Storage conditions: anti-static bag+desiccant packaging, temperature and humidity according to semiconductor device storage standards (usually 5... 40 ° C, non condensing). Before installing long-term inventory devices, it is recommended to review the status of the gate power supply circuit and fiber end face;
Anti counterfeiting and traceability: Verify that the order number 3BHB020720R0002 on the packaging matches the device body identification, and retain the purchase serial number to support original factory quality traceability.
Troubleshooting Approach: From Phenomenon to Device
When a fault occurs in the medium voltage transmission equipped with the IGCT, it can be investigated according to the following levels:
Control level: If the receiving fiber is not properly plugged in or the end face is contaminated, it will result in an alarm of "device no response/trigger loss" - check the only receiving channel link used;
Gate power supply level: When the gate drive power supply is abnormal, the device cannot establish commutation. Check the output of the power unit gate power board;
Device level: The positive and negative characteristics between the anode and cathode are determined using a dedicated tester at low voltage (IGCT exhibits thyristor like blocking characteristics in the forward direction, and direct pressure testing is strictly prohibited when the gate is open), or using the measurement method specified by the original factory;
Thermal mechanical level: Repeatedly damaging components at the same location, with priority given to suspicion of insufficient crimping pressure, degraded heat dissipation interface, or uneven current distribution in the bridge arm;