Secondary load overload: Check whether the total current of the control circuit (contactor coil, indicator light, PLC input, etc.) exceeds the CPT capacity (usually indicated in the model). For example, CPT is 50VA, and the maximum secondary current of 120V is 0.42A. If multiple contactors are simultaneously closed, it may exceed.
Primary voltage error: For example, if the CPT primary tap is connected to 240V and the actual power supply is 480V, it will cause the iron core to saturate and severely heat up. Be sure to wire correctly according to the CPT code.
Chapter 7 Maintenance and Replacement Guide
7.1 Maintenance of contactor contacts
For NEMA size 00~4 contactors, the contacts can be inspected and replaced. Remove the arc extinguishing cover after power failure and observe the main contact:
Slight erosion (surface gray or slightly pitted): Use fine sandpaper (400 grit) to gently polish, do not use files or grinding wheels.
Severe erosion (silver dot melting, unevenness) or wear to less than 1/2 of the original thickness: the contact kit should be replaced (Eaton part number see Tab 16).
Check every 6 months or 100000 operations.
7.2 Overload Relay Replacement
Replacement of bimetallic heater package:
Disconnect all power sources.
Open the overload relay cover and manually remove the old heater element (one for each phase).
Insert the new heater (pay attention to the direction) and ensure it is securely fastened.
Record the replacement date on the device label.
C440 solid-state overload replacement:
No need to replace the heater, just readjust the setting current knob.
If C440 is damaged, the entire module needs to be replaced (C440 in non combination starters is an independent component that can be unplugged). Pay attention to maintaining the same current code (A~H).
7.3 Coil replacement steps
Disconnect the power supply and remove the wires from the coil terminals (marked as excellent).
Remove the coil fixing spring or screw.
Slide the old coil out of the magnetic yoke.
Before installing the new coil, check if the magnetic pole surface is clean (without rust or foreign objects).
Install a new coil, tighten the fasteners, and rewire.
Power on test for suction status (no abnormal noise).
7.4 Combination starter fuse/circuit breaker replacement
Fuse type: Open the outer cover and use a fuse puller to remove the fuse link. Be sure to use dual element fuses of the same model and current level. Ordinary fuses or copper wires shall not be used as substitutes.
Circuit breaker type: operate the handle to the OFF position, release the circuit breaker terminal, and remove the faulty circuit breaker. Before installing a new circuit breaker, confirm that the setting scale matches the motor FLA.
Chapter 8 Safety Regulations and Coordination
8.1 Importance of Type 2 Coordination
According to UL/CSA and IEC 60947-4-1, Type 2 coordination means that after a short circuit fault, the contactor and overload relay will not damage personnel or equipment and can continue to be used without replacement (slight contact fusion welding is allowed, but must be able to separate). The Eaton Freedom combination starter (correctly configured with fuses or circuit breakers) can meet Type 2 coordination under symmetrical current of 100kA.
Engineers must ensure that the brand and model of the fuses used are consistent with Eaton's certified series when selecting. Common certified fuses include Bussmann's LPJsP, JKS, etc. Using non certified fuses may cause Type 2 failure.
8.2 Motor Branch Circuit Protection (NEC 430)
According to Article 430 of the National Electrical Code (NEC), short-circuit protection devices (fuses or circuit breakers) for motor branch circuits can be selected based on the following percentage of motor FLA:
Dual element delay fuse: up to 175% (but not exceeding 225% for certain situations).
Instantaneous circuit breaker: maximum 800% (used for designing B motor).
The fuse clip or circuit breaker in the combination starter is configured according to typical values when it leaves the factory, and the final setting value should be adjusted by the on-site engineer based on the actual motor nameplate.
8.3 Manual operation in emergency situations
For combination starters with isolation switches, the external handle can directly cut off the power supply in the locked state. Some models are equipped with door interlock: the door cannot be opened when the handle is in the ON position to prevent live maintenance. If it is necessary to inspect the interior when powered on, the upstream power supply must be disconnected first and LOTO procedures must be followed.