(4) DP640 speed measurement module. Two channel speed measurement, specifically designed for monitoring the rotational speed of steam turbines. The main channel has a sampling interval of 5 ms, a measurement time of up to one full revolution (such as 20 ms), a 14 bit resolution, an input pulse frequency of up to 50 kHz, and an output frequency lower limit of 0.03 Hz. It accepts three types of signals: 24V analog (such as eddy current probe), 5V TTL, and 5V differential (RS485). Two measurement modes: High Precision ON, measure with one full rotation of the gear disc (high precision), OFF, measure with the MEAs_PER set cycle (1-100 ms, fast mode).
The safety function system of DP640 is the most complete: the trip signal is generated by a dedicated fault safety output when the main channel overspeeds (HI_LIM2 defaults to 110%) or equipment fails (READYOP=0, ERR=1) - the transistor output (pins 7-8) changes to a high impedance of 24V, and the trip relay loses power (2-3 closed, 3-4 open). The tripping delay depends on the measurement cycle: up to 10 ms at 3000 rpm, HIGHPREC=1, H2=110%. Overspeed monitoring can be tested online: after setting the test position (ORD-VAL), DELTAVAL (default 20%) increment is added to the monitoring path, and the actual measurement value is not affected. Gradient supervision (MAX_GRAD default 1%/s) filters measurement glitches caused by EMI. If the disturbance persists for more than 5 measurement cycles, it is determined that the sensor is faulty and a trip signal is generated; If there is no pulse for 5 consecutive cycles (cable breakage), trip will be triggered. If there is no pulse for 30 seconds, the speed output will be 0 and trip will be reset. Sensor signal quality supervision includes minimum peak to peak value (1 Vpp for 24 V input, 0.66 Vpp for TTL, 0.33 Vpp for RS485), active zero point (UA379 transmitter), and upper and lower limits of eddy current probe distance (UT386: low level<-19 V, high level>-1.5 V alarm). The sensor power output+24/-24/12/5 V is monitored for open circuit (>5 mA considered OK) and overload (>50 mA error). Configuration restriction: DP640 can only be configured in one processor module (or two redundant processor modules), otherwise it will be periodically reconfigured and the tripping relay will repeatedly operate.
(5) DX610 relay output module. Mainly used as a trigger actuator for driving protection equipment in boiler protection systems (in conjunction with PM646 processor module). 6 identical functional units, each containing 3 isolation relay contacts (terminals USxF/USxX/ZPx/UVx/AxZ/AxA/AxX, x=1-6), supporting 2-out-3 disconnection operation; Each unit is equipped with an independent relay to form a second tripping circuit, which is triggered by PM646 through a dedicated hard wired input (KN/KP). The relay status can be read back through auxiliary contacts (RM1/RM2). The process voltage UP of each functional unit is independently monitored, and when the voltage is too low, it is indicated by the DB element. Contact rated 60 V DC/2 A fast action, contact rated power 120 W, isolation between output channels and system output is 560 Vrms/1500 Vrms respectively. Unlike 81AR01, this module does not have a built-in actuator power supply fuse, and the output is protected by a zero diode. There are 19 LEDs on the front panel, one for RUN/AULT, with the first 8 yellow lights indicating input status and the last 8 yellow lights indicating output status. The dedicated PC element (PC_SX610) is used for the operation and inspection of the boiler protection system, and the AX646 is also equipped with the PC_SX646 element.
Troubleshooting of Bus Expansion and Communication Module
CI615/CI610 expansion bus pair. CI615 is installed in the Basic Station, and CI610 is installed in the first two slots of each I/O Station (single unit must be in slot 1), interconnected through TK610 bus extension cables (2.5/5/10m three specifications), with a total cable length of no more than 20 meters. The topology must be point-to-point, and branching or radiating connections are not allowed; The terminal I/O station needs to be equipped with TC610 terminator - the extension bus cannot work without a terminator; CI615 contains a proximal end connector. The switching of redundant configuration (two CI615+two CI610 per station+two cables) is completed within 100 ms; The system software periodically switches between primary and backup to verify the effectiveness of redundancy.
The three state mechanism is the diagnostic basis: RESET (after power on or reset), PASSIVE (not communicating with other stations but the OSP watchdog is still active - even if both redundant CI610s are passive, the OSP signal can still be activated), and ACTION (normal transmission). The supervision function of CI610 covers: the module's own power supply (if it is too low, it will remain in a reset state and the FAILT red light will be on), the USA/USB power supply voltage (if it is below 17-15V, an error will be reported but the FAILT red light will not be on), and data transmission supervision (CI610 will stop running when there is a serious transmission error). I/O bus extension cable open circuit monitoring: DB element ERR is activated when the cable is interrupted or not terminated. The station address must be set to 1-7 and unique.