If the voltage is not established, perform magnetization operation and reset the overexcitation shutdown circuit (power off for 1 minute).
Slowly adjust VLT ADJ to rated voltage.
Check stability: Increase or decrease load, observe voltage fluctuations and recovery time.
Adjust UF KNEE to activate the under frequency protection at the correct turning point.
If running in parallel, add droop CT and adjust DRP to balance reactive power distribution.
Simple functional test (detached from the generator, using the test circuit shown in Figure 9):
Apply the corresponding test voltage to the regulator (see Table 2, for example, AVC63-12A1 is 120Vac/50Hz), and connect the bulb and resistor in series as the load between F1-F2.
Rotate VLT ADJ counterclockwise to the bottom, the light bulb should turn off; Rotate clockwise until the light bulb lights up, then retract to the critical point of extinguishing, indicating that the regulator is basically normal.
Common fault phenomena and troubleshooting logic
Possible causes and solutions for malfunction phenomena
Voltage cannot establish residual magnetism deficiency or polarity reversal; Overexcitation shutdown action; Excitation circuit open circuit shutdown magnetization; Power off for 1 minute to reset; Check F1/F2 wiring and exciter field resistance
The voltage is too high or too low, and the VLT ADJ adjustment is ineffective. The remote voltage regulator potentiometer is wired incorrectly or short circuited; FAC CAL was mistakenly activated to confirm 4-7 short circuit status; Check the external voltage regulation circuit; Recalibrate FAC CAL
Voltage oscillation (hunting) STB setting too small (too much counterclockwise); The prime mover governor is unstable. Rotate the STB clockwise until it stabilizes; Check the prime mover speed regulator
Uneven distribution of reactive power during parallel operation, drooping CT polarity reversal or inconsistent DRP setting; Check CT polarity for mismatched sag coefficients of each machine (terminal 5/5A); Unified adjustment of DRP to make the reactive current of each machine proportional to the same load
When the load changes, the voltage drops severely and the frequency inflection point is set too high; Activate the excitation limiter to lower the UF KNEE turning point; Check the EL 200 setting value
External voltage regulation is ineffective. The external potentiometer wiring is incorrect or the resistance value does not match. Confirm that terminals 6a-7 are connected to 10k Ω, and the panel VLT ADJ has been turned clockwise to the maximum
Maintenance and spare parts replacement suggestions
Regular inspection: Check the wiring terminals for looseness every six months, remove dust, and measure whether the excitation voltage and current between F1-F2 are within the rated range.
Overexcitation shutdown test: It can simulate excitation overcurrent and verify whether the shutdown action time conforms to the curves in Figure 3 and Figure 4 (AVC63-12 shuts off in about 10 seconds at 125Vdc and about 1 second at 210Vdc).
Replacement selection: If the original system uses the earlier AVC63-7 or AVC125-7, this new model can be directly replaced, but the input voltage range and output capacity need to be checked. If PMG (permanent magnet generator) excitation is used on site, it is necessary to confirm that the power input comes from PMG rather than the main output. This regulator supports PMG input.
Storage: For long-term backup, it is recommended to power on every six months to maintain the performance of the internal electrolytic capacitor.
