  • Alcatel 8220 CTT 450 Turbo Pump Controller 127821
  • Alcatel-Lucent 3AL78823AAAE 02 Module
  • Alcatel-Lucent 90-0413-01 Universal Card
  • Alcatel-Lucent BRMA 10Base-T/100Base-TX Connecting Box 3BA56170ACAB010842
  • Woodward Micronet 5453-279 Rev E Chassis Rack for TMR Control
  • Alcatel-Lucent KFA632 WMOTBUKLAA 10G Optical Interface Carrier
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 3DB20474BAAB04 23GHz Microwave Radio
  • Alcatel-Lucent KFA720 WMOTCMVLAB SFP/XFP Optical Interface Carrier
  • Alcatel-Lucent 3AL00114AB Universal Interface Module
  • Alcatel-Lucent BBG9 S1:1 OHCTL Optical Hardware Control Module
  • Alcatel-Lucent FB16401-A-I03 GTD-5 Analog Master/Slave Control Board
  • Alcatel-Lucent MCR1721B Control Module
  • Alcatel-Lucent 9500-MPR 3DB20547ACAA01 ODU MPT-HC 11GHz Microwave Radio
  • Alcatel-Lucent 3HE01014AAAA02 Interface Module
  • Alcatel-Lucent 244-2091-005 High Density Digital Line Card V1.5
  • Alcatel-Lucent LAMBDAXTREME WWAA36 Optical Amplifier Module
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 6GHz 2P-2 Radio 3DB20444BAAA05
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 9558HC MPT-XP 6GHz 3DB20442BBAA02
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 23GHz 3DB20476ABAA01 Microwave Radio
  • Alcatel Lucent 3HE01019AAAA01 Module
  • Alcatel CPU5 3BA23071 PCB Card with IO2 3BA23050 Set
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 9558HC 6GHz 3DB20443BBAA02
  • Alcatel Lucent 500-1113-211 Rev H Channel Bank Assembly
  • Alcatel Lucent 89-0419-B-2 BA9ATS0FAB Frontal Compute Module
  • Alcatel-Lucent LambdaXtreme 1625 WWAF31 Optical Amplifier CP Module
  • Alcatel Z24 3BA53065 Analog Extension Card 3BA52065 AAAA KAZZB-01
  • Alcatel 3EH08263AAXX000448 OmniPCX Office Large PBX System
  • Alcatel Lucent VSEM-C 3FE62453 XA VAUCAJZKAA 7330 DSLAM Line Card
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 3DB20432BAAA04 18GHz Microwave Radio
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 3DB20546ACAA01 11GHz Microwave Radio
  • Alcatel-Lucent 3DB04823AAAA Circuit Board
  • Alcatel-Lucent 3DB04530AAAA Circuit Board