Environment and installation specifications
1. Environmental parameters
Remarks on environmental category parameter values
Temperature working temperature (vertical installation) 0 ℃~+50 ℃-
Working temperature (maximum tilt angle) 0 ℃~+40 ℃ Maximum allowable tilt angle ± 35 ° (without external ventilation)
Storage/transportation temperature -20 ℃~+60 ℃-
Maximum relative humidity of 85% in non condensing environment
Front end protection level IP65 dustproof and waterproof, suitable for harsh industrial environments
Backend IP20 only prevents finger touch and needs to be installed inside the control cabinet
2. Installation and physical specifications
Specification Category Parameter Value Remarks
Installation method, installation technology, clamp terminals for easy fixation and disassembly
Front end dimensions (W × H) 212mm × 156mm-
Installation incision size (W × H) 198mm × 142mm control cabinet opening size
Equipment depth 45mm-
Weight Net weight 0.7kg Lightweight design for easy installation
certification standard
International certifications: CE certification, FM Class I Div.2 (hazardous area certification), UL certification, CSA certification;
Compliance: Complies with industrial control equipment safety and electromagnetic compatibility standards.