OMRON D4SL-N/D4SL-NSK10-LK Safety Door Switch Comprehensive Guide

F: | Au:FANS | DA:2026-05-28 | 47 Br: | 🔊 点击朗读正文 ❚❚ | Share:


OMRON D4SL-N/D4SL-NSK10-LK Safety Door Switch Comprehensive Guide

Introduction: The core role of safety door switches in modern industry

In hazardous areas such as automated production lines, robot workstations, and large stamping equipment, safety door switches are the first line of defense to prevent accidental exposure of personnel to mechanical injuries. The Omron D4SL-N series safety door lock switch has become the preferred choice for many equipment manufacturers and system integrators due to its locking retention force of up to 1300N, flexible contact configuration, and unique sliding key attachment. This article is based on the complete technical data of D4SL-N and its matching sliding key D4SL-NSK10-LK. It systematically sorts out the model code, installation specifications, electrical connections, safety logic, and fault diagnosis, aiming to help engineers quickly grasp the engineering application points of this product.


Product Family and Core Features

2.1 D4SL-N Safety Door Lock Switch

The D4SL-N series belongs to the electromagnetic door lock switch, which is divided into two types: mechanical lock+electromagnetic release and electromagnetic lock+mechanical release. Its core advantages include:

High locking force: The key has a holding force of up to 1300N, which can resist moderate external forces and prevent the door from opening abnormally under unexpected force.

Flexible contact configuration: Provides three basic frames: 4-contact, 5-contact, and 6-contact. Each frame also includes multiple built-in switch combinations, which can simultaneously achieve door status monitoring (opening/closing) and lock tongue status monitoring (locking/unlocking).

Direct disconnection mechanism: All NC (normally closed) contacts comply with the direct disconnection requirements of EN60947-5-1, ensuring that the contacts are forcibly disconnected in the event of a switch failure, meeting the "fault safety" principle of the safety circuit.

IP67 protection level (excluding head keyhole): The switch body can be immersed in water for a short period of time, but it should be noted that the keyhole cannot be exposed to cutting fluid, oil stains, or chemical solvents for a long time.

Quick wiring selection: Terminal block type and connector type (M12 circular connector) are available, and the connector type can achieve "one click plugging and unplugging", greatly reducing wiring time.

Rotating head: It can change the insertion direction of the operating key (front, top, side) without disassembling the main body, adapting to different door frame layouts.

2.2 D4SL-NSK10-LK sliding key kit

This attachment is designed specifically for lightweight sliding doors or hinged doors (door weight ≤ 20kg), with the core value of preventing personnel from being trapped: when the operator enters the dangerous area, they can insert their own locking key into the sliding handle and rotate it to the "SLIDE LOCK" position. At this time, no one outside can move the sliding handle to remove the operating key, thus avoiding others from accidentally closing the door and locking internal personnel. The kit includes:

Sliding base (pre installed but not fixed)

Operation key (D4SL-NK1 horizontal installation type)

2 locking keys (optional from 01 to 30, standard 01)

Lock key lanyard, warning label, specialized installation screws, etc

The mechanical durability of this kit is over 20000 times, and the working temperature is -10~55 ℃.


In depth interpretation of model codes

3.1 D4SL-N Basic Model Structure

Example of D4SL-N standard model format: D4SL-N2AFA-DN

The meanings of each part are as follows:

(1) Tube outlet (1st digit)

2: G1/2 thread

3: 1/2-14 NPT thread (with M20 adapter included)

4: M20 thread

M20 is recommended for exporting equipment to Europe, and 1/2-14NPT is recommended for exporting to North America.

(2) Built in switch type (letter)

4, 5, and 6 contacts all have different internal wiring logic:

4-contact standard type (internal series connection):

A: 1NC/1NO+1NC/1NO (one set each for door monitoring and lock monitoring, normally open/closed, and connected in series internally)

B:1NC/1NO + 2NC

C:2NC + 1NC/1NO

D:2NC + 2NC

4-contact non series type (S/T/U/V): The contact form is the same as above, but the door monitoring and lock monitoring circuits are not connected in series internally, suitable for control systems that require independent signal feedback.

5 contact types (E/F/G/H):

E:2NC/1NO + 1NC/1NO

F:2NC/1NO + 2NC

G:3NC + 1NC/1NO

H:3NC + 2NC

6-point type (N/P/Q/R):

N:2NC/1NO + 2NC/1NO

P:2NC/1NO + 3NC

Q:3NC + 2NC/1NO

R:3NC + 3NC

The direct disconnection function is only applicable to specific NC contacts, for example, only 11-12 contacts in Type A are certified.

(3) Head material (3rd place)

F: Resin head (standard)

D: Metal head (only available for 6-point type, for higher strength requirements)

(4) Lock type and release method

Models that do not contain "G" (such as D4SL-N2AFA-DN) are mechanical locks+electromagnetic releases: when powered on, the electromagnet is engaged and unlocked; Mechanical spring locking during power outage. Suitable for power outage safety.

Models containing "G" (such as D4SL-N2AFG-D4N) are equipped with electromagnetic locks and mechanical releases: when powered on, the electromagnet pushes the lock tongue to lock, and when powered off, it unlocks. Suitable for scenarios that require power on locking, but attention should be paid to the risk of automatic unlocking of the rear door after power failure.

(5) Other suffixes

-DN: Connector type with orange LED indicator light (24VDC)

No DN: Terminal block type, no indicator light

-D4: Terminal block type with indicator light (only for some models)

3.2 D4SL-NSK10-LK Lock Key Model

Basic type: D4SL-NSK10-LK (lock key number 01)

Internal leverage type: D4SL-NSK10-LKH (internal leverage sold separately, but cannot be used for other products)

The lock key number can be customized from 02 to 30 (please inquire with Omron representative)

Key points for mechanical installation and dimensions

4.1 Installation of switch body

Fixed with M4 screws, with a tightening torque of 0.75~1.15 N · m, and a washer must be used.

There is a reinforced fixing hole with a diameter of 4.5mm on the back of the switch, which can be inserted with a pin or bolt with a diameter of 4mm and a height of ≤ 1.5mm, further enhancing its impact resistance.

Do not use the switch as a door stopper: a mechanical stopper must be installed independently on the door frame to ensure that the operating key is located within the set area after the door is closed (the key insertion depth is 0.5-3mm, if D4SL-NK5 is installed in reverse, the set area is 2.1-3.0mm).

The farther the switch is from the door hinge, the better to reduce the lever force on the lock tongue. Suggest installing it on the side of the door handle.

4.2 Installation of Operation Key

Key models: Horizontal installation NK1, short type NK1S, with buffer rubber NK1G, vertical installation NK2/NK2G, adjustable NK3/NK5.

Key fixing screw torque: NK1/NK1S is 2.4~2.8 N · m; NK1G is 0.75~1.15 N · m.

The horizontal/vertical deviation between the key insertion center and the keyhole should be controlled within ± 0.8mm, and the insertion radius should follow the curve chart in the data (such as the maximum horizontal insertion radius of about 80mm for NK1/NK2).

Do not use the old D4SL-K series keys, otherwise they cannot be locked.

4.3 Installation of sliding key (D4SL-NSK10-LK)

Only applicable to lightweight doors (≤ 20kg), and the switch type must be D4SL-N.

The sliding base is fixed with 4 M6 screws, with a torque of 6.0~7.0 N · m. It is recommended to apply anti loosening glue.

The sliding handle can only be operated in the direction of A or B as shown in the diagram (horizontal or vertical), and cannot be reversed.

Installation of inner lever: First, use a T30 star wrench to remove the handle fixing screw, and then tighten the hexagonal part of the inner lever (opposite side 10mm) with a torque of 9-10 N · m. Be careful not to lose the spring washer and hex nut.

Do not forcefully push or pull the sliding handle without inserting the locking key, otherwise it may damage the internal mechanism.

The operating torque of the lock key should not exceed 1 N · m. After rotating to the "SLIDE LOCK" position, remove the key to prevent third-party misoperation.


Electrical Connection and Wiring Guide

5.1 Terminal Definition and Internal Circuit

The terminal numbering rules for terminal block switches are as follows (taking 4-contact A type as an example):

Door monitoring: 11 (public), 12 (NC), 42 (NO)

Lock monitoring: 33 (public), 34 (NC), 64 (NO)

For different contact configurations, special attention should be paid to: direct disconnection only certifies some NC terminal pairs, for example, 11-12 in type A are certified direct disconnection contacts; And 34-33 or 64-63 are not directly disconnected and cannot be used as the main channel for safety circuits.

Electromagnetic coil terminal:

E1(+24VDC)

E2(0V)

The positive and negative poles of the indicator light (if equipped) are consistent with the coil.

5.2 Coil Drive Characteristics

Rated voltage: 24VDC+10%/-15%

Starting current (approximately 10 seconds):

6-contact type: 0.26A (approximately 6.4W)

4/5 contact type: 0.2A (approximately 4.8W)

Maintain current: averaging about 0.2A (2.6W), internal PWM circuit automatically switches.

Important timing requirement: For electromagnetic lock types (models including G), power must be supplied to the electromagnetic coil only after the door is completely closed (the operation key is inserted). If you turn on the power first and then close the door, the key may not be able to get stuck by the lock tongue, causing the lock to fail.

5.3 Recommended cables and crimping terminals

Terminal block type suitable wire: AWG22~18 (0.3~0.75mm ²)

Recommended crimping terminals: PHOENIX CONTACT AI 0.34-8TQ(AWG22)、AI 0.5-8WH(AWG20)、AI 0.75-8GY(AWG18)

Stripping length: L1 ≤ 14mm, L2=8mm

Terminal screw torque: 0.5~0.6 N · m

Connector type (D4SL-NO type):

Applicable wires: AWG24~22 (0.2~0.3mm ²)

Supporting socket: JST XHP-10 shell+SXH-001T-P0.6 terminal

Attention: The rated current of the connector type is relatively low, and should not exceed 2A when AWG24 is used.

5.4 Treatment of catheter ports

The thread length of metal cable joints shall not exceed 9mm, otherwise it may touch the internal circuit board.

NPT threads require the use of an accompanying adapter and the wrapping of sealing tape (raw material tape) to prevent leakage.

Do not use metal hoses to directly connect 1/2-14NPT ports to avoid damaging the adapter.


Security authentication and performance parameters

6.1 Standard Certification

Key points of certification body standards

T Ü V S Ü D EN60947-5-1, GS-ET-19 direct disconnection certification

UL UL508, CSA C22.2 No.14 Document Number E76675

CQC GB/T 14048.5 China Compulsory Certification

KOSHA EN60947-5-1 only available for some models

6.2 Rated Value (TUV/CCC)

AC-15: 120V/1.5A (main circuit) or 1A (other terminals)

DC-13:125V / 0.22A

Short circuit protection: Use 4A fuses that comply with IEC60127

6.3 UL/CSA Rated Values

120VAC: Connect current 15A (1800VA), disconnect 1.5A (180VA), continuous current 2.5A

125VDC: Connect/disconnect 0.22A (28VA), continuous current carrying 1.0A

6.4 Example of the highest security level

Omron official example: Combining D4SL-N □ A □ (mechanical lock type)+D4N/D4F/D4B-N limit switches+G9SE-201 safety relay unit can achieve PL e/4 category (ISO 13849-1), stop category 0, and manual reset. The evaluation results of this combination can serve as a reference for user system design.


Operation timing and safety logic

7.1 Mechanical lock type (default power-off lock)

When the door is opened: the operation key is not inserted, the door monitoring contact is activated (NC disconnected), and the lock monitoring contact is in the "unlocked" state.

Closing the door: The key is inserted and the door monitoring contacts switch (NC closed), but the lock tongue is still pushed out by the spring and the key cannot be removed.

Unlock: Supply power to the electromagnetic coil for about 10ms to 10 seconds (starting current stage), the electromagnetic coil will engage, the lock tongue will retract, and the key will be allowed to be removed. Attention: After the coil power supply exceeds 10 seconds, it will automatically switch to constant current holding mode. At this time, the lock tongue may not be able to maintain suction, so it is not suitable for long-term power-off door opening scenarios.

7.2 Electromagnetic lock type (power off automatic unlocking) - critical warning

Correct sequence: Close door → Fully insert key → Power supply to electromagnetic coil → Lock tongue extends to lock key

Wrong sequence: First supply power to the coil → then close the door → the key cannot be stuck by the lock tongue, and the door can be opened at any time, completely losing its safety function! This is the most easily overlooked error in on-site debugging.

The electromagnetic lock type automatically unlocks after the power supply is stopped, so it must not be used for moving parts that are still dangerous after a power outage (such as flywheels for inertial sliding and gravity drop mechanisms). Additional mechanical retaining devices or pneumatic brakes must be used.

7.3 Use of key release

The mechanical lock type body has a release keyhole (linear knob) that can be manually unlocked in emergency situations or power outages.

When leaving the factory, D4SL-N □□ A is in the "UNLOCK" position, and D4SL-N □□ G is in the "LOCK" position.

The operating torque shall not exceed 0.2 N · m. After unlocking, restore to the LOCK position and seal with lead to prevent unauthorized use.

Do not turn the release key when the electromagnetic lock is in the power on lock state, otherwise the internal gears may be damaged.

Anti Trapping Principle and Application of Sliding Key

Traditional safety door switches pose a fatal risk: when personnel enter a hazardous area, external personnel may accidentally close and lock the door, causing internal personnel to be trapped and unable to open the door from the inside. D4SL-NSK10-LK solves this problem through the "lock key" mechanism:

Before entering: The operator inserts the locking key into the sliding handle and rotates it to the "SLIDE LOCK" position, then removes the key and carries it with them.

At this point, the sliding handle is mechanically locked and cannot slide backwards, so the operating key cannot be removed from the keyhole on the switch head - the door cannot be closed.

When leaving: The operator must re insert the locking key from the inside and turn it back to the "FREE" position, slide the handle to resume movement, and then close the door and lock it.

This kit is different from the traditional "trapped key" system: the trap key requires the key to be inserted into the door switch before closing the door, while the D4SL-NSK10-LK can lock the sliding mechanism when the door is not closed. Both have their own advantages and disadvantages, but the sliding key has lower cost and is suitable for lightweight door renovation.

Attention: It is forbidden to install the sliding key vertically (with the sliding handle moving up and down), as it may cause the internal slider to accidentally slide due to gravity, resulting in the inability to close the door.


Common troubleshooting guide

Possible causes and solutions for the fault phenomenon

After the door is closed, it cannot be locked (the key can be removed). 1. Electromagnetic lock type, power on first and then close the door

2. The mechanical lock coil is not powered off. 1. Modify the PLC program to ensure that the signal for closing the door in place is connected before outputting power to the coil

2. Check the coil control logic

The safety circuit cannot be reset after the door is closed. 1. The door monitoring contact does not move (the key is not inserted deeply enough)

2. The lock monitoring contact does not move (the lock tongue is not in place). 1. Adjust the key installation position to ensure that the pre travel is ≥ 15mm

2. Check the door stopper to ensure that the key is in the set area (0.5-3mm)

Electromagnetic coil burnt or abnormally heated 1. Voltage exceeding 28.8V

2. Maintain current circuit fault (always in startup current mode) 1. Check the stability of the 24V power supply

2. Replace the switch

The sliding key can still slide after being locked. 1. The locking key has not been rotated into place

2. The internal locking mechanism is damaged. 1. Confirm that the locking key is rotated to "SLIDE LOCK" and aligned with the mark

2. Check if the mechanical durability exceeds the limit (>20000 times)

The indicator light is not on (with LED model). 1. The coil power supply is normal, but the LED is damaged

2. Reverse polarity (orange light has polarity) 1. Use a multimeter to measure E1/E2 voltage

2. Swap E1/E2 wiring

10. Maintenance and lifespan management

Mechanical durability of switches: The overall lifespan is not explicitly stated in the manual, but the engagement lifespan of electromagnetic coils can typically reach hundreds of thousands of times. It is recommended to replace it regularly according to the actual load (current, on-off frequency), usually every 2 years or 1 million operations for inspection.

Mechanical durability of sliding key: ensuring more than 20000 operations (including reciprocating sliding handle and locking key rotation). After reaching this number, it is necessary to check the wear of the plastic guide rail and the deformation of the locking keyhole.

Environmental requirements: Avoid corrosive gases such as H ₂ S, SO ₂, NH ∝, HNO ∝, Cl ₂, etc; Storage temperature -25~70 ℃.

Daily inspection: Manually test the door lock function at least once a month - try to remove the key while powered on, but it should not be able to be removed; After pressing the emergency stop or disconnecting the safety relay, the key should be able to be smoothly removed (mechanical lock type).


Typical Application Circuit Example (PL e Level)

The following is the recommended safety circuit architecture by Omron:

Input: Connect the door monitoring NC contacts (such as 11-12) of the D4SL-N door lock switch in series to the input terminal of the safety relay; The lock monitoring NC contacts (such as 33-34) are also connected in series to another channel of the same safety relay.

Logic: After the safety relay (such as G9SE-201) detects that both channels are closed (door closed and locked), it allows the manual reset button to take effect, and then closes the internal safety output contacts.

Output: Safety contact controls the main contactor (motor, driver power supply). Before resetting, ensure that the electromagnetic lock coil is powered on (for electromagnetic lock type) or the mechanical lock coil is powered off (for mechanical lock type).

Be sure to install the reset button outside the hazardous area and require manual reset (non automatic reset) to prevent the device from restarting immediately after the door is accidentally closed.

  • B&R X20CM0985 PLC Module
  • Banner XS26-2DE 85064 Safety Controller
  • Siemens 3SK2122-1AA10 Safety Relay
  • HMS Anybus AB7646-F Gateway PROFIBUS EtherNet/IP
  • Siemens 6SN1118-0DM11-0AA0 SIMODRIVE 611 Card
  • Siemens C98043-A7001-L2-4 CUD1 Control Board
  • Stein Sohn E 083.1 PLC Rack Module 0010026-054100A
  • Allen Bradley 800H-2HA7P Push Button Station
  • Schneider BMXNRP0200 M340 PLC Module
  • KEPCO BOP 200-1M Bipolar Power Supply Amplifier
  • Mitsubishi Q2ASHCPU PLC Module with A1SX42 A1SY42 QC24-R2 A1SD75P2-S3
  • Siemens Siprotec 7SJ61 Overcurrent Protection
  • Keyence LJ-V7000 Controller Laser Profiler
  • Siemens 6EP3437-8SB00-0AY0 Power Supply 20A
  • Pasaban MC-2006 03 CAN Bus PLC Card
  • ETAS ES600.2 PLC Module Prototyping
  • ABB ACS800-01-0005-3+P901 Frequency Converter
  • Omron NX102-1100 PLC Module Machine Automation
  • Square D BMXCPS3500 PLC Power Supply Module
  • Allen-Bradley 96657704 Fiber Optic Converter 1771-AF
  • Corcom 20VK1 Power Line Filter
  • Novellus 2805-11407 PLC Rack Assembly
  • Sick RLY3-EMSS100 Safety Relay Module
  • Microchip PIC12F508-I/P Microcontroller
  • Fanuc A02B-0098-B511 Motherboard
  • Merlin Gerin PB80 PLC Rack Module
  • ABB Pluto S20 V2 CFS Safety PLC
  • Honeywell TK-PRR021 Redundancy Module
  • B&R 7XX419L.50-1 Bus Controller
  • Mitsubishi NV400-SW 3P 300A Breaker
  • B&R X20AT2222 Temperature Module
  • Corcom 20VK1 EMI RFI Filter
  • Novellus 2805-11407 PLC Rack Assy
  • Mitsubishi FXAOM01BD Analog Output Module 4CH
  • NORIS A1-91 PCB Rack Module A1-91-4 A1-91-5 A1-91-6 A1-91-7 A1-91-8
  • Omron ZFV-SC50 Smart Camera Vision Sensor
  • Schneider Electric EOCR-PMZ Motor Protection Relay
  • B&R X20 SO 6300 PLC Module Safety Output
  • Mitsubishi A2ACPU21-S1 CPU Module MELSEC
  • Siemens 6ES7405-0KA02-0AA0 PS405 10A Power Supply
  • Samsung PVU-2424 Power Supply Unit DC24V 24W
  • ATTO controlSYS ATT0-CPU44 PLC with Display
  • Lenze EPZ-10203 CANPT010W3E Absolute Encoder
  • GE IS215WEMAH1A+IS210BPPBH2CAA Mark VIe Embedded Processor and Backplane Power Distribution Board
  • GE IS215AEPAH1CH+IS210BPPBH2CAA Mark VIe Application Processor and Backplane Power Distribution Board
  • GE IS215WECAH1B+IS210BPPBH2CAA Mark VIe Control Platform
  • GE PCM Regulator for EX2100e Power Conversion Module 151X1235DB15SA1
  • Lenze ECSEA048C4B servo drive
  • ABB PM665 3BDS005799R1 redundant CPU module
  • BAUMULLER b maXX 3000 Servo Controller BM3401-LIFBO-ACOOOCB-G-02-O-02
  • R&S EPL10200-W EMI Test Receiver
  • Schneider M522220000 16 way relay output module
  • ABB 3HAC031851-001 SMB Unit Technical Manual
  • Fuji NB1U56X-01 Programmable Controller Guide
  • Siemens 6AG1153-2BA02-7XB0 SIPLUS IM 153-2 Manual
  • Beckhoff EL6631 PROFINET Terminal Manual
  • Lenze E82EV302-4C Frequency Inverter Manual
  • Siemens 6SE7038-6EK84-1JC2 IGD8 Board Specifications
  • Pilz 774595 Safety Relay Specifications
  • Fanuc A20B-8200-0847 PLC Board Specification
  • Allen Bradley 1785-L60B/E PLC CPU Manual
  • PASABAN MC-2006 03 PLC Card Specifications
  • B&R X20CP1382 PLC Control Module X20 CPU
  • B&R X20DC2395 PLC Module Digital Output
  • AS-2P-70M-B Industrial PLC Communication Cable 70M
  • Siemens 6ES7136-6BA00-0CA0 PLC Module ET 200SP
  • Siemens 1FK7083-5AF71-1EB3 Servo Motor SIMOTICS S
  • WAGO 750 Series I/O Modules 750-842 750-530 750-430 750-602 750-514 750-600
  • Microchip TC9401CPD F/V Converter 100kHz 14DIP
  • Mitsubishi GT2310-VTBA GT2310-VTBD HMI Touch Screen 10.4 Inch
  • Siemens 3RT2036-1AN20 AC Contactor SIRIUS
  • Mitsubishi GT2708 HMI Touch Screen GT2708-VTBA VTBD STBA STBD
  • Siemens 6FC5110-0CB01-0AA0 CNC PLC CPU
  • ABB SINT4130C PCB Board
  • Omron NX1P2-1040DT PLC Controller
  • Fuji FRN3.7C1S-2J VFD
  • PLC-60/75 /E2UK Shielded Braided Cable
  • Omron CJ1W-NC434 Position Control Unit
  • Omron NX-AD2208 Analog Input Module
  • PASABAN MC-2006 03 PLC Card
  • Schneider 9038CR34 Pressure Switch
  • Pilz 240340 Safety Control Module
  • Mitsubishi A2NCPU Programmable Controller MELSEC
  • Mitsubishi Alpha XL Alarm Modem M20 Expansion
  • AutomationDirect D0-06DD2-D PLC DL06 Controller
  • Toshiba COMW01-21 PCB Control Board Turbine
  • Siemens 6FX1122-1AC02 Coupling Module SINUMERIK
  • Omron CVM1-CPU21-V2 CPU Unit Programmable
  • Beckhoff EL7041 Stepper Motor Terminal EtherCAT
  • B&R X20AI4622 Analog Input Module 4 Channels
  • OAT PMC25.2-003 Programmable Controller Module
  • Fanuc A16B-2200-0350 Graphic Board Series 16
  • Eaton Cutler Hammer 6-26-2 Contactor Contact Kit
  • Omron D4SL-NSK10-LK-K Safety Switch
  • Siemens C98043-A7001-L24 CUD1 Control Board
  • Mitsubishi A2NCPUR21-S1 PLC Module
  • National Instruments NI-9242 4-channel analog input module
  • BEMAC UST-202-D PLC Interface Board
  • Omron CJ1W-DA08C Analog Output Module
  • Mitsubishi QX521 CNC Interface Board
  • Schneider BMEP586040 High-Performance PLC Processor
  • Emerson 5X00875G01 Process Control PLC
  • Siemens SIMODRIVE 611 Power Module 6SN1145-1AA01-0AA0
  • Siemens 840C NC-CPU 486DX4 6FC5110-0BB04-0AA1
  • Mitsubishi GT2708 Series Operation Panel Touch HMI
  • Fanuc A04B-0103-C220 Programmable Controller Module
  • IFM CR2530 Programmable Controller for Mobile Automation
  • Omron FH-3050 Vision Controller i7-2715QE High Performance
  • National Instruments NI-9242 4-Ch Analog Input Module
  • B&R X20AI4632 Analog Input Module 4 Channels
  • Pilz 773600 Input Module Safety Automation
  • Panasonic AFPX-C60P Programmable Controller PLC
  • Siemens 6ES7414-2XL07-0AB0 S7-400 CPU Manual
  • Cutler Hammer WM34V Interlock Kit Manual
  • Pilz 777587 Safety Relay Specifications
  • Omron CJ2H-CPU64-EIP CPU Module Manual
  • B&R X20AI1744-3 Analog Input Module Guide
  • Schneider LC1G185BEEA Contactor Specification
  • Sharp LM64P101 LCD Screen Specifications
  • B&R X20AT4222 Temperature Module Guide
  • Mitsubishi A2UCPU-S1 Controller Specifications
  • Stein Sohn E 083.1 Rack Module Technical Guide
  • Omron CK3W-AX1515N Motion Controller
  • Schneider TSXP572634M PLC Processor
  • Epson RAIOC-33 Programmable Controller
  • GRID T&D iRTUe-D1R1-W.125 I/O Module
  • Fanuc A20B-2002-0520 Control Board
  • B&R X20IF1030 Interface Module