3.3 S5: Selection of constant current source for temperature sensor
Determine whether the onboard constant current source outputs 1.5mA or 5mA.
PTC (Thermistor): Usually uses a small current or a specific voltage divider network.
PT100 (Platinum Resistance): Standard PT100 temperature measurement typically requires a constant current source of around 5mA. If the configuration is incorrect here, the temperature read by the software will deviate significantly from the actual temperature (such as displaying several hundred degrees or minus tens of degrees).
3.4 S10: Input characteristics of pulse encoder
Used to configure the signal type (single ended or differential) and input threshold of the encoder.
Differential mode: has the strongest anti-interference ability and is suitable for long-distance transmission.
Single ended mode: typically used for low-cost connections over extremely short distances. Incorrect jumper settings can cause the system to be unable to read pulses and display a speed of zero.
Practical Specification for Installation and Wiring
4.1 Cable length and shielding
Due to the frequent use of SDCS-IOB-3 as an external board card in the chassis, it is connected to the main control board through a flat cable. Strict adherence to electromagnetic compatibility (EMC) requirements is required during installation:
The length of the flat cable between the board and the CON-2 control board is usually limited to between 0.5 meters (X1/X3 interface) and 1.7 meters (X1/X2 interface), and excessive length can introduce high-frequency interference.
Encoders and analog inputs must use twisted pair shielded wires. The shielding layer needs to be grounded at one end (usually on the grounding bar of the inverter cabinet), and it is strictly prohibited to form a ground loop.
4.2 Polarity of temperature detection
If connecting PT100 or PTC, it is necessary to ensure correct polarity. Usually, the board will provide reference ground or constant current source outflow/reflux terminals. Loose wiring can cause severe fluctuations in temperature sampling values.
Common troubleshooting strategies
When the new version of SDCS-IOB-3 is replaced or abnormal alarms occur during equipment operation, engineers should follow the following logic to troubleshoot:
5.1 Fault phenomenon: Upon power on, it reports "TACHO FAULT" or the speed is out of control
Investigation direction 1: The jumper has not been replicated. Check if S4 (encoder power supply) and S10 (differential/single ended mode) are completely consistent with the old board. If the old board is powered by 24V and the new board defaults to 5V, the speed measurement signal will not be read properly.
Troubleshooting direction 2: Reverse wiring. If the encoder's A and A -, or B and B - are connected in the opposite direction, the system will read the speed direction completely opposite, or it will directly accelerate during closed-loop control.
Investigation direction 3: Power supply inspection. Use a multimeter to measure the voltage at the encoder terminals and confirm if it has reached the design value. If the internal isolation power supply of the new board is damaged, it will cause the encoder to have no power supply.
5.2 Fault phenomenon: No response or numerical drift given by analog quantity
Troubleshooting direction 1: Voltage/current jumper conflict. The on-site upper computer provides a 4-20mA signal, but the S1/S2 jumper of the new board is set to voltage input (such as 10V). At this time, the input impedance is extremely high, and the current cannot form a loop, resulting in a reading of zero.
Investigation direction 2: Zero point and gain calibration. The old board may have fine tuned potentiometers (depending on the version) or have been calibrated in the software. After replacing the new board, although the hardware parameters are consistent, due to the discreteness of electronic components, it may be necessary to re adjust the zero/full range on the DCS software end.
Troubleshooting direction 3: Common mode interference. Check if the negative pole of the on-site analog signal is reliably connected to the AGND (analog ground) of the board.
5.3 Fault phenomenon: Abnormal temperature display or reporting "Motor Overtemp"
Troubleshooting direction 1: The constant current source jumper (S5) is set incorrectly. If using PT100, check if it is set to the wrong current gear.
Troubleshooting direction 2: Open or short circuit in wiring. Disconnect the temperature sensor at the motor end and measure its resistance. If it is PTC, the resistance value is smaller at room temperature; If it is PT100, it is about 100 ohms at room temperature. If the resistance value is infinite, it indicates that the sensor cable is broken.
5.4 Fault phenomenon: Communication or functional abnormalities (signal jump) after replacement
Confirm whether the ribbon cable is securely plugged in and whether the foolproof buckle is locked properly.
Check if the grounding column of the board is connected to the cabinet backplane with low impedance. The accumulation of static electricity in high-rise buildings or dry environments can easily penetrate the optoelectronic isolation devices on the board.